Relative Humidity Operation  
Relative Humidity Sensor  
The thermostat includes an internal relative humidity (RH) sensor and has the option to connect to an  
external RH sensor. The installer has the option to disable the internal RH sensor when an external  
RH sensor is installed. When both the internal and external RH sensors are enabled, the RH reading  
is averaged.  
Humidifier Operation  
The thermostat controls the relative humidity (RH) by operating either the Accessory 1 or Accessory 2  
relays. This is an installer configurable setting. When the RH is below the Humidify To setting by 3%,  
the Accessory 1 or 2 relay is closed to operate a humidifier. The humidifier is shut off when the RH  
reaches the Humidify To setting.  
The thermostat can operate 3 types of humidifiers:  
Stand Alone  
- The humidifier is not connected to the HVAC system.  
- The thermostat Mode can be set to Heat, Cool, Auto or Off.  
Steam  
- The steam humidifier is ducted to the HVAC system.  
- The thermostat Mode can be set to Heat, Cool, Auto or Off.  
- Requires the system fan to turn on when operating.  
Evaporative  
- A drum style humidifier which requires the heating system to operate  
to evaporate the water.  
- This system requires the system fan to operate.  
- The thermostat Mode must be set to Heat or Auto.  
Humidifier Window Protection  
During cold weather, condensation will form on windows when the relative humidity (RH) is too high.  
The optional window protection feature automatically calculates the indoor dew point based upon  
the outdoor temperature and the quality of the windows installed. The humidifier is then operated to  
the highest possible RH that is below the Humidify To setting. This feature requires that the outdoor  
temperature be available (via sensor or internet).  
Dehumidifier Operation  
The thermostat controls the relative humidity (RH) by operating either the Accessory 1 or Accessory 2  
relay. This is an installer configurable setting. When the RH is above the Dehumidify To setting by 3%,  
the Accessory 1 or 2 relay is closed to operate the dehumidifier. The dehumidifier is shut off when the  
RH reaches the Dehumidify To setting.  
T
h
e
t
h
e
r
m
o
s
t
a
t
c
a
n
o
p
e
r
a
t
e
2
t
y
p
e
s
o
f
d
e
h
u
m
i
d
i
f
i
e
r
s
:
Stand Alone  
- The dehumidifier is not connected to the HVAC system.  
- The thermostat Mode can be set to Heat, Cool, Auto or Off.  
DX Coil  
- The HVAC cooling system is used for dehumidification.  
- The Accessory 1 or Accessory 2 relay activates the DHUM operation on the air  
handling unit to operate the system fan at low speed.  
- The cooling compressor Y1 and Y2 relays are operated. The chilled DX coil  
condenses moisture from the air.  
- The cooling system can over cool the room temperature by 2°F (1°C) during  
dehumidification.  
30  
GeneralDetails
NameWATTS IOM-T-564 tekmar Invita WiFi Thermostat Instruction Manual
MakeWATTS
LanguageEnglish
FiletypePDF (Download)
File size0.66 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
WATTS IOM-T-563 Tekmar WiFi Thermostat Installation Guide
WATTS IOM-T-563 Tekmar WiFi Thermostat Installation Guide
WATTS BT-A03 RF Electronic Room Thermostat Installation Guide
WATTS BT-A03 RF Electronic Room Thermostat Installation Guide
WATTS TEK564 Invita WiFi Thermostat Instruction Manual
WATTS TEK564 Invita WiFi Thermostat Instruction Manual
WATTS WTC-ES Contact Thermostat User Manual
WATTS WTC-ES Contact Thermostat User Manual
WATTS 563 WiFi Thermostat User Manual
WATTS 563 WiFi Thermostat User Manual
WATTS W561 WiFi Thermostat Instruction Manual
WATTS W561 WiFi Thermostat Instruction Manual
WATTS Tekmar Wi-Fi Thermostat Instruction Manual
WATTS Tekmar Wi-Fi Thermostat Instruction Manual

WATTS IOM-T-564 tekmar Invita WiFi Thermostat Instruction Manual