ELKO ep TEV-1 Thermostat Owner’s Manual
EN
TEV-1
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
Thermostat
Made in Czech Republic
02-210/2016 Rev.: 2
Characteristics
Symbol
L
• two-level thermostat with function “WINDOW” meaning that output is switched
in case the measured temperature is within set range (adjustable in range -20..
+20 °C / -4 °F to +68 °F)
T
T
° C
N
• used as protection against freezing (water-shoots, pavements, drives, pipes, etc.)
heating is on when temperature falls under set upper level (e.g. +5 °C / +41 °F)
and off in case it falls under lower level (e.g. -10 °C / 14 °F, when heating is not able
effectively operate)
V2 V1
• thermostat is placed in water-proof box with IP65, which allows installation
outside, with in-built sensor TZ-0 (included in the supply)
Connection
• thermostat status is indicated by LED (3colours) under transparent cover
• function monitoring short-circuit and sensor disconnection (break)
• output changeover contact 16 A / SPDT (AC1)
Function heating
Description
1. Device status indication
2. Bottom temperature setting
3. Upper temperature setting
1
4. Terminal for sensor
2
3
4
5. Terminals for connection of supply
voltage and output contact
5
7
6. Sensor TZ-0
7. Sleeve for incoming cables
Function cooling
6
HAL.230V
M
M
cos φ ≥ 0.95
Type of load
AC5a
uncompensated
AC5a
compensated
AC1
AC2
AC3
AC5b
800W
AC6a
x
AC7b
AC12
Mat. contacts AgNi,
contact 16 A
x
250V / 16A
250V / 5A
250V / 3A
230V / 3A (690VA)
250V / 3A
250V / 10A
M
M
K
Type of load
DC3
AC13
AC14
AC15
DC1
DC5
DC12
DC13
DC14
Mat. contacts AgNi,
contact 16 A
24V / 6A
250V / 6A
250V / 6A
250V / 6A
24V / 16A
24V / 4A
24V / 16A
24V / 2A
24V / 2A
1 / 2