Danfoss RT 115 Thermostat Installation Guide
Installation guide
Thermostat
RT 115
089
RT 115
Fig. 2
Code no. 017-519766
Code no. 017-519866
230V
400V
230V
Fig. 1
Fig. 3
Fig. 4
(units with automatic reset) or IP54 (units
with external reset) grade of RT enclosure
it is necessary to assemble this gland as
shown in the fig. 3. If this gland is not used
with a cable, a metal blinding should be
also assembled.
ENGLISH
RT 115
DANSK
RT 115
Anvendelse
Application
Termostat type RT 115 anvendes til styring
af tvungen ventilation i stalde og hønse-
huse.
The thermostat type RT 115 is designed
for control of forced ventilation in livestock
buildings and hencoops.
Fitting
Termostaten bevirker at der ventileres
uafbrudt sålænge rumtemperaturen er
højere end indstil-lingstemperaturen. Er
rumtemperaturen lavere, ventileres der
kun periodevis.
The thermostat has the effect of constant
ventilation as long as the room tempera-
ture exceeds the temperature setting.
The thermostate should be fitted in the
centre of the building, but in such a
position that the body heat from the larger
animals cannot directly influence the
thermostat.
If the room temperature is lower than the
temperature setting, there wil only be
intermittent ventilation. The cut-out period
is extended when the room temperature
falls, and if the temperature falls, and if
the room temperature is 2°C lower than
the temperature setting, the thermostat
cannot start the fan.
Udkoblingsperioden forlænges med
faldende rumtemperatur; og er rumtem-
peraturen 2°C lavere end indstil-lings-
temperaturen kan termostaten ikke starte
ventilatoren.
Setting
Set the thermostat by rotating the knob (5)
for a temperature which is approx. 1°C
higher than actually desired in the building.
RT 115´s specielle styreform skyldes den
ekstra føler (B) inden i termostathuset.
Langs føleren ligger et elvarmelegeme (C)
der kobles ind når ventilatoren kobles ud
og vice versa.
• If the fan then runs continuously, the
capacity of the fan is to low of the
outdoor temperature is too high
• If the fan runs intermittently, the
plant operation should not be iterfered
with until a stable room temperature is
reached. If the room temperature is then
too high or too low, resetting is done
• If the fan does not start, the room
temperature is too low to permit
ventilation.
The special kind of control offered by
RT 115 is due to the extra sensor (B) inside
the thermostat housing. Alongside the
sensor there is an electric heater (C) which
is cut in when the fan is cut out, and vice
versa.
Montering
Et sæt Pg13,5 kabelforskruning er vedlagt
produktet i en separat pose. For at sikre
kapslingsgrad IP66 (enheder med automa-
tisk reset) eller IP54 (enheder med ekstern
RESET) er det nødvendigt at montere
Installation
A set of Pg13.5 cable gland is attached to
the RT in a separate bag. To ensure IP66
AN00008643546501-000102 | 1
© Danfoss | Climate Solutions | 2021.07
| General | Details |
|---|---|
| Name | Danfoss RT 115 Thermostat Installation Guide |
| Make | Danfoss |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.3 MB |

Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide

Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide

Danfoss UT 72-UT 73 Universal Thermostat Installation Guide

Danfoss ECtemp 530 Electronic Thermostat Installation Guide

Danfoss 014G0251 Eco Radiator Thermostat User Guide

Danfoss RET230P Electronic Thermostat Instruction Manual

Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide

Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide

Danfoss RET1000 Series Electronic Thermostat User Guide

Danfoss RT 115 Manual: Questions and Answers
What does the extra sensor inside the Danfoss RT 115 do?
The extra sensor (B) inside the housing enables the special control method. An electric heater (C) alongside it activates when the fan cuts out, and deactivates when the fan runs. Installation Guide, p. 1
How do I install the Danfoss RT in my livestock building?
Mount the thermostat in the centre of the building where body heat from larger animals cannot directly affect it. A Pg13.5 cable gland is provided to maintain the IP66 or IP54 enclosure rating. Installation Guide, p. 1
What happens if the room temperature on a Danfoss RT 115 falls 2°C below the set point?
The thermostat cannot start the fan. The cut-out period lengthens as room temperature drops, allowing only intermittent ventilation until temperature rises closer to the setting. Installation Guide, p. 1