• MINIMUM HEAT/COOL SET POINT DIFFERENCE
— The Heat and Cool set point temperature will not
be allowed to come any closer to each other than
the value set in Advanced Setup Step 5, on page 4.
This minimum difference is enforced during Auto
changeover and Program On operation.
Advanced Setup
F
• ENERGY SAVING SMART FAN — If Fan On is
selected, the fan will run continuously at all times,
except in Off, and will only run if there is a heating
or cooling demand in Unoccupied periods.
• OVERRIDE — As explained on page 3, pressing
the Override button during a programmed, Unoccu-
pied period will force the thermostat into Occupied
1, temporarily, up to 4 hours. If the Override button
is pressed during an Occupied period, the thermo-
stat will be forced into Unoccupied and the occu-
pied number (1,2 or 3), it was forced out of will be
turned off, only for that day.
During Override periods the set point temperature
may be adjusted, but they will not be remembered
after Override ends.
• HEAT — First Stage = Heat Pump. Second Stage =
Heat Pump and Electric Heat.
• FAN PURGE TIMER — When this feature is acti-
vated, the fan will turn on during Unoccupied at a
preset amount of time prior to Occupied 1. This pre-
occupancy fan purge timer may be set as instructed
on this page, Step 12, from 0 to 3 hours. 0 = this
feature turned off.
=
to
Press the Mode button. While holding the Mode, press the Program button
leave the Setup screens. If no buttons are pressed, the display will leave the
setup screens after 30 seconds.
• KEYPAD LOCK — To prevent unauthorized use of
the thermostat, the front panel buttons may be dis-
abled. To disable, or ‘lock’ the keypad, press and
hold in the Mode button. While holding the Mode
button in, press the Up and Down buttons in
together. The Locked icon will appear on the
display.
Advanced Setup Table
STEP
NO.
FACTORY
DEFAULT
DESCRIPTION
Time of day clock set
RANGE
1
2
3
4
24 hour
Su - Sa
Off / On
1 - 6 F
12:00 Am
Mo
Day of the week
Program On
:
Heat Pump
Off
Pm
unoccupied
W
Deadband or Temperature swing
2 F
Forced minimum difference heat/
cool
ON
Locked
5
0 - 6 F
2 F
6
7
Cycles per hour
d, d1, 2 - 6
0 - 3
6
0
Security Levels
8
Maximum allowable Heat set point
Minimum allowable Cool set point
Fahrenheit or Celsius
35 - 99 F
35 - 99 F
F / C
80 F
65 F
F
9
To unlock the buttons, again press and hold the
Mode button. While holding the Mode button in,
press the Up and Down buttons in together. The
Locked icon will disappear from the display.
10
11
Thermoglow™ backlight
Off / On
On
0:00 - 3:00
min.
12
13
Fan Purge timer
Soft Start
0:00 min.
0
0 - 99
• DRY CONTACT SWITCH — The terminals are ‘nor-
mally open’. Closing or completing the circuit will
cause the thermostat to enter Occupied 1. This fea-
ture allows an external device such as a Central
Time Clock, Occupancy Sensor, or a Telephone
activated device to force 1 or more thermostats into
Occupied 1. For the Dry Contact to work the ther-
mostat must be in Program On. Set Occupied 1
to Off for all 7 days, so the Contact closure will be in
control. When the thermostat is forced into
About Advanced Features and Operation
• CLOCK BACKUP — In the event of a power loss,
the thermostat internal clock will continue to keep
proper time for a minimum of 48 hours without
external power or batteries.
• TWO-STAGE OPERATION — The Second Stage of
heat (Heat pump models only) is turned on when
(1) the first Stage has been on for a minimum of two
minutes, and (2) the temperature spread from the
set point is equal to or greater than: the set point
temperature plus the deadband, plus 2 degrees.
Occupied 1 via the Dry Contact closure, the icon
Occupied 1 will blink.
CK1
GND
Heating
Cooling
Dead
Band
Dead
Band
2 degrees 2 degrees
2 degrees 2 degrees
Cool
turn on Set Point Set Point
1st Stage
Low
1st Stage
turn on
2nd Stage
turn on
3rd Stage 2nd Stage
1st Stage Heat
Fan Speeds
Low
Med
High
High
Med
Page 5
| General | Details |
|---|---|
| Name | Carrier 53DFS250-SL Programmable Digital Thermostat Owner’s Manual |
| Make | Carrier |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.48 MB |

Carrier 33TWSPL-4 Wifi Stat Plus Thermostat Owner’s Manual

Carrier EB-STATE3LTICB-01 lLite Smart Thermostat Instructions

Carrier ecobee3 Lite Smart Thermostat User Manual

Carrier EB-STATE7ICR-01 Ecobee for Smart Thermostat Owner’s Manual

Carrier TSTATCCEWF-01 Smart Thermostat Owner’s Manual

Carrier 33WIFISTAT43 Wi-Fi Thermostat Installation Guide

Carrier Wi-Fi Enabled 24V Smart Thermostat Instruction Manual