Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide
Table 2 — Parameters (cont)
PARAMETER NAME/DESCRIPTION
DEFAULT AND RANGE
OCCUPANCY OUTPUT — When set to ON-Y3, ON-O/B, or ON-W2, selected relay output equals current Occupancy D: Off
state. Can be used for ECON Enable.
NOTE: The OCCUPANCY OUTPUT option is not displayed or available if Y3, O, and W2 relays are being used; i.e.
Humidification/ Heat Pump/ 3-stage cooling/ etc.
R: Off
On-Y3
On-W2
On-O/B
OCCUPANCY INPUT — This setting changes the current heating and cooling setpoints to the option selected for MAX D: Occupied
HOLD TIME. This occurs when the short is detected on the Remote Space Sensor for the duration of 2 to 5 seconds. R: Occupied
Unoccupied
HUM OUTPUT — Select which output to use for humidifier.
NOTE: Only unassigned outputs are available.
D: Off
R: On-Y3
On-W2
On-O/B
DEHUM OUTPUT — Select the unassigned output to use for dehumidifier (Humid-MiZer™/Perfect Humidity™/Hot Gas D: Off
Reheat).
R: On-Y3
NOTE: Only unassigned outputs are available.
On-W2
On-O/B
LINE FREQUENCY — Used to increment operational timers within the thermostat to ensure timing accuracy.
D: 60HZ
R: 50HZ
60HZ
DEALER NAME — (Optional) This setting identifies the name of the installing contractor and could be carried forward D:
from the sensor if input through the local display. R:
DEALER PHONE — (Optional) This setting identifies the phone number of the installing contractor and can be carried D:
forward from the sensor if input through the local display.
R:
MSTP MAX MASTERS — Used to identify max number of masters for token passing on the MS/TP network.
D: 127
R: 1 to 127
MSTP BAUD RATE — The protocol's baud rate (communication speed) on the MS/TP network. The baud rate must be D: 76,800
the same for all controllers on the network.
R: 9,600
19,200
38,400
76,800
115,000
MSTP MAC ADDRESS — Unique identifier for this thermostat on the MSTP network
D:
1
R: 1 to 127
BACNET UTC OFFSET — Offset applied to UTC time
D: 5 hrs / 0 min
R: -13 to 13 hrs / 0 min
DEVICE ID — This is a unique identifier for this thermostat. The default is the BACnet identifier (16) and the last 4 digits D: 16xxxx
of the thermostat serial number.
R: 1 to 4194302
DEVICE OBJECT NAME — Assign a unique alpha-numeric string. The default is the BACnet identifier (16) and the
last 4 digits of the thermostat serial number. This parameter is limited to a maximum of 16 characters.
D: 16xxxx
R:
DEVICE LOCATION — (Optional) Use to provide details about thermostat location.
D: (Location)
R:
DEVICE DESCRIPTION — (Optional) Use to provide additional details about this thermostat.
D: (Description)
R:
BACNET BMS OCC — Use to enable or disable BACnet occupancy control.
D: No
R: No
Yes
NOTE: Occupancy is determined by 1 of 3 methods. You cannot have BACNET BMS OCC with both
PROGRAMMABLE MODE and REMOTE SENSOR set to OCCUPANCY. Setting BACNET BMS OCC to YES forces
PROG OR NON-PROG to NON-PROG and switches REMOTE SENSOR to NONE if set to OCCUPANCY.
BACNET CONFIG WRITE — If YES, allows BACnet to write to GATED_WRITE points. See Appendix BACnet Points D: No
List.
R: No
Yes
NET GP OUT TIMEOUT — Used to timeout Network General Purpose Outputs.
D: 2 min
R: 2 min
20 min
NOTES:
•
Sets the maximum time to lapse between writes to the present_value property of the output object before it returns
to INACTIVE.
1 hr
•
Accessible only if Y3, W2, or O/B output is available as a GP OUTPUT.
Unlimited
NET GP Y3 MODE — Controls the Y3 output over the BACnet network.
D: Disabled
R: Disabled
•
•
•
DISABLED sets the Present_Value of the BACnet object to INACTIVE and READ_ONLY and the corresponding
output relay will be in a de-energized state
Energized Active
Energized Inactive
Selecting ENERGIZE ACTIVE allows BACnet writes and energizes the output relay when the Present_Value is
ACTIVE.
Selecting ENERGIZE INACTIVE allows BACnet writes and will energize the output relay when the Present_Value is
INACTIVE.
NET GP W2 MODE — Controls the W2 output over the BACnet network.
D: Disabled
R: Disabled
Energized Active
Energized Inactive
•
•
•
DISABLED sets the Present_Value of the BACnet object to INACTIVE and READ_ONLY and the corresponding
output relay will be in a de-energized state
Selecting ENERGIZE ACTIVE allows BACnet writes and energizes the output relay when the Present_Value is
ACTIVE.
Selecting ENERGIZE INACTIVE allows BACnet writes and will energize the output relay when the Present_Value is
INACTIVE.
NET GP OB MODE — Controls the Y3 output over the BACnet network.
D: Disabled
R: Disabled
Energized Active
Energized Inactive
•
•
•
DISABLED sets the Present_Value of the BACnet object to INACTIVE and READ_ONLY and the corresponding
output relay will be in a de-energized state
Selecting ENERGIZE ACTIVE allows BACnet writes and energizes the output relay when the Present_Value is
ACTIVE.
Selecting ENERGIZE INACTIVE allows BACnet writes and will energize the output relay when the Present_Value is
INACTIVE.
8
| General | Details |
|---|---|
| Name | Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide |
| Make | Carrier |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.39 MB |

Carrier 53DFS250-SL Programmable Digital Thermostat Owner’s Manual

Carrier 33TWSPL-4 Wifi Stat Plus Thermostat Owner’s Manual

Carrier EB-STATE3LTICB-01 lLite Smart Thermostat Instructions

Carrier ecobee3 Lite Smart Thermostat User Manual

Carrier EB-STATE7ICR-01 Ecobee for Smart Thermostat Owner’s Manual

Carrier TSTATCCEWF-01 Smart Thermostat Owner’s Manual

Carrier Wi-Fi Enabled 24V Smart Thermostat Instruction Manual