Dettson 2-Stage WiFi Thermostat R02P033 Owner’s Manual
1.2 Wiring Diagram
(a) Conventionnal system
(b) Heat pump system
Information
Terminal Definition
RC
Cooling Power (if 2 transformers) Jumpered with R (if only one transformer)
Heating Power
R
W (O/B)
Heating output
Cooling output
Fan output
Reversing valve output (heat pump)
Compressor output (heat pump)
Y
G
Y2
Cooling output 2nd stage
W2 (AUX) Heating output 2nd stage
Compressor output 2nd stage (heat pump)
Auxiliary heat output (heat pump)
1.3 System Modes
#
0.0 1H/1C (conventional) R, C, W, Y
Type
Terminals
System
Compressor delay
1.0 1H/2C
2.0 2H/2C
3.0 2H/1C
4.0 1H/1C
5.0 2H/1C
6.0 2H/2C
7.0 3H/2C
R, G, W, Y, Y2
Conventionnal
N/A
R, G, W, Y, W2, Y2
R, G, W, Y, W2
R, G, O/B, Y
R, G, O/B, Y, AUX
R, G, O/B, Y, Y2
R, G, O/B, Y, AUX, Y2
Heat pump
1 min (default)
5