Munters RDT-5 Triple Phase Digital Thermostat User Manual
4.2 Cold Start
Cold Start returns the unit to its default settings. Only perform this procedure when
advised to do so by your dealer or a Munters technician.
To perform a Cold Start:
1. Disconnect power.
2. Apply power while pressing Select, Up Arrow, and Down Arrow.
3. When Cold Start Screen appears, press Select.
4.3 Software Version
After applying power, RDT-5:
Loads the temperature and growth day settings
•
•
Displays the software version on the screen for a few seconds
Figure 2: Software Version
NOTE If the RDT-5 cannot load the settings, it displays ----- in place of the software
version. These lines should disappear within a short time. If the lines remain in
place, reapply power. If they still remain in place, contact Technical Support.
NOTE RDT-5 retains all settings in the event of any power cut.
4.4 RDT-5 Configuration
The following sections explain how to configure the RDT-5.
Quick Start
•
•
•
•
•
•
Reading the Main Screen
Displaying the Current Temperature
Configuring the Basic Settings
Configuring the Stage Activation Temperature
Configuring the Temperature Curve
UICK TART
4.4.1 Q
S
This section describes the basic setup steps. For more detailed information refer to the
subsequent sections.
1. Press Select quickly. The unit displays the current temperature.
2. Press Down Arrow for three seconds. Set the general settings.
3. Press Select for three seconds. The 3 digit display shows current stage activation
temperature and “dif”. Use the arrow keys to modify the dif.
© Munters AB, 2021