Document No.129-076  
Installation Instructions  
March 14, 2022  
Changeover Point Adjustment  
Limit Stop Adjustment  
The changeover point is factory set to occur between 19  
and 22 psi (131 and 152 kPa). The changeover point can  
be field adjustable to occur between 14 and 22 psi (96 and  
152 kPa).  
Thermostat limit stops define the minimum and maximum  
thermostat set points. The limit stops engage in the set  
point cam gear teeth and cause interference between the  
set point cam gear and the adjustment knob gear.  
To change the limit stop settings, use a needle nose pliers  
to pull the limit stop (Figure 3) between the set point cam  
gear teeth. Do not pull limit stop any more than necessary  
to clear the gear teeth. Rotate the limit stop to its new  
position. Changing the limit stop position one gear tooth  
changes the limit stop setting by 1-1/3F (0.7C).  
1. Connect a pressure gauge or a manometer to measure  
the supply pressure to the thermostat. Use 30 psi  
(207 kPa) supply through a positioning switch so  
pressure can be fully variable.  
2. Determine the current change over point. Turn the  
cooling dial so that the cooling and heating control  
pressures are different. Then note the changeover  
point on the control gauge as the supply pressure  
changes.  
Sensitivity Adjustment  
The factory thermostat sensitivity setting is approximately  
2.5 psi/F (31 kPa/C). To change the sensitivity, use a flat  
blade screwdriver to carefully move the sensitivity slide  
(Figure 3) to the desired position as follows:  
3. Place an Allen wrench in the opening of the  
thermometer assembly (Figure 3) to adjust the  
changeover adjustment screw as follows:  
Graduation closest  
to the rigid end of  
the bimetal element  
4 psi/F (50 kPa/C)  
Graduation closest to  
the minimum (MIN) end  
of the bimetal element  
1 psi/F (12 kPa/C)  
a. If the changeover is too high, turn off the supply  
pressure and rotate the changeover adjustment  
screw clockwise. One turn decreases the  
changeover point by about 3 psi (20 kPa). Turn  
on the supply pressure and recheck to verify the  
new changeover point.  
NOTE:  
If the thermostat sensitivity is adjusted,  
recalibrate the thermostat.  
b. If the changeover is too low, turn off the supply  
pressure and rotate the changeover adjustment  
screw counterclockwise. One turn increases the  
changeover point by about 3 psi (20 kPa). Turn  
on the supply pressure and recheck to verify the  
new changeover point.  
Thermostat Calibration  
The thermostat is factory calibrated to a control pressure of  
7.5 psi (52 kPa) when the set point and the ambient  
temperature are both at 72°F (22°C). No adjustments are  
required if these settings are appropriate.  
If the thermostat has been tampered, the sensitivity  
changed, or it is out of adjustment, use the following  
procedures to recalibrate the instrument.  
The output pressure test port (Figure 4) is accessible  
without removing the thermostat cover through the 8th  
opening:  
For TH192 HC thermostats, the port is on the left side.  
CAUTION:  
If you use the wrong test port, thermostat  
damage can occur and result in  
replacement of the device.  
Figure 3. TH192 HC Thermostat Details.  
Cooling Calibration  
1. Remove the cover using the calibration tool.  
Verify that the room temperature is between 70 and  
80F (21 and 27C).  
2. Verify that the supply pressure is 18 psi (124 kPa).  
Set the cooling dial to the room temperature by turning  
the exposed adjustment knob or using a hex key. Allow  
the thermostat to stand for about five minutes to adjust  
to the new setting.  
Figure 4. TH192 HC Output Pressure Test Port  
.
Siemens Industry, Inc.  
Page 3 of 4  
GeneralDetails
NameSIEMENS TH192 HC Heating-Cooling Room Thermostat Instruction Manual
MakeSIEMENS
LanguageEnglish
FiletypePDF (Download)
File size0.09 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual

SIEMENS TH192 HC Heating-Cooling Room Thermostat Instruction Manual