Home > PECO > PECO T8168B-2 BACnet Proportional Thermostat Installation Guide

PECO T8168B-2 BACnet Proportional Thermostat Installation Guide

Typical ON-OFF Operation  
Typical Three-Wire Floating Operation  
24 VAC 1 (UNSWITCHED)  
24 VAC 1 (UNSWITCHED)  
24  
24  
24VAC  
XFMR  
24VAC  
XFMR  
24 VAC 2  
24 VAC 2  
24  
24  
24 VAC 2  
24 VAC 2  
24  
24  
COOL STAGE1  
HEAT STAGE 1  
COOL OPEN  
HEAT OPEN  
Y1  
W1  
Y2  
Y1  
W1  
Y2  
COOL STAGE 2  
OR FAN MED  
COOL STAGE 2  
OR FAN MED  
HEAT STAGE 2  
FAN HI  
HEAT CLOSE  
FAN HI  
W2  
G
W2  
G
FAN LO  
OR DAMPER  
FAN LO  
OR DAMPER  
G1  
YD  
WD  
GD  
G1  
YD  
WD  
GD  
0-10 VDC OR  
4-20 mA COOL  
0-10 VDC OR  
4-20 mA COOL  
0-10 VDC OR  
4-20 mA HEAT  
0-10 VDC OR  
4-20 mA HEAT  
0-10 VDC OR  
4-20 mA FAN  
0-10 VDC OR  
4-20 mA FAN  
OPTIONAL REMOTE PROBE  
OPTIONAL PIPE SENSOR  
OPTIONAL REMOTE PROBE  
OPTIONAL PIPE SENSOR  
S1  
S2  
SC  
S1  
S2  
SC  
DC / SENSOR COMMON  
RS485A (-)  
DC / SENSOR COMMON  
RS485A (-)  
4A  
4B  
4C  
4A  
4B  
4C  
RS485B (+)  
RS485B (+)  
RS485 COMMON  
RS485 COMMON  
BACnet® Communication  
The T8168B-2 Thermostat is equipped with BACnet® IP or MS/TP wired Connections.  
More detailed information is available using the QR code provided  
BACnet® IP Communication  
This thermostat will broadcast a Wi-Fi network on power up. From your device Wi-Fi The network will  
appear as “T8168 #####”. Select this network and enter Password: 12345678, then press connect. Next  
Sign-In to open the BACnet Configuration Page at IP Address 10.10.0.1 on the T8168XXXX network.  
More information is available on our website.  
MS/TP Wired Connections  
Recommended wiring specification  
22 -24 AWG Shielded twisted pair, Low Capacitiance  
Installation  
1. Care must be taken to ensure that the communication wiring does not touch the Shield/Ground.  
2. Do not connect the Shield/Ground to earth ground or the controllers power ground.  
3. Care should be taken to assure that polairty is maintained for all connections with shared power  
4. This controller does not have an EOL termination or biasing.  
- 4A  
+ 4B  
5. Terminal 4A is Negative, 4B is positive and 4C is ground  
6. When complete this thermostat will be part of a system that is not controlled by PECO.  
Follow system equipment specifications for approporate installation.  
Shield 4C  
Visit: pecocontrolsystems.com for additional information.  
© COPYRIGHT 2024 PECO, INC. ALL RIGHTS RESERVED.  
P/N 74599 3220-2406 REV 00  
8
GeneralDetails
NamePECO T8168B-2 BACnet Proportional Thermostat Installation Guide
MakePECO
LanguageEnglish
FiletypePDF (Download)
File size0.42 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PECO T8168 Performance Pro Thermostat Installation Guide
PECO T8168 Performance Pro Thermostat Installation Guide
PECO T372P Thermostat Instruction Manual
PECO T372P Thermostat Instruction Manual
PECO TW180 Thermostat Instruction Manual
PECO TW180 Thermostat Instruction Manual

PECO T8168B-2 BACnet Proportional Thermostat Installation Guide