Home > Emerson > EMERSON 1D56-310 White-Rodgers Low Voltage Horizontal Mounting Thermostat Instruction Manual

EMERSON 1D56-310 White-Rodgers Low Voltage Horizontal Mounting Thermostat Instruction Manual

Factory-Installed Jumper  
RH  
W
B
O
Y
G
RC  
A
SET HEAT ANTICIPATOR  
5
Heat  
Relay  
Compressor  
Relay  
Fan  
Relay  
Hot  
Set anticipator to match the setting of your old thermostat you noted in Step 3, or, the  
anticipatorshouldbesettomatchthecurrentratingstampedonyourmainheatingcontrol.  
Theheatanticipatorisadjustablefrom0.15to1.2amps.Adjusttheanticipatorbyrotating  
thecontactarm(seefig.5).Theanticipatorsettingisindicatedbythenumbersonthebase  
that the pointer points to. If you are unsure where to set the anticipator contact the heater  
24 VAC  
120 VAC  
Neutral  
TRANSFORMER  
Figure 2. Typical wiring for single transformer heating/cooling system  
manufacturer for a recommended setting.  
Rotate contact arm  
to adjust heat anticipator  
RH  
W
B
A
O
Y
G
RC  
Move the pointer counterclockwise to  
TRANSFORMER  
Hot  
TRANSFORMER  
Hot  
Heat  
Relay  
Compressor  
Relay  
Fan  
Relay  
lengthen heating system cycles; move  
clockwise to shorten heating cycles.  
Adjustments should not be greater than  
1/2 marking at a time.  
24 VAC  
24 VAC  
120 VAC  
Neutral  
120 VAC  
Neutral  
Figure 3. Typical wiring for two-transformer heating/cooling system  
Snap on Cover: Carefully align the cover  
Factory-Installed Jumper  
Field-Installed Jumper  
with the base and snap the cover onto  
Arrow points to the  
current rating of  
the primary control  
RC  
G
RH  
O
W
Y
B
A
the base.  
TRANSFORMER  
Hot  
Fan  
Relay  
Compressor  
Relay  
*
* *  
24 VAC  
120 VAC  
Neutral  
Figure 5. Anticipator adjustment  
Terminal energized  
in cooling  
Terminal energized  
in heating  
*
* *  
NEWTHERMOSTATOPERATION  
6
Figure 4. Typical wiring for single transformer, single stage heat pump system  
This thermostat is easy to operate. After power is turned on, use the system switch to  
select either heating or cooling, or to turn the heating/cooling system off. Use the fan  
switch to control fan operation. When the fan switch is in the AUTO position, the fan will  
cycle with the heating or cooling system (the fan will not run if the system switch is in the  
OFF position and the fan switch is in the AUTO position). When the fan switch is in the  
ON position, the fan will run continuously, regardless of system switch position (even if  
the system switch is set to OFF, the fan will run if the fan switch is in the ON position).  
SPECIFICATIONS  
7
ELECTRICAL DATA  
Switch Rating...................................... 24 VAC (30 VAC max.)  
Heating ................................................. 0.15 to 1.2 Amps  
Cooling ................................................. 0 to 1.5 Amps  
Anticipator Rating:  
Heating ................................................. Adjustable from 0.15 to 1.2 Amps  
Cooling ................................................. Fixed  
THERMAL DATA:  
Temperature Range ............................ 50°F to 90°F (10°C to 32°C)  
Operating Humidity Range ................ 0 – 90% noncondensing  
TROUBLESHOOTING  
8
Symptom  
Possible Cause  
Corrective Action  
No Heat/No Cool/No Fan  
(common problems)  
1. Blown fuse or tripped circuit breaker.  
2. Furnace power switch to OFF.  
Replace fuse or reset breaker.  
Turn switch to ON.  
3. Furnace blower compartment door or  
panel loose or not properly installed.  
Replace door panel in proper position to engage  
safety interlock or door switch.  
No Heat  
1. Pilot light not lit.  
Re-light pilot.  
2. Broken or melted anticipator wire.  
Excessive current or dead short in system. Have a qualified service person check the system before  
replacing thermostat.  
3. Loose connection to thermostat or system.  
Verify thermostat and system wires are securely attached.  
4. Thermostat or heating system requires  
replacement or service.  
Your furnace manufacturer or service person can describe how to test the heating system to verify it is  
operating correctly. If the heating system is capable of operation and the no heat condition persists,  
replace the thermostat.  
5. System Switch not set to Heat.  
1. Furnace Lock-Out Condition  
Set System Switch to Heat and raise temp above room temp.  
Intermittent Heat  
No Cool  
