Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide

Table 2 — Parameters (cont)  
PARAMETER NAME/DESCRIPTION  
DISCONNECT WIFI — Disconnects the thermostat from the Wi-Fi network.  
DEFAULT AND RANGE  
D:  
NOTE: Disconnecting the Wi-Fi requires setting up the WIFIStat Thermostat using the WIFIStat mobile application in R:  
order to re-establish Wi-Fi connectivity.  
INSTALLATION TEST — See Installation Test for detailed instructions.  
D:  
R:  
RESTORE DEFAULTS — Press and hold the 5 button for 5 seconds to initiate and restore all system setting defaults. D:  
Press the CANCEL button to go back to SYSTEM SETTINGS screen.  
R:  
The cooling stage 5-minute minimum off-timer has  
expired  
The space temperature has exceeded the cooling setpoint  
by the DIFFERENTIAL value (0.5°F default)  
OPERATING YOUR SYSTEM USING  
THE WIFISTAT  
The thermostat supports the following types of constant volume  
units:  
Additional stages are added and dropped, based on demand using  
the DIFFERENTIAL value, STAGE DELAY timer, and  
FORCED STAGE UP timer configuration values. If the LOW  
COOL LOCKOUT is configured for ON, or between 80 and  
110°F, and the OAT is equal to or greater than that value, cool  
stages 1 and 2 are energized on a demand for cooling and remain  
on until the cooling demand is satisfied.  
Standard heat/cool unit types with up to 3 stages of me-  
chanical cooling, up to 2 stages of gas or electric heating.  
Heat pump units utilizing a reversing valve output for  
heating and cooling control.  
Heat pump unit with an OEM defrost control board.  
NOTES:  
NOTE: Once a cooling stage is energized, it remains on for a min-  
imum of 5 minutes, regardless of demand.  
Humidification or dehumidification control strategies are  
available for appropriately equipped units.  
Econ Enable  
The following configurations have interdependencies that  
may preclude the use of others:  
Reversing valve  
Third-stage cooling  
Humidification  
Dehumidification  
Occupancy Output  
The flex outputs, Y3, O, and W2, may be available for  
optional functions.  
The thermostat’s application and configuration determine the spe-  
cific cooling sequence. It can control up to 2 stages of cooling,  
with an additional output for a reversing valve or up to 3 stages of  
cooling for non-heat pump applications.  
NOTE: The cooling stages are controlled based on a drift algo-  
rithm and the configurable DIFFERENTIAL value (0.5°F  
default).  
-
-
-
-
-
-
The following conditions must be true for the cooling to operate:  
The OAT must be above the COOL LOCKOUT (55°F  
EXAMPLE: In a single stage heating system, the W2 output  
could be used as the Occupancy output to enable the ECON  
during occupied periods.  
default), if enabled  
The cooling stage 5-minute minimum off-timer has ex-  
pired  
The space temperature has exceeded the cooling setpoint  
by the DIFFERENTIAL value (0.5°F default)  
Occupancy  
Configure the thermostat to operate in a programmable or non-  
programmable mode. Non-programmable operates continuously  
in occupied mode. Programmable operates as a 7-day programma-  
ble thermostat for either 2 or 4 periods per day. You can set each  
period as occupied or unoccupied.  
If you configure Smart Recovery for 30 to 90 minutes, the occu-  
pied start time increases up to the maximum time, in order to bring  
the space to the occupied setpoints at actual occupied time.  
Additional stages are added and dropped, based on demand using  
the DIFFERENTIAL value, STAGE DELAY timer, and  
FORCED STAGE UP timer configuration values. If the LOW  
COOL LOCKOUT is configured for ON, or between 80 and  
110°F, and the OAT is equal to or greater than that value, cool  
stages 1 and 2 are energized on a demand for cooling and remain  
on until the cooling demand is satisfied.  
Supply Fan  
Configure the supply fan for ON or AUTO, in either occupied or  
NOTE: Once a cooling stage is energized, it remains on for a min-  
imum of 5 minutes, regardless of demand.  
unoccupied mode.  
Heating  
ON – Fan runs continuously regardless of demand  
AUTO – Fan cycles heat or cool demand if there is a de-  
mand for humidity or dehumidification  
The thermostat's application and configuration determine the spe-  
cific heating sequence. It can control up to 4 stages of heating  
when configured for heat pump applications, or up to 2 stages of  
heating for non-heat pump applications. When applied to a com-  
mercial heat pump, HEAT TYPE must be set to GAS. HEAT  
TYPE set to ELECTRIC supports a 3-stage heat operation using  
2 outputs. See Outputs based on demand and configuration.  
NOTE: The heating stages are controlled, based on a drift algo-  
rithm and the configurable DIFFERENTIAL value (0.5°F de-  
fault).  
Cooling  
The thermostat's application and configuration determine the spe-  
cific cooling sequence. It can control up to 2 stages of cooling,  
with an additional output for a reversing valve, or up to 3 stages of  
cooling for non-heat pump applications.  
NOTE: The cooling stages are controlled based on a drift algo-  
rithm and the configurable DIFFERENTIAL value (0.5°F de-  
fault).  
The following conditions must true for heating to operate:  
The OAT must be below the HEAT LOCKOUT (55°F  
default), if enabled  
The following conditions must be true for the cooling to operate:  
The OAT must be above the COOL LOCKOUT (55°F  
default), if enabled  
The heating stage 5-minute minimum off-timer has  
expired  
9
GeneralDetails
NameCarrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide
MakeCarrier
LanguageEnglish
FiletypePDF (Download)
File size0.39 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Carrier 53DFS250-SL Programmable Digital Thermostat Owner’s Manual
Carrier 53DFS250-SL Programmable Digital Thermostat Owner’s Manual
Carrier 33TWSPL-4 Wifi Stat Plus Thermostat Owner’s Manual
Carrier 33TWSPL-4 Wifi Stat Plus Thermostat Owner’s Manual
Carrier EB-STATE3LTICB-01 lLite Smart Thermostat Instructions
Carrier EB-STATE3LTICB-01 lLite Smart Thermostat Instructions
Carrier ecobee3 Lite Smart Thermostat User Manual
Carrier ecobee3 Lite Smart Thermostat User Manual
Carrier EB-STATE7ICR-01 Ecobee for Smart Thermostat Owner’s Manual
Carrier EB-STATE7ICR-01 Ecobee for Smart Thermostat Owner’s Manual
Carrier TSTATCCEWF-01 Smart Thermostat Owner’s Manual
Carrier TSTATCCEWF-01 Smart Thermostat Owner’s Manual
Carrier Wi-Fi Enabled 24V Smart Thermostat Instruction Manual
Carrier Wi-Fi Enabled 24V Smart Thermostat Instruction Manual

Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide