Home > Honeywell > Honeywell N100 Series Non Programmable Thermostat Installation Guide

Honeywell N100 Series Non Programmable Thermostat Installation Guide

3160 Heating Cycle Rate  
Auxiliary Heat  
1-12 (TH1320U4002 only)  
1-12 (TH1320U4002 only)  
2010 Heating Equipment  
Type  
Conventional Forced Air Heat:  
1 = Standard Efficiency Gas Forced Air  
2 = High Efficiency Gas Forced Air  
3 = Oil Forced Air  
4 = Electric Forced Air  
5 = Hot Water Fan Coil  
Réglages de l'installateur (ISU)  
2
3165 Heating Cycle Rate  
Emergency Heat  
Lors de la configuration initiale, le thermostat entrer  
dans le menu ISU. Si vous entrez dans le menu ISU  
après la configuration initiale, suivez les étapes  
ci-dessous :  
FocusPRO N100 Series Nonprogrammable Thermostat  
TH1110U4000, TH1320U4002  
NOTE: The complete list of ISUs can be found in the online  
Installation Manual.  
Heat pump:  
7 = Air to Air Heat Pump  
8 = Geothermal Heat Pump  
Device input power rating: 24V, 60Hz, 1.1VA.  
Device contact ratings of up to 1A, inductive.  
EN Installer Guide  
Radiant Heat:  
9 = Hot Water Radiant Heat  
12 = Steam  
1. Appuyez sur la touche et maintenez  
le bouton en bas à gauche et la  
flèche vers le haut pendant 5  
secondes pour accéder au menu  
CAUTION: ELECTRICAL HAZARD  
Can cause electrical shock or equipment damage.  
Disconnect power before beginning installation.  
O = O (O/0B in Cool)  
1 = B (O/0B in Heat)  
2060 Reversing Valve O/B  
2070 Compressor Stages  
Scan for the full Installation Manual  
1
Maintenir  
CONFIGURATION DE  
L'INSTALLATEUR (ISU)  
CAUTION: EQUIPMENT DAMAGE HAZARD  
Compressor protection is bypassed during testing. To prevent  
equipment damage, avoid cycling the compressor quickly  
0, 1, 2 (2 for TH1320U4002 Only)  
Heat Stages /  
Backup Heat Stages  
Heat Stages: 1, 2  
Backup Heat Stages (TH1320U4002  
Only): 0, 1  
2071  
Le numéro ISU est à gauche. Le  
réglage de l'ISU se trouve à droite.  
2.  
CAUTION: MERCURY NOTICE  
M39505  
If this product is replacing a control that contains mercury in a  
sealed tube, do not place the old control in the trash. Contact your  
local wast management authority for instructions regarding  
recycling and proper disposal.  
Fan Control in Heat  
(Shown if 2010 = 4 or 5)  
2110  
1 = Equipment Controls fan  
2 = Thermostat Controls Fan  
Lorsqu'un numéro ISU s'affiche,  
appuyez sur ou pour modifier le  
paramètre pour cet ISU.  
2175 Aux / E Terminal  
Control  
0 = Drive both Aux & E together  
1 = Aux and E independent  
CAUTION: ELECTRONIC WASTE NOTICE  
The product and batteries should not be disposed of with other  
household waste. Check for the nearest authorized collection center  
or authorized recyclers. The correct disposal of end-of-life equipment  
will help prevent negative consequences for the environment and  
human health.  
info.honeywellhome.com/focuspro-n100-im  
3. Après avoir choisi le paramètre  
correct pour une ISU, appuyez sur  
NEXT (SUIVANT) pour passer au  
paramètre ISU suivant.  
2180 Backup Heat Source  
(Heat Pump Only)  
(TH1320U4002 Only)  
31 = Electric Forced Air  
32 = Standard Efficiency Gas Forced Air  
33 = High Efficiency Gas Forced Air  
34 = Oil Forced Air, Hot Water Fan Coil  
35 = Hot Water Radiant Heat  
36 = Other  
M39545  
NOTE: For Heat Pump systems do NOT attach a wire  
to the W terminal of the UWP™ Mounting System.  
2185 Emergency Heat Source  
(TH1320U4002 Only)  
FCC statement available at:  
codes-and-standards/FCC15105/Pages/default.aspx  
Pour terminer la configuration, appuyez sur le bouton SAVE & EXIT.  
4.  
3000 System Changeover  
0 = Manual  
1 = Automatic  
#ISU  
Nom de l'ISU  
Options ISU (les valeurs par défaut sont en gras)  
Installer Setup (ISU) Settings  
2
1050 Échelle de température  
F = Fahrenheit  
0 = Aucun  
C = Celsius  
3015 Auto Changeover  
Differential  
0°F to 5°F  
0.0°C to 2.5°C  
On initial setup, the thermostat will enter the ISU  
menu. If entering the ISU menu after initial setup,  
follow the steps below:  
Customer Assistance  
For assistance with this product, please visit  
customer.resideo.com  
3
1060 Capteur extérieur  
(TH1320U4002 seulement)  
1 = Capteur extérieur câblé  
3020 Finish With High Cool  
Stage  
0 = No  
1 = Yes  
1 = Chauffage conventionnel à air pulsé  
2 = Pompe à chaleur  
3 = Chauffage par rayonnement  
5 = Aucun (refroidissement seulement)  
2000 Type de système de chauffage  
Or call Resideo Customer Care toll-free at  
1-800-633-3991  
1. Press and hold the bottom left  
button and Up arrow button for 5  