Many furnaces have safety devices that shut the system down when a lock-out condition occurs. If the heat works  
intermittently contact the furnace manufacturer or local service person for assistance.  
1. Loose connection to thermostat or system.  
Verify thermostat and system wires are securely attached.  
2. Thermostat or cooling system requires  
replacement or service.  
Your cooling system manufacturer or service person can describe how to test the cooling system to verify it  
is operating correctly. If the cooling system is capable of operation and the no cooling condition persists,  
replace the thermostat.  
3. System Switch not set to Cool.  
Set System Switch to Cool and lower temp below room temp.  
Heat, Cool or Fan Runs  
Constantly.  
1. Possible short in wiring.  
Check each wire connection to the thermostat to verify it is neatly looped under the terminals. No extra  
wire should stick out from under the terminals.  
2. Possible short in thermostat.  
3. Possible short in heat/cool/fan system.  
Furnace Cycles Too Fast  
or Too Slow Narrow or  
wide temperature swing  
See Step 5, Adjusting the Anticipator.  
The anticipation setting is the only adjustment that effects the heating cycle rate. If an acceptable cycle rate  
is not achieved using the anticipator contact a local service person for additional suggestions. The location of  
the thermostat, size of the Heat/Cool System and current draw can influence the cycle rate.  
Cooling Cycles Too Fast  
or Too Slow (narrow or  
wide temperature swing)  
1. Poor thermostat location for sensing room  
temperature.  
The cycle rate for cooling can not be adjusted. The location of the thermostat, size of the Cool system and  
current draw can influence the cycle rate. Contact a local service person for suggestions.  
2. Cooling system over or undersized.  
3. Excessive Current draw influencing thermostat.  
Thermostat Setting and  
Thermostat Thermometer  
Disagree  
1. Thermostat thermometer setting requires  
adjustment.  
The thermometer can be adjusted by using a standard slotted screwdriver. Turn the thermometer pointer  
screw located inside the front cover to change the setting. For calibrating the setting lever contact a local  
heating and cooling service person.  
2. Thermostat setting lever requires calibration.  
Adjusting Thermometer  
1. Thermostat thermometer disagrees with  
other room thermometers.  
The thermometer on the thermostat is accurately calibrated at our factory but you can adjust it by using a  
standard slotted screwdriver. Turn the thermometer pointer screw located inside the front cover to change  
the setting.  
The Emerson logo is a  
trademark and service mark  
of Emerson Electric Co.  
GeneralDetails
NameEMERSON 1D56-310 White-Rodgers Low Voltage Horizontal Mounting Thermostat Instruction Manual
MakeEmerson
LanguageEnglish
FiletypePDF (Download)
File size0.1 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
EMERSON ST75W Sensi Touch Wi-Fi Smart Thermostat Installation Guide
EMERSON ST75W Sensi Touch Wi-Fi Smart Thermostat Installation Guide
EMERSON Thermostat Common Wire Kit SA11 Instruction Manual
EMERSON Thermostat Common Wire Kit SA11 Instruction Manual
EMERSON 1F75H-21PR Programmable Heat Pump Thermostat Instruction Manual
EMERSON 1F75H-21PR Programmable Heat Pump Thermostat Instruction Manual
EMERSON 1F75C-11PR Programmable Thermostat Installation Guide
EMERSON 1F75C-11PR Programmable Thermostat Installation Guide
EMERSON Programmable Touchscreen Thermostat Setup in E2 and Site Supervisor User Guide
EMERSON Programmable Touchscreen Thermostat Setup in E2 and Site Supervisor User Guide
EMERSON 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
EMERSON 1F76U-22WFB Series Sensi Lite Smart Thermostat Installation Guide
EMERSON 1F87U-42WF Sensi Smart Thermostat User Guide
EMERSON 1F87U-42WF Sensi Smart Thermostat User Guide
EMERSON 1F83C-11NP Single Stage Thermostat Owner’s Manual
EMERSON 1F83C-11NP Single Stage Thermostat Owner’s Manual
EMERSON 1F75P-21PR Display Thermostat Instruction Manual
EMERSON 1F75P-21PR Display Thermostat Instruction Manual
EMERSON 1F75H-21NP Non Programmable Heat Pump Thermostat Instruction Manual
EMERSON 1F75H-21NP Non Programmable Heat Pump Thermostat Instruction Manual

EMERSON 1D56-310 White-Rodgers Low Voltage Horizontal Mounting Thermostat Instruction Manual