Home > Carrier > Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide

Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide

Lockout  
INSTALLATION TEST  
Locks out unauthorized changes made on the touchscreen. All  
touch interaction is locked out without the unlock code. After 5  
failed attempts, a notification (fault) is sent to the registered owner  
of the thermostat through Wi-Fi. More unlock attempts are  
blocked for 15 minutes.  
To set up a new PIN or change the current PIN, select the EN-  
ABLE button or the CHANGE PIN button, which displays on  
the SET PIN screen. If the thermostat does not already have a  
PIN, the CHANGE PIN button cannot be used.  
Complete the following to field test the WIFIStat Thermostat's  
outputs.  
1. Press the CHANGE button to cycle the MODE screen  
through the following settings:  
HEATING (default) — not available in a cooling-only  
configuration  
-
-
-
-
EM HEAT — not available unless a heat pump is  
configured  
COOLING  
configuration  
FAN  
not available in  
a
heating-only  
On the SET PIN screen, use the 3 blue-digit PIN wheels  
to set the PIN. Set the 3-digit PIN and press the orange  
Save button to save the PIN and return to the LOCKOUT  
screen. Press the DISABLE button to cancel the LOCK-  
OUT function and reset the PIN to 000. The default is 000  
and the range is 1 to 999.  
2. Press the START button.  
a. The first stage of HEATING, EM HEAT, COOLING,  
or FAN starts running and the text reads 1ST STAGE:  
180 or FAN ON and 180 seconds starts counting down.  
Clean  
b. The START button is replaced with a STOP button and  
Stops touchscreen interaction for 10 seconds to allow cleaning the  
screen with a dry nonabrasive cloth. A 10-second countdown  
shows on the CLEAN screen and then resumes normal operation.  
the CHANGE button disappears.  
c. Once the countdown reaches 0, if another stage exists, it  
starts and the text changes to 2ND STAGE: 180.  
Log  
d. If no other stage exists, the cycle ends, the text disap-  
You can use this screen to view software update history, fault his-  
tory, and system events. Swipe up or down on the vertical yellow  
Row Indicator to scroll through logged events.  
pears, and the START button reappears.  
e. If a third stage exists, it starts running after the second  
stage countdown reaches 0.  
f. While the HEATING and EM HEAT MODES are  
running, if a humidifier has been configured, a HUM  
button appears below the STOP button. If you press the  
HUM button, the text HUMIDIFYING appears and  
turns on the humidifier.  
g. While the COOLING MODE is running, if a dehu-  
midifier has been configured, a DEHUM button appears  
below the STOP button and, if pressed, the text DEHU-  
MIDIFYING appears and the dehumidifier turns on.  
The log includes:  
Startup  
Software Update Events  
Power Cycle Events  
Parameter Out-Of-Range Events  
Server Connectivity Events  
Non-volatile Memory Faults  
Temperature Faults  
h. Pressing the STOP button turns off running equipment,  
the STOP button is replaced with the START button,  
the CHANGE button reappears, and the second (stage  
running and countdown time) and third lines (humidify-  
ing or dehumidifying), are erased.  
The list displays the 5 most recent logged events, with the most re-  
cent at the top. The last line in the list includes the RESET LOG  
command to clear the list. Pressing an event item displays a screen  
with more information. Press the BACK button to return to the  
LOG screen.  
i. When you press the CANCEL button, any equipment  
that is running is turned off and the SYSTEM SET-  
TINGS screen displays.  
Status  
Displays the current status of  
Thermostat Outputs  
Timers  
Stages  
j. When you press the HOME icon, any equipment that is  
running is turned off and the HOME screen displays.  
After 15 minutes of inactivity (no button presses), the installer test  
stops and the HOME screen displays.  
Lockouts  
Current timer status is displayed and can be cleared for testing and  
troubleshooting by pressing and holding the TIMERS text for 5  
seconds. Press and hold LOCKOUT TIMERS for 5 seconds to  
clear timer values for COOL, E-HEAT, and HP HEAT.  
TROUBLESHOOTING  
If the display does not turn on:  
1. Check terminals R and C on the thermostat base.  
2. Verify power is 24 Vac +/-10%.  
Scroll the vertical yellow Row Indicator to see more  
options.  
3. Verify that the green LED on the base is flashing at 1 Hz.  
Service  
NOTE: If the green LED is not flashing and you do have 24 Vac  
on terminals R and C, you need to replace the thermostat.  