seconds to access the INSTALLER  
SETUP (ISU).  
3021 Finish With High Heat  
Stage  
0 = No  
1 = Yes  
2010 Équipement de chauffage  
type  
Chauffage conventionnel à air pulsé :  
1 = Air pulsé au gaz à efficacité standard  
2 = Air pulsé au gaz à haute efficacité  
3 = Air pulsé à l'huile  
4 = Air pulsé électrique  
5 = Ventilo-convecteur à eau chaude  
0 = Comfort  
2 °F to 15 °F in 1 °F  
increments)  
1.0 °C to 7.5 °C (in 0.5 °C  
increment).  
3090 Backup Heat Droop  
(For heat pump with  
aux heat stage. 0 only  
for electric)  
2. The ISU number is on the left. The  
ISU setting is on the right.  
M39544  
0 = Off  
8 = 4 hours  
9 = 5 hours  
3110 Upstage Time for  
Backup Heat  
When an ISU number is displayed,  
press or to change the setting.  
Pompe à chaleur :  
7 = Thermopompe air-air  
8 = Thermopompe géothermique  
1 = 30 minutes  
2 = 45 minutes  
3 = 60 minutes  
4 = 75 minutes  
5 = 90 minutes  
6 = 2 hours  
10 = 6 hours  
11 = 8 hours  
12 = 10 hours  
13 = 12 hours  
14 = 14 hours  
15 = 16 hours  
(If 3090 = 0 and 2180 =  
31, 3110 only has  
settings 0-3)  
After choosing the correct setting  
for an ISU, press NEXT to advance  
to the next ISU setting.  
3.  
4.  
Chauffage radiant :  
9 = Chaleur radiante à eau chaude  
12 = Vapeur  
Série FocusPRO N100 Thermostat Non Programmable  
TH1110U4000, TH1320U4002  
7 = 3 hours  
To finish setup, press the SAVE &  
EXIT button.  
2060 Vanne d'inversion O/B  
2070 Phase du compresseur  
O = O (O/0B en refroidissement)  
1 = B (O/0B en chauffage)  
3120 Compressor Lockout.  
Wired outdoor sensor  
is needed.  
0 = Off  
25 = 25°F (-4°C)  
30 = 30°F (-1°C)  
35 = 35°F (1.5°C)  
40 = 40°F (4.5°C)  
45 = 45°F (7°C)  
50 = 50°F (10°C)  
55 = 55°F (13°C)  
60 = 60°F (15.5°C)  
65 = 65°F (18.5°C)  
M39545  
1 = -15°F (-26°C)  
2 = -10°F (-23.5°C)  
3 = -5°F (-20.5°C)  
4 = 0°F (-18°C)  
5 = 5°F (-15°C)  
10 = 10°F (-12°C)  
15 = 15°F (-9.5°C)  
20 = 20°F (-6.5°C)  
FR Guide d'installation  
0, 1, 2 (2 pour TH1320U4002 uniquement)  
2071 Phase de chauffage / Phase  
de chauffage d'appoint  
Phase de chauffage : 1, 2  
Phase de chauffage d'appoint : 0, 1  
#ISU ISU Name  
ISU Options (default in bold)  
3121 Outdoor Lockout  
Backup Heat.  
Consultez le manuel d'installation complet  
1
Wired outdoor sensor  
is needed.  
2110 Commande du ventilateur en  
mode chauffage  
1 = L'équipement contrôle le ventilateur  
2 = Le thermostat contrôle le ventilateur  
1050 Temperature Scale  
F = Fahrenheit  
C = Celsius  
(Setting 65 not for 3120. 1-5 not for  
3121)  
(affiché si 2010 = 4 ou 5)  
1060 Outdoor Sensor  
(TH1320U4002 Only)  
0 = None  
1 = Wired Outdoor Sensor  
[0] = Off  
[1] 5 min to [24] 120 min (in 5  
minutes increments)  
2175 Contrôle du terminal Aux / E  
0 = Pilotage simultané des auxiliaires et de  
l'alimentation électrique  
1 = Aux et E indépendants  
3125 Lockout Fan after a  
Cool Call  
1 = Conventional Forced Air Heat  
2 = Heat Pump  
3 = Radiant Heat  
2000 Heating System Type  
Compressor Cycle  
Rate (Stage 1)  
1-6  
3140  
3141  
2180 Source de chaleur de secours  
Thermopompe uniquement  
31 = Air pulsé électrique  
32 = Air pulsé au gaz à rendement normal  
5 = None (Cool Only)  
(
TH1320U4002 uniquement) 33 = Air pulsé au gaz à haut rendement  
34 = Air pulsé au mazout, ventilo-convecteur à eau  
chaude  
Compressor Cycle  
Rate (Stage 2)  
1-6 (TH1320U4002 only)  
1-12  
info.honeywellhome.com/focuspro-n100-im  
35 = Chauffage par rayonnement à l'eau chaude  
36 = Autre  
Source de chaleur de secours  
(TH2320 uniquement)  
2185  
3150 Heating Cycle Rate  
(Stage 1)  
REMARQUE : Pour les systèmes de thermopompe,  
ne connectez PAS de fil à la borne W du système de  
montage UWP™.  
3000 Changement de système  
0 = Manuel  
1 = Automatique  
3151 Heating Cycle Rate  
(Stage 2)  
1-12 (TH1320U4002 only)  
33-00682EFS-03  
GeneralDetails
NameHoneywell N100 Series Non Programmable Thermostat Installation Guide
MakeHoneywell
LanguageEnglish
FiletypePDF (Download)
File size0.16 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TL116A Thermostat Installation Guide
Honeywell TL116A Thermostat Installation Guide
T10 Pro Smart Thermostat with Redlink Room Sensor
T10 Pro Smart Thermostat with Redlink Room Sensor
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide
Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell N100 Series Non Programmable Thermostat Installation Guide
Get the free PDF manual for the Honeywell N100 Series Non Programmable Thermostat Installation Guide and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

