• MINIMUM HEAT/COOL SET POINT DIFFERENCE  
— The Heat and Cool set point temperature will not  
be allowed to come any closer to each other than  
the value set in Advanced Setup Step 5, on page 4.  
This minimum difference is enforced during Auto  
changeover and Program On operation.  
Advanced Setup  
F
• ENERGY SAVING SMART FAN — If Fan On is  
selected, the fan will run continuously at all times,  
except in Off, and will only run if there is a heating  
or cooling demand in Unoccupied periods.  
• OVERRIDE — As explained on page 3, pressing  
the Override button during a programmed, Unoccu-  
pied period will force the thermostat into Occupied  
1, temporarily, up to 4 hours. If the Override button  
is pressed during an Occupied period, the thermo-  
stat will be forced into Unoccupied and the occu-  
pied number (1,2 or 3), it was forced out of will be  
turned off, only for that day.  
During Override periods the set point temperature  
may be adjusted, but they will not be remembered  
after Override ends.  
• HEAT First Stage = Heat Pump. Second Stage =  
Heat Pump and Electric Heat.  
• FAN PURGE TIMER — When this feature is acti-  
vated, the fan will turn on during Unoccupied at a  
preset amount of time prior to Occupied 1. This pre-  
occupancy fan purge timer may be set as instructed  
on this page, Step 12, from 0 to 3 hours. 0 = this  
feature turned off.  
=
to  
Press the Mode button. While holding the Mode, press the Program button  
leave the Setup screens. If no buttons are pressed, the display will leave the  
setup screens after 30 seconds.  
• KEYPAD LOCK — To prevent unauthorized use of  
the thermostat, the front panel buttons may be dis-  
abled. To disable, or ‘lock’ the keypad, press and  
hold in the Mode button. While holding the Mode  
button in, press the Up and Down buttons in  
together. The Locked icon will appear on the  
display.  
Advanced Setup Table  
STEP  
NO.  
FACTORY  
DEFAULT  
DESCRIPTION  
Time of day clock set  
RANGE  
1
2
3
4
24 hour  
Su - Sa  
Off / On  
1 - 6 F  
12:00 Am  
Mo  
Day of the week  
Program On  
:
Heat Pump  
Off  
Pm  
unoccupied  
W
Deadband or Temperature swing  
2 F  
Forced minimum difference heat/  
cool  
ON  
Locked  
5
0 - 6 F  
2 F  
6
7
Cycles per hour  
d, d1, 2 - 6  
0 - 3  
6
0
Security Levels  
8
Maximum allowable Heat set point  
Minimum allowable Cool set point  
Fahrenheit or Celsius  
35 - 99 F  
35 - 99 F  
F / C  
80 F  
65 F  
F
9
To unlock the buttons, again press and hold the  
Mode button. While holding the Mode button in,  
press the Up and Down buttons in together. The  
Locked icon will disappear from the display.  
10  
11  
Thermoglow™ backlight  
Off / On  
On  
0:00 - 3:00  
min.  
12  
13  
Fan Purge timer  
Soft Start  
0:00 min.  
0
0 - 99  
• DRY CONTACT SWITCH — The terminals are ‘nor-  
mally open’. Closing or completing the circuit will  
cause the thermostat to enter Occupied 1. This fea-  
ture allows an external device such as a Central  
Time Clock, Occupancy Sensor, or a Telephone  
activated device to force 1 or more thermostats into  
Occupied 1. For the Dry Contact to work the ther-  
mostat must be in Program On. Set Occupied 1  
to Off for all 7 days, so the Contact closure will be in  
control. When the thermostat is forced into  
About Advanced Features and Operation  
• CLOCK BACKUP — In the event of a power loss,  
the thermostat internal clock will continue to keep  
proper time for a minimum of 48 hours without  
external power or batteries.  
• TWO-STAGE OPERATION — The Second Stage of  
heat (Heat pump models only) is turned on when  
(1) the first Stage has been on for a minimum of two  
minutes, and (2) the temperature spread from the  
set point is equal to or greater than: the set point  
temperature plus the deadband, plus 2 degrees.  
Occupied 1 via the Dry Contact closure, the icon  
Occupied 1 will blink.  
CK1  
GND  
Heating  
Cooling  
Dead  
Band  
Dead  
Band  
2 degrees 2 degrees  
2 degrees 2 degrees  
Cool  
turn on Set Point Set Point  
1st Stage  
Low  
1st Stage  
turn on  
2nd Stage  
turn on  
3rd Stage 2nd Stage  
1st Stage Heat  
Fan Speeds  
Low  
Med  
High  
High  
Med  
Page 5  
GeneralDetails
NameCarrier 53DFS250-SL Programmable Digital Thermostat Owner’s Manual
MakeCarrier
LanguageEnglish
FiletypePDF (Download)
File size0.48 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Carrier 33TWSPL-4 Wifi Stat Plus Thermostat Owner’s Manual
Carrier 33TWSPL-4 Wifi Stat Plus Thermostat Owner’s Manual
Carrier EB-STATE3LTICB-01 lLite Smart Thermostat Instructions
Carrier EB-STATE3LTICB-01 lLite Smart Thermostat Instructions
Carrier ecobee3 Lite Smart Thermostat User Manual
Carrier ecobee3 Lite Smart Thermostat User Manual
Carrier EB-STATE7ICR-01 Ecobee for Smart Thermostat Owner’s Manual
Carrier EB-STATE7ICR-01 Ecobee for Smart Thermostat Owner’s Manual
Carrier TSTATCCEWF-01 Smart Thermostat Owner’s Manual
Carrier TSTATCCEWF-01 Smart Thermostat Owner’s Manual
Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide
Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide
Carrier Wi-Fi Enabled 24V Smart Thermostat Instruction Manual
Carrier Wi-Fi Enabled 24V Smart Thermostat Instruction Manual

Carrier 53DFS250-SL Programmable Digital Thermostat Owner’s Manual