See Table 4 for Outputs Based on Demand and Configurations.  
Displays the dealer/installer service contact information.  
This information is editable using the mobile app, LAN  
mode transfer, and Wi-Fi transfer.  
14  
Table 4 — Outputs Based on Demand and Configuration  
Demands Stages  
Fan Only  
Y1  
Off  
On  
On  
On  
On  
On  
On  
On  
On  
Off  
Off  
On  
On  
On  
On  
Off  
Off  
Off  
Off  
Off  
Y2  
Off  
Off  
On  
On  
Off  
On  
Off  
Off  
On  
Off  
Off  
Off  
On  
On  
On  
Off  
Off  
Off  
Off  
Off  
W1  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On  
On  
Off  
Off  
On  
On  
On  
On  
On  
Off  
On  
W2  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
On  
On  
Off  
On  
Off  
On  
On  
G
Y3  
Off  
Off  
On  
X
*Rev Val=0 *Rev Val=B  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
X
X
X
X
Cool 1 (A/C)  
Cool 2 (A/C)  
X
X
Cool 3 (A/C)  
X
X
Cool 1 (Heat Pump)  
Cool 2 (Heat Pump)  
Dehumidify  
X
On  
On  
X
Off  
Off  
X
X
X
Cool 1 and Dehumidify  
Cool 2 and Dehumidify  
Heat 1 (A/C)  
X
X
X
X
X
X
X
X
X
Heat 2 (A/C)  
X
X
X
Heat 1 (Heat Pump)  
Heat 2 (Heat Pump)  
Heat 3 (HP w/Emerg Ht)  
Heat 4 (HP w/Emerg Ht)  
Heat 1 and Dehumidity  
Heat 2 and Dehumidity  
Heat Low  
X
Off  
Off  
Off  
Off  
X
On  
On  
On  
On  
X
X
X
X
X
X
X
X
X
X
X
Heat Med  
X
X
X
Heat High  
X
X
X
NOTE: Use this table along with the HUM/DEHUM table, if either of those functions are enabled. See HUMIDITY.  
Fault Definitions  
Table 5 shows a list of Fault messages which are displayed and  
logged in the banner during the fault condition and then sent to the  
Cloud server.  
Table 5 — Fault Definitions  
FAULTS  
CONDITION  
Temperature reading > 122°F  
When this fault occurs, the thermostat uses the temperature reading from the temperature/humidity sensor  
as the space temperature.  
ID TEMP SENSOR HIGH  
Temperature reading = 0  
Reading not available  
ID TEMP SENSOR LOW  
When this fault occurs, the thermostat uses the temperature reading from the temperature/humidity sensor  
as the space temperature.  
Remote temperature > 122°F  
REMOTE SENSOR HIGH  
REMOTE SENSOR LOW  
NOTE: Displayed only if REMOTE SENSOR is set to INDOOR or AVERAGE.  
Remote temperature = 0  
NOTE: Displayed only if REMOTE SENSOR is set to INDOOR or AVERAGE.  
Humidity sensor temperature > 122°F  
HUM TEMP SENSOR HIGH  
HUM TEMP SENSOR LOW  
NOTE: Displayed only if using humidity temperature as a backup source during a fault condition with the  
primary temperature sensor.  
Humidity sensor temperature = 0  
NOTE: Displayed only if using humidity temperature as a backup source during a fault condition with the  
primary temperature sensor.  
ID TEMP RANGE HIGH  
ID TEMP RANGE LOW  
Indoor Temp above cooling setpoint plus MAX SETPOINT ERROR  
Indoor Temp below heat setpoint minus MAX SETPOINT ERROR  
Any of the following:  
Humidity sensor timed out  
Humidity reading is > 99%  
Humidity reading is 0  
HUM SENSOR FAILURE  
HUMIDITY RANGE HIGH  
HUMIDITY RANGE LOW  
OUTDOOR SENSOR FAILURE  
NOT CONNECTED TO SERVER  
NOT CONNECTED TO ROUTER  
WI-FI HARDWARE FAULT  
ECONOMIZER FAULT  
Humidity reading is > 90%  
Humidity reading is < 10%  
OD temp > 127 or < -60  
Not connected to Ayla server  
Router signal strength is 0 = no bars = not connected  
Communications error occurred with Wi-Fi module (resets after valid message received)  
Contact closure on remote sensor input, as determined by Economizer  
User has entered incorrect pin 5 consecutive times  
LOCKOUT  
15  
GeneralDetails
NameCarrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide
MakeCarrier
LanguageEnglish
FiletypePDF (Download)
File size0.39 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Carrier 53DFS250-SL Programmable Digital Thermostat Owner’s Manual
Carrier 53DFS250-SL Programmable Digital Thermostat Owner’s Manual
Carrier 33TWSPL-4 Wifi Stat Plus Thermostat Owner’s Manual
Carrier 33TWSPL-4 Wifi Stat Plus Thermostat Owner’s Manual
Carrier EB-STATE3LTICB-01 lLite Smart Thermostat Instructions
Carrier EB-STATE3LTICB-01 lLite Smart Thermostat Instructions
Carrier ecobee3 Lite Smart Thermostat User Manual
Carrier ecobee3 Lite Smart Thermostat User Manual
Carrier EB-STATE7ICR-01 Ecobee for Smart Thermostat Owner’s Manual
Carrier EB-STATE7ICR-01 Ecobee for Smart Thermostat Owner’s Manual
Carrier TSTATCCEWF-01 Smart Thermostat Owner’s Manual
Carrier TSTATCCEWF-01 Smart Thermostat Owner’s Manual
Carrier Wi-Fi Enabled 24V Smart Thermostat Instruction Manual
Carrier Wi-Fi Enabled 24V Smart Thermostat Instruction Manual

Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide