PECO T8168B-2 BACnet Proportional Thermostat Installation Guide

300  
310  
Range High  
Setback Low  
50-90 F (90F Default)  
The highest selectable temperature setpoint value  
Off, 50-90 F (67F Default)  
Accessed from Wi-Fi or by occupancy sensor detection.  
“Off” turns heating setpoint off.  
320  
330  
340  
Setback High  
Off, 50-90 F (78F Default)  
+/-9F (0F Default)  
Accessed from Wi-Fi or by occupancy sensor detection.  
“Off” turns cooling setpoint off.  
Zone Temp Offset  
Keypad Lockout  
Zone Temperature offset adjusts the sensed Zone Temperature displayed, allowing calibra-  
tion in the field  
0- No Key Pad Lockout (Default)  
1- Disables Schedule and System Keys  
2 - Disables Schedule, System, And Fan Keys  
3 - Disables All Keys  
This function blocks access to certain features of the device. The Service Menu is still  
available if the key pad lockout is enabled.  
If PIN is entered keypad lockout is overridden for 5 minutes.  
341  
342  
350  
Enable Pin Access  
Set Pin  
0=Disable, 1= Enable (Default = 0)  
000-999 (Default 000)  
Applies a 3-digit access code to enter service menu 342  
Selects pin access three-digit code.  
Fan Mode  
1- On  
ON: Fan is always on, regardless of demand.  
User selections are: ON HI, ON MED, ON LO based on the number of fan speeds.  
2- Auto  
Auto- Fan is only on with heating or cooling demand User selections are: AUTO HI, AUTO  
MED, AUTO LO based on the number of fan speeds.  
3- ON Or Auto (Default)  
4 – Staged Only  
ON or Auto user can choose either selection. User selections are: AUTO HI, AUTO MED,  
AUTO LO, ON HI, ON MED, ON LO based on the number of fan speeds.  
Fan speed selected from available speeds by thermostat per Fan Access section. User  
selections are: AUTO or ON.  
5- On Or Staged - Hotel Mode  
ON- Fan is always on at user selected speed, regardless of demand  
Auto Staged- Fan cycles off with demand. Fan speed is selected by thermostat from avail-  
able fan speeds.  
360  
375  
System Mode  
0- Off, Auto  
Sets the system modes the occupant is able to select  
1- OFF, Heat, Cool, Auto (Default)  
2- OFF, Heat, Cool  
3- Heat, Cool, Auto  
0 = No Flush (Default)  
1 = W1 Flush  
Hotel operation - For ease of use change available System modes to ON-AUTO  
SM360=02  
System Flush Enable  
!
WARNING: Service Menu 375 may disable fan operation during valve flush.  
Enables the flush function for fan coil systems. This feature should be set to 0  
(zero) unless outputs are connected to hydronic heating or cooling valves. Failure  
to follow this instruction can result in damage to equipment and/or property.  
2 = Y1 Flush  
3 = W1 & Y1 Flush  
1 To 3 Minutes (Default 1)  
376  
377  
Flush Duration  
Defines how long to open the valve to perform the flush function  
Flush Frequency  
0 = Every 24 Hrs (Default 0)  
1 = Every 12 Hours  
Defines how often the flush is performed when output has remained inactive  
2 = Every 6 Hours  
380  
390  
Minimum Dead-band  
Adjustment  
3F (Default)  
A changeover dead-band value prevents short cycling between heating and cooling  
modes. The value is adjustable to meet various HVAC system requirements.  
1-10F, 1.5-5C  
0 Hours (Default)  
0-3 Hours  
Pre-Occupancy Purge  
Energizes the lowest fan available for selected number of hours (0-3) prior to events Occ 1  
and Occ 2. This featrure applies to Programmable thermostat operation.  
This feature is disabled for 0-10 VDC proportional fan applications.  
395  
Temporary  
Occupied Duration Limit  
0-4 Hours (Default = 3)  
This set the duration of a user override for programmable operation.  
0: Will override the schedule until the next programmed event.  
1,2,3,4: Sets the number of allowed hours of override after user adjustment. User can  
adjust override duration up to this limit of hours.  
480  
500  
Minimum Off Time  
0-10 Minutes (Default 1 Minutes)  
Sets the minimum off time for both the heat and cool output.  
Programmable/  
Intermittent Fan  
0- Disable (Default)  
1 – Programmable Fan  
2 - Intermittent Fan  
In programmable mode the fan will operate continuously during occupied periods or with  
demand during unoccupied/setback periods. In intermittent fan will operate based on the  
on and off times set in menus 501 and 502 whenever there is demand for fan.  
This feature is disabled for 0-10 VDC proportional fan applications.  
3 - Intermittent Fan During Occupied Periods  
Only  
501  
502  
Intermittent Fan On Time  
Intermittent Fan Off Time  
5 Minutes (Default)  
1-60 Minutes  
Defines the duration in which fan low will be on. Fan On will be activated after Fan Off  
time has passed.  
25 Minutes (Default)  
0-60 Minutes  
Defines the duration in which fan low will be off. Fan Off will be activated after Fan On  
time has passed. A selection of 0 will result in continuous Fan.  
© COPYRIGHT 2024 PECO, INC. ALL RIGHTS RESERVED.  
P/N 74599 3220-2406 REV 00  
6
GeneralDetails
NamePECO T8168B-2 BACnet Proportional Thermostat Installation Guide
MakePECO
LanguageEnglish
FiletypePDF (Download)
File size0.42 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PECO T8168 Performance Pro Thermostat Installation Guide