Home > Danfoss > Danfoss RT 8L Thermostat Installation Guide

Danfoss RT 8L Thermostat Installation Guide

the knob 5. The setting can be read on the  
main scale 9.  
The required neutral zone (NZ) is found in the  
diagram. On the lower scale of the diagram,  
the value at which the neutral zone setting  
disc 40 is to be set, can be read.  
RESET) er det nødvendigt at montere denne  
kabelforskruning som vist i fig. 10. Hvis denne  
kabelforskruning ikke bruges sammen med et  
kabel, bør der monteres en blindprop (metal  
skive).  
ENGLISH  
Thermostats  
with neutral zone  
Technical data  
Mechanical differential (DIFF)  
RT 8L and RT 16L: 1.5K (2.7 °F)  
RT 14L: 1.5K (2.7 °F) / 0.7K (1.3 °F)  
min./max. range  
RT 101L: 2.5K (4.8 °F) / 3.5K (6.7 °F)  
min./max. range  
Benyt monteringshullerne pos. 25.  
Termostaten monteres bedst med  
håndknappen 5 opad.  
Termostathuset og kapillarrøret kan  
anbringes koldere eller varmere end føleren.  
For RT 8L og RT 14L kan den cylindriske føler  
fastgøres til væg ved hjælp af en følerholder  
26 eller monteres i brinetank ved hjælp af et  
dykrør 30 eller en kapillar-rørspakdåse 31.  
Se fig. 1.  
Example: RT 8L  
Required temperature: -2.5 °C (27.5 °F).  
Required neutral zone (NZ): 3 °C (5.5 °F).  
The thermostat is set for -2.5 °C (27.5 °F) by  
rotating the knob 5.  
RT 140L: 1.8K (3.2 °F) / 2K (3.8 °F)  
min./max. range  
As it can be seen from the diagram, the re-  
quired dead zone of 3 °C (5.5° F) is obtained  
by setting the setting disc 40 at 2.4.  
The make and break temperatures of the  
switch (see fig. 5) are then – with the differen-  
tial fixed at 1 °C (1.8 °F):  
Maximum ambient temperature  
RT 8L, RT 14L, RT 101L, RT 140L:  
-50 °C (-58 °F) − 70 °C (160 °F)  
RT 16L: 50 °C (120 °F)  
Skal kapillarrøret føres gennem en væg, gøres  
dette lettest via et indmuret rør, der lukkes  
med gummipropper.  
Make temperature of contacts  
1–4 = -2.5 °C + 1 °C = -1.5 °C (27.5 °F + 1.8 °F =  
29.3 °F).  
Maximum bulb temperature  
El-tilslutning  
Kabeltilslutning Pg 13.5.  
Kabeldiameter 6 − 14 mm.  
Ved stiv kabelbeskyttelse anvendes  
kabelforskruningen vist på fig. 11.  
Jordforbindelsen tilsluttes jordskruen 38.  
RT 8L:  
RT 14L:  
RT 16L:  
145 °C (290 °F)  
150 °C (300 °F)  
100 °C (210 °F)  
Break temperature of contacts  
1-4 = temperature setting: -2.5 °C (27.5 °F).  
RT 101L: 300 °C (570 °F)  
RT 140L: 240 °C (465 °F)  
Make temperature of contacts  
1-2 = -1.5 °C - 3 °C = -4.5 °C (29.3 °F - 5.5 °F =  
23.8 °F).  
Min. temperature variation rate  
< 1K/15 minutes.  
Indstilling  
Break temperature of contacts  
1-2 = -4.5 °C + 1 °C = -3.5 °C (23.8 °F + 1.8 °F =  
25.6 °F).  
Den ønskede temperatur (= brydetempera-  
turen for kontakterne 2-3) indstilles ved hjælp  
af håndknappen 5. Indstillingen aflæses på  
områdeskalaen 9. Den ønskede neutralzone  
(NZ) opsøges i diagrammet.  
På diagrammets nederste skala aflæses den  
position, neutralzonerullen 40 skal indstilles  
på.  
Enclosure  
IP 66 acc to IEC 529.  
DANSK  
Rating  
See switch cover or fig. 10.  
The marking, e.g. 10 (4) A, 400 V ~ AC means  
that max. connection current is 10 A ohmic  
and 4 A inductive at 400 V ~.  
Termostater  
med neutralzone  
Tekniske data  
Fast differens (DIFF)  
RT 8L og RT 16L: 1.5K  
Eksempel: RT 8L  
Ønsket temperatur: -2.5 °C (27.5 °F).  
Ønsket neutralzone (NZ): 3 °C (5.5 °F).  
The max. starting current on motor cutin (L.R.)  
may be up to seven times the inductive load.  
RT 14L:  
1.5K/0.7K i min./maks. område  
RT101L: 2.5K/3.5K i min./maks. område  
RT 140L: 1.8K/2K i min./maks. område  
Med håndknappen 5 indstilles termostaten på  
-2.5 °C (27.5 °F) Som det ses af diagrammet,  
opnås den ønskede neutralzone på  
3 °C (5.5° F) ved at indstille neutralzonerullen  
