TH 192 DN Day-Night and DNV Day-Night-Vent Room Thermostat  
Operation  
Day-Night Operation  
The TH 192 DN thermostat is either direct or reverse acting for both day and night  
operating modes. In a direct acting thermostat, an increase in temperature increases  
the control air pressure, and a decrease in temperature decreases the control pressure.  
In a reverse acting thermostat, an increase in temperature decreases the control air  
pressure, and a decrease in temperature increases the control pressure.  
The TH 192 DN provides two separate bimetal elements: one for day temperature and  
one for night temperature. Each bimetal element operates independently of the other.  
Use of two different supply air pressures accomplishes changeover from day to night  
temperature. A supply pressure of 18 psi (124 kPa) or 25 psi (172 kPa) positions a  
changeover switch so a changeover relay operates in the day or night mode,  
respectively.  
Figure 5. TH 192 DN and DNV Input/Output Characteristics.  
Manual Selector Switch  
A manual selector switch allows an individual thermostat to control at its day setting  
even though the remainder of the system is controlling at its night setting.  
In the normal AUTO position, the manual selector switch does not interfere with air  
passage to the changeover relay.  
To manually set the selector switch to the DAY position, push the selector in until it  
latches and the handle points downward. In the latched DAY position, the manual  
selector switch seals off air to the changeover relay.  
To manually reset the selector switch, rotate the handle until it unlatches and returns  
to the normal AUTO position.  
Manual Selector Switch resets automatically when supply pressure changes back to  
day time control.  
Day-Night-Vent  
Operation  
The TH 192 DNV provides a supplementary air line connection at the back of the  
thermostat.  
NOTE: This third line feature cannot be added to a TH 192 DN in the field.  
The vent line provides either 0 or 25 psi (0 or 172 kPa) pressure via the manual selector  
switch to pilot auxiliary controls. For example, a unit ventilator can provide continuous  
full day operation when the space is occupied and intermittent night operation when the  
space is unoccupied.  
Page 6  
Siemens Industry, Inc.  
GeneralDetails
NameSIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
MakeSIEMENS
LanguageEnglish
FiletypePDF (Download)
File size0.16 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual
SIEMENS RDF660MB Flush Mount Room Thermostat Instruction Manual
SIEMENS RDF660MB Flush Mount Room Thermostat Instruction Manual

SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual