TIME O STAT 2 Channel 3 Wired HMO Thermostat Installation Guide
Q. Low battery symbol is showing?
•
Remove the batteries, then press a few buttons to clear
any charge from the memory, wait for 30 seconds. Then
replace the batteries with new AA high performance
batteries.
•
Low battery levels may be insufficient for radio
frequency signal to operate correctly
Q. Heating is on when it should be off?
•
RESET the unit by holding the right hand side red +
and blue - temperature buttons for 3 seconds. This may
have not been done following an advanced settings
change.
•
•
Check hot water usage is not being called for that
would result in the boiler running.
Check RF interference from another Time:o:stat. - If
there is another Time:o:stat in close proximity then each
Time:o:stat should be set to a different RF channel and
then reset following the change. (A step by step guide to
change the RF channel is in section 5.)
•
Time:o:stats are factory paired and do not require
pairing. Changing the RF channel is only required if
there are more than one Time:o:stat in close proximity.
Is the wiring correct? – this should be checked by a
qualified person
Check mains voltage has not passed through the low
voltage contacts which may have damaged the unit
during installation. (Maximum switchable current is 2A).
•
•
Q. Heating is off when it should be on?
•
Check the boilers master thermostat is not too low.
If too low then the boiler will shut off the heating
regardless of the temperature selected on the
Time:o:stat.
•
Check the heating is set to 'constantly on' on the
boiler. If the heating is selected as off or on a separate
timer then the Time:o:stat will not operate during the
other timers ‘off’ periods.