amount that they were adjusted, prior to entering  
Auto.  
About Advanced Features and Operation  
• HOLIDAY MODE — This feature forces the thermo-  
stat into Unoccupied for a preset duration, up to  
99 days. The Holiday setup display is entered as  
follows:  
For example: If the Cool set point was set to 80  
while in the Cool mode and the Heat set point was  
adjusted to 70 while in the Heat mode, upon enter-  
ing the Auto mode the Heat and Cool set points  
would be 80 and 70. Both set point temperatures  
would then move up and down together, (in this  
example spread by 10 degrees), by pressing the up  
or down buttons.  
1
HOLIDAY  
To move the Heat and Cool set point temperatures  
closer together, enter the Cool or Heat mode by  
pressing the Mode button, then adjust the set point  
temperatures closer together. Heat is limited to how  
close it can come to Cool by Step 5, page 4.  
2
• REMOTE SENSORS (Optional Accessory) —  
When connected to terminals RS+5, RS, and GND  
on the back of the thermostat, the thermostat will  
read the temperature from the Remote Sensor and  
ignore the temperature sensor inside the thermo-  
stat. The thermostat automatically recognizes when  
a Remote Sensor is connected. When reading the  
temperature from the remote, the degree icon  
above the room temperature blinks once a second.  
The thermostat will enter the Holiday mode when  
the clock crosses midnight.  
During Holiday mode Unoccupied set points are  
enforced.  
The Override button  
on the Remote Sensor  
works slightly different  
than the Override but-  
ton on the front panel.  
Each press of the  
‘External’ Override but-  
ton adds 2 hours to the  
The Override button is active during Holiday mode.  
It will override to Occupied 1 settings up to 4 hours  
then return to Holiday mode. The Dry Contact  
Switch is ignored.  
OVER  
RIDE  
OVER  
RIDE  
The thermostat will exit Holiday mode at midnight of  
the final programmed day. To terminate Holiday  
immediately, enter the Holiday setup screen and  
select 0.  
Optional  
Remote Sensor  
Optional Sensor  
override timer. If the  
timer was already active, the first button press will  
round the runtime to either 2:00 or 4:00.  
• SOFT START — This feature is utilized in multiple  
thermostat installations controlled by the Dry Con-  
tact terminals. Assigning a unique Soft Start num-  
ber to each thermostat will stagger the turn on  
times, even though the Dry Contact closes, for all  
the thermostats connected, at the same time. Each  
Soft Start number represents a multiple of 30 sec-  
onds from the Dry Contact closure. For example,  
no. 1 = turn on 30 seconds after Dry Contact clo-  
sure, no. 2 = turn on 60 seconds after closure,  
no. 3 = turn on 90 seconds after closure, and so on.  
See page 5, Step 13, to configure the thermostat for  
Soft Start.  
Subsequent button presses will not wraparound as  
the Override button on the thermostat does, so the  
second or greater button press will set the runtime  
to 4:00. The Locked feature has no effect on the  
external Override button. The wired Remote Sensor  
is connected to the thermostat with up to 500 ft of  
20 ga. or 300 ft of 18 ga. thermostat wire. See the  
Remote Sensor instructions for further details.  
• FACTORY DEFAULTS — Before restoring factory  
defaults, set thermostat to OFF mode. If, for any  
reason it is desirable to return all stored settings  
back to the factory default settings, press the Mode  
button. While holding the Mode button in, press the  
Fan button for 5 seconds. All icons will appear.  
Press and hold in the Fan button until Fd appears.  
This resets all factory settings. To calibrate room  
temperature, press the Up and Down buttons at  
the same time twice. At this point use the Up and  
Down buttons to calibrate room temperature, if  
needed. Press the Mode button to return to normal  
operation.  
• DUAL SET POINT BEHAVIOR — The adjustable  
set point range is: 35 to 99 degrees in Fahrenheit  
and 7 to 35 degrees in Celsius. When in the modes  
Heat or Cool, this adjustable range is unhampered.  
When adjusting any Auto mode, including program-  
ming Occupied and Unoccupied periods, the ther-  
mostat will not allow the Heat set point to get closer  
to the Cool set point than the value programmed as  
the minimum difference in Step 5, page 4.  
When entering the Auto mode from Cool, the Heat  
and Cool set points will remain spread apart by the  
Page 6  
GeneralDetails
NameCarrier 53DFS250-SL Programmable Digital Thermostat Owner’s Manual
MakeCarrier
LanguageEnglish
FiletypePDF (Download)
File size0.48 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Carrier 33TWSPL-4 Wifi Stat Plus Thermostat Owner’s Manual
Carrier 33TWSPL-4 Wifi Stat Plus Thermostat Owner’s Manual
Carrier EB-STATE3LTICB-01 lLite Smart Thermostat Instructions
Carrier EB-STATE3LTICB-01 lLite Smart Thermostat Instructions
Carrier ecobee3 Lite Smart Thermostat User Manual
Carrier ecobee3 Lite Smart Thermostat User Manual
Carrier EB-STATE7ICR-01 Ecobee for Smart Thermostat Owner’s Manual
Carrier EB-STATE7ICR-01 Ecobee for Smart Thermostat Owner’s Manual
Carrier TSTATCCEWF-01 Smart Thermostat Owner’s Manual
Carrier TSTATCCEWF-01 Smart Thermostat Owner’s Manual
Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide
Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide
Carrier Wi-Fi Enabled 24V Smart Thermostat Instruction Manual
Carrier Wi-Fi Enabled 24V Smart Thermostat Instruction Manual

Carrier 53DFS250-SL Programmable Digital Thermostat Owner’s Manual