SIEMENS 194-2042 Pnuematic Room Thermostat User Guide

356 Limitem™Rigid Bulb Thermostats  
188 Unit M ounted Thermostats  
Features  
Features  
Durable copper motor tube and 18” (457mm)  
steel rod temperature sensing element.  
Two-valve design reduces air waste.  
Liquid-filled thermal system  
temperature sensing element.  
Durable die-cast metal case  
with rugged setpoint knob.  
Direct or reverse acting models.  
Duct mount hardware included.  
Rugged, all metal construction.  
Adjustable sensitivity.  
Universal mounting bracket for  
easy installation.  
Applications  
Integral adjustable limit stops.  
The 356 Limitem™Rigid Bulb Thermostat provides  
primary control for unit ventilators, fan coils and  
other air handling units. This device can also be  
used as low limit control for air flow to a controlled space.  
Applications  
The 188 Unit Mounted Thermostats are designed primarily for use in  
fan coil induction units and unit ventilators to control the temperature  
within an occupied space. The thermostat’s temperature range is  
limited to applications at ambient temperatures.  
Available in three temperature operating ranges:  
0 to 100 °F (-18 to +38°C)  
30 to 180°F(-1 to +82°C)  
100 to 250°F(38 to 121°C)  
Available with three control actions:  
Direct Acting only (Heating)  
Reverse Acting only (Cooling)  
Click on this link for 356 Limitem Rigid Bulb Technical Instructions  
Heat or Cool depending on supply air pressure  
Click on this link for 188 Unit Mount Thermostat Technical Instructions  
134 Pneumatic High and Low  
357 D Limitem™Remote Bulb Thermostats  
Temperature Detection Thermostats  
Features  
Features  
Direct acting operation only.  
Remote or averaging bulbs for  
Snap-acting pneumatic switch.  
Sight-set calibrated setpoint scale.  
flexibility in installation  
.
No leakage of air prior to reset of  
switch  
Liquid-filling sensing element  
for rapid response to changes  
in temperature.  
Easily adju.stable settings.  
Normally closed air valve; bleeds to  
less than 2 psi (14 kPa) when supplied  
through a restrictor.  
Two-valve design reduces air  
waste.  
Adjustable sensitivity.  
Applications  
Applications  
The 134 Pneumatic High and Low Temperature Detection Thermostats  
are used on pneumatic heating and cooling systems in areas protected  
from the weather.  
The 357 D Limitem Remote Bulb Thermostat provides primary  
monitoring and control for air handling units or a low limit control.  
Available in three temperature operating ranges:  
On a typical high limit application, the thermostat shuts down air  
conditioning or ventilating fans when the duct temperature becomes  
excessively high. A normally closed switch opens at setpoint.  
Averaging Bulb Model: 35 to 145°F(2 to 63°C)  
Remote Bulb Model: 20 to 100°F(-7 to +38°C)  
Remote Bulb Model: 120 to 230°F(48.9 to 110°C)  
On a typical high limit application, the thermostat stops the fan or  
closes a damper when the temperature drops to the setpoint at any  
one foot (30.5 cm) or more of the sensing element.  
Click on this link for 357 D Limitem Remote Bulb Technical Instructions  
Click on this link for 134 High-Low Temp Detect Technical Instructions  
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design  
improvements are introduced. POWERS is a trademark of Siemens Industry Inc. Product or company names mentioned herein may be the trademarks of  
their respective owners. © 2017 Siemens Industry, Inc.  
Siemens Industry, Inc.  
Building Technologies Division  
1000 Deerfield Parkway  
Buffalo Grove, IL 60089-4513  
USA  
Your feedback is important to us. If you have  
comments about this document, please send them to  
Document No. A6V112210116  
Printed in the USA  
Page 4 of 4  
+ 1 847-215-1000  
GeneralDetails
NameSIEMENS 194-2042 Pnuematic Room Thermostat User Guide
MakeSIEMENS
LanguageEnglish
FiletypePDF (Download)
File size0.12 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual

SIEMENS 194-2042 Pnuematic Room Thermostat User Guide