PELICAN TC1 Commercial Connected Thermostat Installation Guide
Notes
1
Connect to 24 VAC class 2 circuits only.
2
3
Latching relays are rated for 24 VAC @ 2 amps continuous load.
All wire to be installed by customer in accordance with local electrical
codes.
3a
4
Use 18 gauge unshielded thermostat wire.
Only found for actuators that are 24 VAC floating type.
Troubleshooting
If the Pelican thermostat does not power on, check the following:
1. Check that all wires are properly inserted into the terminal blocks at the
thermostat and at the HVAC equipment. Lightly pull on the wires to make sure
they are not loose.
2. Use a multi-meter to ensure that 24 VAC power is being supplied by HVAC
equipment. If 24 VAC is not found, check that the master power has been
turned back on for the HVAC equipment or verify that the HVAC electrical
breaker has not tripped. If the breaker has tripped contact a Licensed
Professional to assist, otherwise damage can occur to the equipment or you can
get hurt.
3. Use a multi-meter to ensure that 24 VAC power is found at the thermostat. If
24 VAC was not found, but is found at the HVAC equipment, check for loose or
spliced wires.
4. If you used the Wiring Module, use a multi-meter to ensure that 24 VAC
power is found at the Wiring Module and the thermostat. Check that the (R), (C),
and (D) wires are properly connected between the Wiring Module and the
thermostat.
If the thermostat still does not power on, contact Pelican technical support for
further assistance at 888.512.0490.