Ground Fault Circuit Interrupter (GFCI)  
This thermostat has a built-in GFCI function that protects people from  
electric shock. It is very important to check whether the GFCI function is  
normal or not every month. Here are the check steps:  
1.Confirm that the thermostat is turned on.  
2.Press the [Test Monthly] button. If a red light appears in the upper left  
corner of the thermostat and GROUND FAULT appears on the screen, the  
GFCI function is normal. If there is no response, it means the function is  
invalid, please contact the dealer or electrical installer.  
Note: Do not press and hold the [Test Monthly] button.  
3.Press the [Reset] button. The red light is off and the screen shows the  
power off state.  
4.Press the [Reset] button again. The thermostat is turned on.  
If in daily use, the red light is on and the screen appears GROUND FAULT.  
Then you need to check if the ground fault is present by pressing the  