Honeywell N100 Series Non Programmable Thermostat Installation Guide Overview

Summary of Contents

  • Page 1: Heating cycle rate settings are crucial for optimal performance. The equipment types include conventional forced air heat, heat pumps, and radiant heat. Installer setup (ISU) settings are essential for configuration. Emergency heat settings are available for specific models. Caution is advised regarding electrical hazards during installation. Proper disposal of mercury-containing controls is necessary for environmental safety. Fan control options allow for equipment or thermostat control. Backup heat source settings are specific to heat pump models. The temperature scale can be set to Fahrenheit or Celsius. The complete list of ISUs is available in the online installation manual.
  • Page 2: Pull to remove the thermostat from the UWP. Thermostat FocusPRO Serie N100 no programable TH1110U4000, TH1320U4002. Opciones ISU (los valores predeterminados están resaltados). Control de Ventilador en Calefacción. PRECAUCIÓN: PELIGRO ELÉCTRICO. Desconecte la corriente antes de comenzar la instalación. PRECAUCIÓN: AVISO DE MERCURIO. No tire el control antiguo a la basura. El producto y las pilas no deben desecharse con el resto de residuos domésticos. Para obtener asistencia con este producto, visite customer.resideo.com. La lista completa de ISUs se encuentra en el Manual de instalación en línea. Potencia nominal de entrada del dispositivo: 24 V, 60 Hz, 1,1 VA.