TH 192 DN Day-Night and DNV Day-Night-Vent Room Thermostat
Operation
Day-Night Operation
The TH 192 DN thermostat is either direct or reverse acting for both day and night
operating modes. In a direct acting thermostat, an increase in temperature increases
the control air pressure, and a decrease in temperature decreases the control pressure.
In a reverse acting thermostat, an increase in temperature decreases the control air
pressure, and a decrease in temperature increases the control pressure.
The TH 192 DN provides two separate bimetal elements: one for day temperature and
one for night temperature. Each bimetal element operates independently of the other.
Use of two different supply air pressures accomplishes changeover from day to night
temperature. A supply pressure of 18 psi (124 kPa) or 25 psi (172 kPa) positions a
changeover switch so a changeover relay operates in the day or night mode,
respectively.
Figure 5. TH 192 DN and DNV Input/Output Characteristics.
Manual Selector Switch
A manual selector switch allows an individual thermostat to control at its day setting
even though the remainder of the system is controlling at its night setting.
•
In the normal AUTO position, the manual selector switch does not interfere with air
passage to the changeover relay.
•
To manually set the selector switch to the DAY position, push the selector in until it
latches and the handle points downward. In the latched DAY position, the manual
selector switch seals off air to the changeover relay.
•
•
To manually reset the selector switch, rotate the handle until it unlatches and returns
to the normal AUTO position.
Manual Selector Switch resets automatically when supply pressure changes back to
day time control.
Day-Night-Vent
Operation
The TH 192 DNV provides a supplementary air line connection at the back of the
thermostat.
NOTE: This third line feature cannot be added to a TH 192 DN in the field.
The vent line provides either 0 or 25 psi (0 or 172 kPa) pressure via the manual selector
switch to pilot auxiliary controls. For example, a unit ventilator can provide continuous
full day operation when the space is occupied and intermittent night operation when the
space is unoccupied.
Page 6
Siemens Industry, Inc.
| General | Details |
|---|---|
| Name | SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual |
| Make | SIEMENS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.16 MB |

SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual

SIEMENS M3182 Room Thermostat Instruction Manual

SIEMENS RDS120-B Smart Thermostat Instructions

SIEMENS RDG400 Room Thermostat Instruction Manual

SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual

SIEMENS RDH100RF/SET Room Thermostat Instruction Manual

SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide

SIEMENS RS485 Flush Mounted Room Thermostat User Manual

SIEMENS RDG260KN Room Thermostat Instruction Manual

SIEMENS RDF660MB Flush Mount Room Thermostat Instruction Manual