azbil TY6000Z2000 Neostat Room Thermostat Instruction Manual
AB-7258
Part Numbers of Optional Items
Mount Neostat with the following optional items (sold separately). Order necessary items.
Item
Part number/Model number
Part No. 83172617-001
Note
Adapter
—
Auxiliary device
Thermoplate for individual room Model QY1100A
With slide switch
With rotary switch
control
Model QY1100C
Model QY1100D
Thermoplate
Part No. DY2000A1022
Part No. DY2000A1023
Part No. DY2000A2023
For mounting one Neostat, lengthwise
For mounting one Neostat, crosswise
For mounting two Neostat in
94mm (H) x 192mm (W) outlet box, crosswise
For mounting two Neostat in
Part No. DY2000A2024
106mm (H) x 198mm (W) outlet box, crosswise
For mounting three Neostat, crosswise
For mounting one Neostat, square
For mounting two Neostat, crosswise
For mounting three Neostat, crosswise
Part No. DY2000A3022
Part No. DY2000A1021
Part No. DY2000A2021
Part No. DY2000A3021
Thermoplate for open wiring
* Thermoplate for open wiring
is used for open wiring
installation.
Multi-Thermocase
Model TY1100Z
83104506-020
—
10 pcs
Protection cover
Specifications
Item
Specification
Differential
Model TY600_Z
Model TTY6023Z
Model HY6000Z
1.5 ± 1 °C (in 10–30 °C range)
5 ± 3 % RH (in 30–90 % RH range)
Temperature
difference Model TTY6023Z 2 ± 1 °C fixed (in 10–30 °C range)
between steps
(of two-position, two-step
control)
Proportional band
Sensing elements
Model TY900_Z
Thermostat
Humidistat
2 ± 1 °C fixed (in 10–30 °C range)
Temperature-sensitive diaphragm
Moisture-sensitive nylon ribbon
Environment conditions
Rated operating conditions
Transport/storage conditions
Model TY600_Z
Model TTY6023Z
Model TY900_Z
Model HY6000Z
Ambient temperature 0–50 °C
-20–50 °C
5–95 % RH
(without condensation)
-20–50 °C
Ambient humidity
10–90 % RH
(without condensation)
Ambient temperature 10–40 °C
Ambient humidity
10–90 % RH
(without condensation)
5–95 % RH
(without condensation)
Contact rating of two-position control*1 *3
Model TY600_Z
125 V AC
6 A
36 A
250 V AC
3 A
18 A
3 A
24 V DC
1 A
10 A
2A
Operating
Startup
Resistive load
6 A
Model TTY6023Z Operating
4 A
2 A
—
Startup
18 A
9 A
—
Resistive load
4 A
2 A
—
Contact rating of two-position control*1 *2 *3
Model HY6000Z
125 V AC
4.4 A
26.4 A
8 A
250 V AC
2.2 A
13.2 A
4 A
24 V DC
0.4 A
2 A
Operating
Startup
Resistive load
1 A
Color
Pale gray (BN-85, Japan Paint Manufacturers Association in 2003)
Cover
Base
PC resin
PC resin
Materials
Weight
Approx. 180 g
Installation
Connection
With the mounting kit (sold separately)
Connections using the terminal blocks
Model TY600_Z
Model TY900_Z
Model HY6000Z
Model TTY6023Z Lead wire connection
Two mounting screws (M4 x 10 mm, pan-head screw)
Accessory
Notes:
*1 Minimum allowable current is 50 mA.
*2 Contact rating of the humidistat model (Model HY6000Z) shown above is the maximum current at startup and in operation when Model
HY6000Z is connected to dehumidifier/humidifier.
*3 Select a device (load) of which the Neostat contact rating is tolerable. If a load larger than the Neostat contact rating is connected to Neostat,
the contact may be welded and may not turn on or off.
4
| General | Details |
|---|---|
| Name | azbil TY6000Z2000 Neostat Room Thermostat Instruction Manual |
| Make | azbil |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.75 MB |