Home > VENSTAR > VENSTAR Fan Coil Thermostat T2100 / T2150 User Guide

VENSTAR Fan Coil Thermostat T2100 / T2150 User Guide

Troubleshooting  
Use the following troubleshooting guide to diagnose common  
problems.  
Problem  
Possible Cause  
Solution  
Display won’t turn on  
Lack of proper power  
Make sure that the fancoil  
unit is powered.  
Check for 24 VAC between  
R and C at backplate  
Cooling won’t turn on  
Heating won’t turn on  
The cool setpoint  
is set too high  
Lower the cool setpoint,  
minimum setpoint limit  
or reduce deadband  
The heat setpoint  
is set too low  
Raise the heat setpoint,  
maximum setpoint limit or  
reduce deadband  
Two pipe auto changeover  
fancoil shows heat  
with chilled water or  
cool with hot water  
Water changeover switch  
not installed or  
incorrect type  
Contact Venstar for proper  
changeover switch (closed  
below 60F, open above 75F)  
2 pipe water valve  
won’t open in heat or cool  
Valve not wired  
to Y1 terminal  
Check wiring  
4 pipe hot water  
valve open with  
no heat demand  
Valve might be  
‘power to close’ type  
Check with fancoil  
manufacturer before  
altering ‘Hot Water  
Valve Type’ setting  
(continued)  
12  