40 på positionen 2.4.  
Slutte- og brydetemperaturerne for  
kontaktsystemet (se fig. 5) bliver herved, idet  
den faste differens = 1 °C (1.8 °F):  
Fitting  
A set of Pg13.5 cable gland is attached to the  
RT in a separate bag. To ensure IP66 (units  
with automatic reset) or IP54 (units with ex-  
ternal reset) grade of RT enclosure it is neces-  
sary to assemble this gland as shown in the  
fig. 10. If this gland is not used with a cable, a  
metal blinding should be also assembled.  
Maks. omgivelsestemperatur  
RT 8L, RT 14L, RT 101L, RT 140L:  
-50 °C (-58 °F) − 70 °C(160 °F)  
RT 16L: 50 °C (120 °F)  
Maks. følertemperatur  
Sluttetemperatur for kontakterne  
1-4 = –2.5 °C +1 °C = -1.5 °C (27.5 °F + 1.8 °F =  
29.3 °F).  
RT 8L:  
RT 14L:  
RT 16L:  
145 °C (290 °F)  
150 °C (300 °F)  
100 °C (210 °F)  
Use the mounting holes item 25.  
The thermostat is fitted best with the knob 5  
facing upwards.  
The thermostat housing and the capillary  
tube can be placed colder or warmer than the  
bulb.  
In the case of RT 8L and RT14L, the cylindrical  
bulb can be fixed to a wall by using a bulb  
holder 26 or it can be fitted in a brine tank by  
means of a bulb pocket 30 or in capillary tube  
gland 31. See fig. 1.  
Brydetemperatur for kontakterne  
1-4 = indstillet temperatur: –2.5°C (27.5 °F).  
RT 101L: 300 °C (570 °F)  
RT 140L: 240 °C (465 °F)  
Sluttetemperatur for kontakterne  
1-2 = –1.5°C - 3°C = -4.5°C 29.3 °F - 5.5 °F =  
23.8 °F).  
Min. temperaturændringshastighed  
< 1K/15 minutter.  
Brydetemperatur for kontakterne  
1-2 = -4.5 °C + 1 °C = -3.5°C (23.8 °F + 1.8 °F =  
25.6 °F).  
Tæthedsgrad  
IP 66 iht. IEC 529.  
If the capillary tube is to be passed through  
a wall, it can be done most easily by using a  
grouted-in pipe closed by rubber plugs.  
Kontaktbelastning  
Se kontaktdækslet eller fig. 10.  
Mærkningen, f.eks. 10 (4) A, 400 V ~ AC  
angiver, at der maks. må tilsluttes 10 A ohmsk  
og i A induktiv belastning ved 400 V~.  
Den maksimale startstrøm ved indkobling  
af motor (L.R.) må være op til syv gange den  
induktive belastning.  
Electrical connection  
Cable connection Pg 13.5.  
Cable diameter 6 − 14 mm.  
The screwed cable entry shown in fig. 11 is  
used with rigid cable conduit. Earth connec-  
tion to earth terminal 38.  
Montering  
Et sæt Pg13,5 kabelforskruning er vedlagt  
produktet i en separat pose. For at sikre  
kapslingsgrad IP66 (enheder med automatisk  
reset) eller IP54 (enheder med ekstern  
Setting  
The required temperature (= break  
temperature of contacts 2-3) is set by rotating  
AN12088643530601-000202 | 2  
© Danfoss | Climate Solutions | 2021.07  
GeneralDetails
NameDanfoss RT 8L Thermostat Installation Guide
MakeDanfoss
LanguageEnglish
FiletypePDF (Download)
File size0.69 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide
Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide
Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide
Danfoss UT 72-UT 73 Universal Thermostat Installation Guide
Danfoss UT 72-UT 73 Universal Thermostat Installation Guide
Danfoss ECtemp 530 Electronic Thermostat Installation Guide
Danfoss ECtemp 530 Electronic Thermostat Installation Guide
Danfoss 014G0251 Eco Radiator Thermostat User Guide
Danfoss 014G0251 Eco Radiator Thermostat User Guide
Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide
Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide
Danfoss RET230P Electronic Thermostat Instruction Manual
Danfoss RET230P Electronic Thermostat Instruction Manual
Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide
Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide
Danfoss RET1000 Series Electronic Thermostat User Guide
Danfoss RET1000 Series Electronic Thermostat User Guide

Danfoss RT 8L Thermostat Installation Guide