Home > azbil > azbil TY6000Z2000 Neostat Room Thermostat Instruction Manual

azbil TY6000Z2000 Neostat Room Thermostat Instruction Manual

AB-7258  
Part Numbers of Optional Items  
Mount Neostat with the following optional items (sold separately). Order necessary items.  
Item  
Part number/Model number  
Part No. 83172617-001  
Note  
Adapter  
Auxiliary device  
Thermoplate for individual room Model QY1100A  
With slide switch  
With rotary switch  
control  
Model QY1100C  
Model QY1100D  
Thermoplate  
Part No. DY2000A1022  
Part No. DY2000A1023  
Part No. DY2000A2023  
For mounting one Neostat, lengthwise  
For mounting one Neostat, crosswise  
For mounting two Neostat in  
94mm (H) x 192mm (W) outlet box, crosswise  
For mounting two Neostat in  
Part No. DY2000A2024  
106mm (H) x 198mm (W) outlet box, crosswise  
For mounting three Neostat, crosswise  
For mounting one Neostat, square  
For mounting two Neostat, crosswise  
For mounting three Neostat, crosswise  
Part No. DY2000A3022  
Part No. DY2000A1021  
Part No. DY2000A2021  
Part No. DY2000A3021  
Thermoplate for open wiring  
* Thermoplate for open wiring  
is used for open wiring  
installation.  
Multi-Thermocase  
Model TY1100Z  
83104506-020  
10 pcs  
Protection cover  
Specifications  
Item  
Specification  
Differential  
Model TY600_Z  
Model TTY6023Z  
Model HY6000Z  
1.5 ± 1 °C (in 10–30 °C range)  
5 ± 3 % RH (in 30–90 % RH range)  
Temperature  
difference Model TTY6023Z 2 ± 1 °C fixed (in 10–30 °C range)  
between steps  
(of two-position, two-step  
control)  
Proportional band  
Sensing elements  
Model TY900_Z  
Thermostat  
Humidistat  
2 ± 1 °C fixed (in 10–30 °C range)  
Temperature-sensitive diaphragm  
Moisture-sensitive nylon ribbon  
Environment conditions  
Rated operating conditions  
Transport/storage conditions  
Model TY600_Z  
Model TTY6023Z  
Model TY900_Z  
Model HY6000Z  
Ambient temperature 0–50 °C  
-20–50 °C  
5–95 % RH  
(without condensation)  
-20–50 °C  
Ambient humidity  
10–90 % RH  
(without condensation)  
Ambient temperature 10–40 °C  
Ambient humidity  
10–90 % RH  
(without condensation)  
5–95 % RH  
(without condensation)  
Contact rating of two-position control*1 *3  
Model TY600_Z  
125 V AC  
6 A  
36 A  
250 V AC  
3 A  
18 A  
3 A  
24 V DC  
1 A  
10 A  
2A  
Operating  
Startup  
Resistive load  
6 A  
Model TTY6023Z Operating  
4 A  
2 A  
Startup  
18 A  
9 A  
Resistive load  
4 A  
2 A  
Contact rating of two-position control*1 *2 *3  
Model HY6000Z  
125 V AC  
4.4 A  
26.4 A  
8 A  
250 V AC  
2.2 A  
13.2 A  
4 A  
24 V DC  
0.4 A  
2 A  
Operating  
Startup  
Resistive load  
1 A  
Color  
Pale gray (BN-85, Japan Paint Manufacturers Association in 2003)  
Cover  
Base  
PC resin  
PC resin  
Materials  
Weight  
Approx. 180 g  
Installation  
Connection  
With the mounting kit (sold separately)  
Connections using the terminal blocks  
Model TY600_Z  
Model TY900_Z  
Model HY6000Z  
Model TTY6023Z Lead wire connection  
Two mounting screws (M4 x 10 mm, pan-head screw)  
Accessory  
Notes:  
*1 Minimum allowable current is 50 mA.  
*2 Contact rating of the humidistat model (Model HY6000Z) shown above is the maximum current at startup and in operation when Model  
HY6000Z is connected to dehumidifier/humidifier.  
*3 Select a device (load) of which the Neostat contact rating is tolerable. If a load larger than the Neostat contact rating is connected to Neostat,  
the contact may be welded and may not turn on or off.  