CAUTION  
To ensure effective signal transmission, install a 120 ohm resistor between  
ports A and B on both the RDT-5 Communication Card and the Platinum RS-485  
Communication Card.  
Figure 13 key  
1
RDT-5 Unit  
2
3
4
5
RDT-5 Communication Card RS-485  
RDT-5 ground strip  
Platinum PP-485ISO_485 Communication Card  
Platinum Controller  
5.3 Configuring the RS-485 Communication  
Configuring the RS-485 communication consists of:  
• Defining the 5V Status  
• Defining the Termination  
• Defining the Baud Rate  
Figure 15: Communication Board Dipswitches  
The following section provides guidelines on how to set the RNET-485i Card dipswitches.  
•
•
(5V): Always enable (5V) in the RDT-5.  
Termination  
o
o
Termination is required in each chain, in the beginning and in the end units.  
When RDT-5 is a beginning or end unit, enable 120 ohm termination using  
the S2 dipswitch.  
•
115k bit/sec: This speed is always on.  
The illustrations below demonstrate these principles:  
(5V) means RDT-5 supplies 5V  
o