EPH CONTROLS CDC2 Cylinder Room Thermostat User Guide
P03 Hysteresis HOn & HOFF
HOn 5°C HOFF 0°C
This menu allows the installer to change the switching differential of the
thermostat when the temperature is rising and falling.
If ‘HYS ON’is set at 5˚C and the setpoint is 60˚C, then the thermostat will
switch on when the temperature drops below 55˚C.
If ‘HYS OFF’is set at 5˚C and the setpoint is 60˚C, then the thermostat
will switch off when the temperature reaches 65˚C.
To access this setting, press and hold
&
together for 5 seconds.
‘P01’ will appear on the screen.
Press
‘HOn’ will appear on the screen.
until ‘P03 & HYS’appears on the screen. Press
.
Press
Use
and the differential temperature will begin to flash.
&
to select the ‘HOn’temperature, press
to confirm.
EPH Controls Ltd.
23
| General | Details |
|---|---|
| Name | EPH CONTROLS CDC2 Cylinder Room Thermostat User Guide |
| Make | EPH CONTROLS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.66 MB |

EPH CONTROLS eTRV-HW Smart Cylinder Thermostat User Guide

EPH CONTROLS eTRV-HW Smart Hot Water Thermostat Instruction Manual

EPH CONTROLS eTRV Smart Radiator Thermostat Instruction Manual

EPH CONTROLS 20221026 RFRA – RF Room Thermostat Instruction Manual

EPH CONTROLS CDTP2 Hardwired Room Thermostat Instruction Manual

EPH Controls CDT2-24 24V Room Thermostat Installation Guide

EPH CONTROLS RFCA RF Cylinder Thermostat Instruction Manual

EPH CONTROLS PR092K7 RF Cylinder Thermostat Instruction Manual

EPH CONTROLS COMBIPACK2 Smart Thermostat with Automation and Optimum Start Instructions

EPH CONTROLS CRT2 Room Thermostat Instruction Manual