System Fan Type  
0 = On/Off Fan (Default)  
0: Uses available fan speeds per Service Menu 110  
1: Uses GD output for 0-10 VDC fan*. User selection of speed.  
HI Speed is set at SM 125-126,LO speed is set at SM 127, MED is set between HI-LO.  
2: Uses GD output for 0-10 VDC fan*.  
Modulates between Min and Max selections in SM 125-127*.  
*Damper Output is Available at (G1) and runs per SM 111  
1 = 0–10VDC FAN Hi-MED-LO Fan  
2 = Proportional 0-10VDC Fan  
0-10 VDC Fan Ramping  
0 to 3 Minutes, 30 sec Increments  
(Default 1:00)  
Sets how long it takes for the fan to transition between 0 VDC and 10 VDC when  
SM112=1 or 2. The duration will be shorter if SM125 or SM126 are less than 10 VDC.  
114  
120  
Valve Stoke Time  
30 Sec To 5 Min (Default 120)  
0 – OFF for Heating (Gas/Oil Heat)  
1= Electric Furnace (DEFAULT)  
0 = 4 – 20mA  
Set the amount of time for a TWF valve to go from fully closed to fully Open.  
Fan Control (Heating)  
0: The thermostat will not activate the fan with a heating demand.  
1: The thermostat will activate the fan with heat demand.  
122  
YD Output Configuration  
WD Output Configuration  
Configures digital cooling output for 0-10VDC or 4-20mA DC  
Configures digital heating output for 0-10VDC or 4-20mA DC  
1 = 0 – 10 Volts (DEFAULT)  
0 = 4 – 20mA  
1 = 0 – 10 Volts (DEFAULT)  
123  
124  
GD Output Configuration  
0 = 4 – 20ma  
Configures digital fan output for 0-10VDC or 4-20mA DC  
1 = 0 – 10 Volts (DEFAULT)  
125  
126  
127  
135  
GD Max Voltage, Heating  
Demand  
6 – 10 VDC (Default: 8)  
12 – 20 mA (Default: 20)  
Depending on SM 124 setting, sets Fan HI speed voltage or current (mA) at terminal GD  
with demand for Heat.  
GD Max Voltage, Cooling  
Demand  
6 – 10 VDC (Default: 10)  
12 – 20 mA (Default: 20)  
Depending on SM 124 setting, sets Fan HI speed voltage or current (mA) at terminal GD  
with demand for Cool.  
GD Min Voltage  
0 – 6 VDC (Default: 2)  
4 – 12 mA (Default: 4)  
Depending on SM 124 setting, sets Fan LO speed voltage or current (mA) at terminal GD  
with no demand.  
W1 Output Configuration  
0 - NC: Normally Closed Operation (Default)  
1 - NO: Normally Open Operation  
Reverses the ON/OFF operation for W1. NC operation powers on with a demand. NO  
opreation powers off with a demand and will be on with no demand unless main power is  
removed from the thermostat.  
170  
171  
S1 Remote Sensor Input  
S2 Pipe Sensor  
0
=
N
o
R
e
m
o
t
e
S
e
n
s
o
r
s
(
D
e
f
a
u
l
t
)
0: Remote temperature sensing is disabled.  
1: The T8168 uses the remote sensor only for temperature sensing.  
2: The T8168 averages the local and remote sensor for temperature sensing.  
When using a remote sensor an open or short will turn off outputs and display either  
2Ero(open) or 2Erc (closed). Fault detection settings are not used.  
1= Remote Indoor Sensor Connected  
2 = Remote Sensor Connected And Sensor  
Averaging  
0 – Disabled (Default)  
1 – Two Pipe Operation  
Enables fan coil pipe sensor operation. Connect a PECO pipe sensor or dry switch closure  
for change over from Summer (cold water) to Winter (hot water). 2-pipe operation uses the  
Cool 1 output for heating and cooling. Heat 1 is disabled. 4-pipe operation allows heat 1 in  
summer mode of operation.  
2 – Four Pipe Operation (use for 2-pipe with  
electric heat relay)  
Available when SM 110 = 1 through 5 or 14 through 16  
172  
173  
174  
Pipe Sensor Threshold for 50F to 72F (Default 60F)  
Cooling  
Changes to Cool when pipe temp is below threshold. Available when SM 171 = 1 or 2  
Pipe Sensor Threshold for 75F to 90F (Default 80F)  
Heating  
Changes to Heat when pipe temp is above threshold. Available when SM 171 = 1 or 2  
Pipe Sensor Purge  
0 = Time  
TEMP: Purge continues until a non-ambiguous condition is sensed.  
TIME: A 3-minute purge is started. Once complete and still ambiguous mode all thermostat  
outputs are disabled for 1 hour.  
1 = Temp (Default)  
Available when SM 171 = 1 or 2  
175  
240  
Fault Detection/ Setback  
0 = Disabled (Default)  
1 = Active On Open  
2 = Active On Open  
3 = Active On Close  
4 = Occupancy Sensor  
When enabled connect dry switch between S1 and SC.  
Displays “Door” in clock location, turn outputs OFF, blink red LED  
Displays “Fdd” in clock location, outputs function normally  
Displays “Err” on clock location, turn outputs OFF blink red LED  
Sets thermostat to setback with a closure at SC and S1 .  
(requires SM170=0)  
No remote probe  
Number of Program Events 2 or 4 Events (DEFAULT = 2)  
When the T8168 is set up as programmable this sets the number of events per day.  
Events are OCC1, UNOCC1, OCC2, UNOCC2  
250  
260  
Clock Format  
F or C  
12 or 24 Hrs (Default = 12)  
0- Celsius  
This service menu sets the clock format.  
Determines temperature displays in Fahrenheit or Celsius  
1- Fahrenheit (Default)  
0-99 Seconds (0-Default)  
270  
Fan Off Delay Heat  
The amount of time (in seconds) the lowest available fan speed will run after the  
thermostat heating outputs are disabled  
280  
290  
Fan Off Delay Cool  
Range Low  
0-99 Seconds (0-Default)  
50-90 F (50F- Default)  
The amount of time (in seconds) the lowest available fan speed will run after the  
thermostat cooling outputs are disabled  
The lowest selectable temperature setpoint value  
© COPYRIGHT 2024 PECO, INC. ALL RIGHTS RESERVED.  
P/N 74599 3220-2406 REV 00  
5
GeneralDetails
NamePECO T8168B-2 BACnet Proportional Thermostat Installation Guide
MakePECO
LanguageEnglish
FiletypePDF (Download)
File size0.42 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PECO T8168 Performance Pro Thermostat Installation Guide
PECO T8168 Performance Pro Thermostat Installation Guide
PECO T372P Thermostat Instruction Manual
PECO T372P Thermostat Instruction Manual
PECO TW180 Thermostat Instruction Manual
PECO TW180 Thermostat Instruction Manual

PECO T8168B-2 BACnet Proportional Thermostat Installation Guide