P menus for installer.
Menus without minimum and maximum values are read-only menus.
Menu P3 Setting ventilation programmes
Ventilation programme values
Sub-menu Description
Minimum Maximum Factory reset
P30
P31
P32
P33
P34
P35
P36
P37
Setting the capacity (in %) of the exhaust fan in
absent setting.
0% or
15%
97%
98%
99%
100%
97%
98%
99%
100%
nL / HL
15% / 15%
Setting the capacity (in %) of the exhaust fan in low
setting.
16%
17%
18%
nL / HL
35% / 40%
Setting the capacity (in %) of the exhaust fan in
normal setting.
nL / HL
50% / 70%
Setting the capacity (in %) of the exhaust fan in high
setting.
nL / HL
70% / 90%
Setting the capacity (in %) of the supply fan in absent
setting.
0% or
15%
nL / HL
15% / 15%
Setting the capacity (in %) of the supply fan in low
setting.
16%
17%
18%
nL / HL
35% / 40%
Setting the capacity (in %) of the supply fan in normal
setting.
nL / HL
50% / 70%
Setting the capacity (in %) of the supply fan in high
setting.
nL / HL
70% / 90%
P38
P39
Current capacity (in %) of the exhaust fan.
Current capacity (in %) of the supply fan.
-
-
-
-
Current %
Current %
Menu P4 Reading temperatures
Temperature values
Sub-menu
Description
Minimum
Maximum Factory reset
P40
Current value of TAH
-
-
Current ˚ C
(Optional)
(= Temperature of the Post-heater)
P41
P44
P45
Comfort temperature
n/a
12 ˚C
28 ˚C
20 ˚C
-
-
-
-
Current ˚C
Current ˚C
Current value of T1
(= Outside air temperature)
P46
P47
P48
P49
Current value of T2
-
-
-
-
-
-
-
-
Current ˚C
Current ˚C
Current ˚C
Current ˚C
(= Supply air temperature)
Current value of T3
(= Stale air temperature)
Current value of T4
(= Exhaust air temperature)
n/a
All temperatures are in degrees Celsius (°C). In the back of this document you
can find an conversion table. (°F = °C × 1.8 + 32)
18 - EN