Wiring Diagrams  
For conventional heating and cooling systems, refer to pages 8–9.  
For heat pump systems, refer to pages 10–11.  
For two-pipe fan coils, refer to pages 12–13.  
For four-pipe fan coils, refer to pages 14–15.  
For zone damper control, please see the separate installation guide for Zone  
Damper Control.  
For installations not covered in this guide, STOP INSTALLING THE  
THERMOSTAT and contact Pelican Sales Engineering Support for further  
assistance at 888-512-0490.  
24 VAC Terminal Block Designations  
Conventional  
Heat Pump  
DATA  
DATA  
D
C
R
D
C
R
COMMON  
COMMON  
24 VAC POWER  
24 VAC POWER  
Y
W
Y
W
COOL STAGE 1  
HEAT STAGE 1  
FAN  
COMPRESSOR STAGE 1  
REVERSING VALVE (O/b)  
FAN  
G
G
W2  
Y2  
W2  
Y2  
HEAT STAGE 2  
COOL STAGE 2  
AUXILIARY HEAT  
COMPRESSOR STAGE 2  
Two-Pipe Fan Coil  
Four-Pipe Fan Coil  
DATA  
DATA  
D
C
R
D
C
R
COMMON  
24 VAC POWER  
COMMON  
24 VAC POWER  
Y
W
Y
W
VALVE OPEN  
UNUSED  
CHILLED VALVE OPEN  
HOT VALVE OPEN  
FAN  
G
G
FAN  
W2  
Y2  
W2  
Y2  
AUXILIARY HEAT  
VALVE CLOSE  
HOT VALVE CLOSE  
CHILLED VALVE CLOSE  
8
GeneralDetails
NamePELICAN TC1 Commercial Connected Thermostat Installation Guide
MakePelican
LanguageEnglish
FiletypePDF (Download)
File size0.32 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PELICAN TC4 Commercial Connected Thermostat Installation Guide
PELICAN TC4 Commercial Connected Thermostat Installation Guide
PELICAN TC3 Commercial Connected Thermostat Installation Guide
PELICAN TC3 Commercial Connected Thermostat Installation Guide

PELICAN TC1 Commercial Connected Thermostat Installation Guide