PELICAN TC1 Commercial Connected Thermostat Installation Guide
Wiring Diagrams
For conventional heating and cooling systems, refer to pages 8–9.
For heat pump systems, refer to pages 10–11.
For two-pipe fan coils, refer to pages 12–13.
For four-pipe fan coils, refer to pages 14–15.
For zone damper control, please see the separate installation guide for Zone
Damper Control.
For installations not covered in this guide, STOP INSTALLING THE
THERMOSTAT and contact Pelican Sales Engineering Support for further
assistance at 888-512-0490.
24 VAC Terminal Block Designations
Conventional
Heat Pump
DATA
DATA
D
C
R
D
C
R
COMMON
COMMON
24 VAC POWER
24 VAC POWER
Y
W
Y
W
COOL STAGE 1
HEAT STAGE 1
FAN
COMPRESSOR STAGE 1
REVERSING VALVE (O/b)
FAN
G
G
W2
Y2
W2
Y2
HEAT STAGE 2
COOL STAGE 2
AUXILIARY HEAT
COMPRESSOR STAGE 2
Two-Pipe Fan Coil
Four-Pipe Fan Coil
DATA
DATA
D
C
R
D
C
R
COMMON
24 VAC POWER
COMMON
24 VAC POWER
Y
W
Y
W
VALVE OPEN
UNUSED
CHILLED VALVE OPEN
HOT VALVE OPEN
FAN
G
G
FAN
W2
Y2
W2
Y2
AUXILIARY HEAT
VALVE CLOSE
HOT VALVE CLOSE
CHILLED VALVE CLOSE