Limited Wire Installation
In some installations, there may be
limited wiring between the thermostat
and the HVAC equipment. The
Wiring Module
included Wiring Module allows control
of the HVAC system without the need
to install new or additional wires.
This setup requires at least three (3)
wires between the thermostat and the
Wiring Module (unshielded wire is
acceptable).
It supports a maximum distance of
500 feet between the Wiring Module
and the thermostat.
Step 1: Remove the Wiring Module
from the thermostat’s back plate.
Loosen the (R), (C), and (D)
terminals on the Wiring Module.
Gently slide the Wiring Module
upwards, away from the three-pin
connector, to remove it.
Loosen
terminals.
Three pin
connector
Step 2: Install the Wiring Module in
the HVAC equipment.
Use a sheet metal
screw to secure the
Wiring Module.
Wiring Module
Locate the HVAC equipment’s
control board. Using new wire,
connect the Wiring Module’s
terminals to the corresponding
low-voltage input terminals on the
HVAC control board.
HVAC Control Board
Y2
W2
G
W
Y
Refer to the wiring diagrams on
Pages 8–15 for the most common
thermostat wiring.
R
C