Braeburn 8205-100-02 Universal Smart Wi-Fi Thermostat Instruction Manual
No. Installer Setting
Displayed Default Available Description of
Setting Settings Available Settings
OFF
ON
Auto-Changeover disabled
Auto-Changeover enabled
8
Auto Changeover
AUTO CNG
OFF
When auto-changeover mode is enabled and selected, the system can automatically switch between heating and
cooling modes. There is a 5 minute delay when switching modes if auto changeover is selected. Auto changeover may
affect your setpoint limit options in settings 21-24.
2, 3, 4, 5 Select an Auto Changeover Dead Band of
2°, 3°, 4° or 5˚ F (1°, 2° or 3° C)
9
Auto Changeover
Dead Band
DEADBAND
3
[Only available if Auto Changeover was enabled in setting 8] When using auto changeover mode, the dead band
is a forced separation between the heating and cooling setpoints so that the systems do not work against each other.
This setting selects the amount of this dead band in degrees.
10 Conventional Heat
Fan Control
FAN 1
GAS
GAS
Select for conventional Gas heating
ELEC
Select for conventional Electric heating
[Only available if a conventional system was selected in setting 4] Selects a 1st stage fan control of either
gas or electric heat. If Electric is selected, the thermostat turns on the system fan with a call for heating.
ELEC
GAS
Select for Electric Emergency Heat
Select for Gas Emergency Heat
11 Emergency Heat
Fan Control
EMER FAN
ELEC
[Only available if a 2 or 3 stage heat pump system was selected in setting 4] Selects emergency heat fan control
of either gas or electric heat. If Electric is selected, the thermostat turns on the system fan with a call for emergency heat.
90, 60,
30, 0
Select fan delay duration in seconds
12 Residual Cooling
Fan Delay
RESIDUAL 60
COOL
Selects a delay for the system fan after the cooling compressor has turned off. This delay will help remove the remaining
cool air out of the ductwork providing additional efficiency.
OFF
ON
Circulating Fan Lock is disabled
Circulating Fan Lock is enabled
13 Circulating Fan Lock
CIRCLOCK
OFF
When enabled, the only user fan settings available are ON and CIRC (Circulation). The AUTO and PROG fan settings are
not available with this setting enabled.
0
B
Select for cool active Reversing Valve
Select for heat active Reversing Valve
14 Reversing Valve
(O/B Terminal)
R VALVE
0
[Only available if a heat pump system was selected in setting 4] Selects the output state of the O/B terminal. Select
O for this terminal to be active in the cool mode or select B for this terminal to be active in the heat mode.
5, 4, 3,
2, 1, 0
Select CSCP delay duration in minutes
15 Compressor Short Cycle CSCP MIN
Protection (CSCP)
5
Selects the number of minutes the compressor(s) will be locked out after turning off. This delay will run simultaneously with
any delay built into the equipment.
ELEC
GAS
Select for Electric Auxiliary heat (with compressor)
Select for Gas Auxiliary heat (without compressor)
16 Fossil Fuel
Backup Heat
AUX HEAT
ELEC
[Only available if a 2 or 3 stage heat pump system was selected in setting 4] When set to electric, both the
compressor and auxiliary stage will run when a call for auxiliary heat is made. When set to gas, the compressor stage(s)
will be locked out one minute after a call for auxiliary heat. This setting can be overridden if setting an auxiliary heat
Continued on next page
9
Installer Manual
| General | Details |
|---|---|
| Name | Braeburn 8205-100-02 Universal Smart Wi-Fi Thermostat Instruction Manual |
| Make | Braeburn |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.32 MB |

Braeburn Programmable Touchscreen Thermostat User Manual

Braeburn TH-BR22 Programmable Thermostat Instructions

Braeburn 8205 Universal Smart Wi-Fi Thermostat User Guide

Braeburn 2030 Economy Model Thermostat User Manual

Braeburn 2030 Programmable Thermostat Instruction Manual