Wiring  
CAUTION: ELECTRICAL HAZARD. Can cause electrical shock or equipment damage.  
Disconnect power before wiring.  
Wiring  
Keep wires in this  
shaded area  
1
2
3
Loosen screw terminals, insert  
wires into terminal block, then  
re-tighten screws.  
Push excess wire back into the  
wall opening. Keep wires in shaded  
area as shown at left.  
Plug the wall opening with non-  
flammable insulation to prevent  
drafts from affecting thermostat  
operation.  
Terminal Designations  
Heat Pump  
Conventional Terminal Letters:  
Y2 2nd stage compressor contactor  
W2 2nd stage heat relay  
Conventional  
G
W
C
Fan relay  
1st stage heat relay  
NOTES  
Common wire from secondary side of  
cooling system transformer  
1st stage compressor contactor  
Heating power. Connect to secondary  
side of heating system transformer.  
R & Rc terminals  
In single-transformer system, leave metal  
jumper in place between R & Rc. Remove  
metal jumper if two-transformer system.  
Y
R
Rc Cooling power. Connect to secondary  
side of cooling system transformer.  
C terminal  
The C (common wire) terminal is optional  
when thermostat is powered by batteries.  
Heat Pump Terminal Letters:  
L
Heat pump reset. L terminal powered  
continuously when System is set to Em  
Heat.  
W (O/B) terminal  
If thermostat is configured for a heat pump  
in the Installer Setup, configure changeover  
valve for cool (“O” factory setting) or heat  
(“B”).  
E
Emergency heat relay  
Aux Auxiliary heat relay  
Fan relay  
O/B Changeover valve for heat pumps  
G
L terminal (Output)  
C
Common wire from secondary side of  
cooling system transformer.  
Compressor contactor  
Heat pump reset. L terminal powered contin-  
uously when thermostat is set to Em Heat.  
Configure thermostat for 2 heat / 1 cool heat  
pump in the Installer Setup.  
Y
R
Heating power. Connect to secondary  
side of heating system transformer.  
Rc Cooling power. Connect to secondary  
Wire specifications  
Use 18- to 22-gauge thermostat wire.  
Shielded cable is not required.  
side of cooling system transformer.  
4
firealarmresources.com  
GeneralDetails
NameHoneywell TH5220D Non-Programmable Digital Thermostat Installation Guide
MakeHoneywell
LanguageEnglish
FiletypePDF (Download)
File size0.58 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TL116A Thermostat Installation Guide
Honeywell TL116A Thermostat Installation Guide
T10 Pro Smart Thermostat with Redlink Room Sensor
T10 Pro Smart Thermostat with Redlink Room Sensor
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide
Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell TH5220D Non-Programmable Digital Thermostat Installation Guide