SIEMENS RDG400 Room Thermostat Instruction Manual

Temporary timer for extended presence or absence  
The Comfort and Energy Saving modes can be temporarily extended by 0.5 to 9.5 hours using the  
temporary timer.  
1. To set the temporary timer, press and hold the operating mode button for maximum 3 seconds.  
While holding the button, turn the rotary knob clockwise or counterclockwise as required.  
a) Turn the rotary knob clockwise to extend Comfort mode.  
Display:  
b) Turn the rotary knob counterclockwise to extend Energy Saving mode.  
Display: 0....-9:30  
2. Release the operating mode button and the mode is temporarily changed, indicated by  
0....+9:30  
.
After the temporary timer has elapsed, the thermostat will resume in the new operating mode as follows:  
Extended Comfort mode  
New operating mode = Energy Saving  
Extended Energy Saving mode  
New operating mode = Comfort  
If Energy Saving mode cannot be selected via the operating mode button (P02≠2), Protection mode  
will be used for extended absence instead!  
The temporary timer function is aborted whenever a new setting is made  
Note:  
Extended Comfort mode is also possible when an external contact such as a keycard switch or central time clock is active.  
To enable this function, the time for the extended period must be set via parameter P68.  
Changing from heating to cooling mode  
Depending on the type of plant, the changeover from heating to cooling  
(or vice versa) is made either automatically by a changeover sensor or a  
remote changeover switch, or manually by pressing the operating mode  
button (see parameter P01)  
To select cooling or heating manually (P01=2), press the operating mode  
button until the desired mode appears  
With automatic changeover or continuous heating / cooling, symbols  
/
indicate that the system currently operates in heating or cooling mode  
With manual changeover, symbol appears, indicating that the system  
currently operates in heating or cooling mode  
Control parameters  
To change control parameters, proceed as follows:  
1. Press both buttons simultaneously for at least 3 seconds.  
2. Release them and, within 2 seconds, press and hold the right button again for 3 seconds. The display  
shows P01.  
3. Select the required parameter by turning the rotary knob.  
4. Press button  
(OK). The current value of the selected parameter starts blinking and can be changed  
by turning the rotary knob.  
5. Press button  
(OK) to confirm the adjusted value, or (Esc) to cancel the change.  
6. If you wish to adjust additional parameters, repeat steps 3 through 5, or press (Esc) to leave the  
parameter setting mode.  
Parameter list  
No.  
P01  
Parameter name  
Control sequence  
Default value  
Single-duct /  
single-duct & H/C  
coil:  
1 = cooling only  
1
Setting range  
0 = heating only  
1 = cooling only  
2 = H/C changeover, manually  
3 = H/C changeover, auto  
1 = Comfort / Protection  
mode  
Adj.  
P02  
Mode selection via  
operating mode button  
2 = Comfort / Energy Saving /  
Protection mode  
0 = °C  
1 = °F  
– 3...3 K  
(– 6...6 °F)  
0 = Room temperature  
1 = Setpoint  
0 = --- (no display)  
1 = ˚C and ˚F  
5...40 °C  
(41…104 °F)  
5...40 °C  
(41…104 °F)  
5...40 °C  
(41…104 °F)  
OFF, 5 °C…WcoolE-saving  
(OFF, 41 °F…WcoolEconomy)  
P04  
P05  
P06  
P07  
P08  
P09  
P10  
P11  
Selection of °C or °F  
Sensor calibration  
Depends on  
wizard setting  
0.0 K  
(0.0 °F)  
0
Standard temperature  
display  
Additional display  
information  
0
Comfort basic setpoint  
21 °C  
(70 °F)  
5 °C  
(41 °F)  
35 °C  
(95 °F)  
15 °C  
(59 °F)  
Minimum setpoint  
limitation in Comfort mode  
Maximum setpoint  
limitation in Comfort mode  
Setpoint for heating in  
Energy Saving mode  
(WheatE-saving)  
P12  
P14  
Setpoint for cooling in  
Energy Saving mode  
(WcoolE-saving)  
30 °C  
(86 °F)  
OFF, WheatE-saving…40 °C  
(OFF, WheatEconomy…104 °F)  
Button lock  
0
0 = disabled  
1 = automatically  
2 = manually  
The control parameters displayed depend on the DIP switch settings made  
Siemens Switzerland Ltd.  
Subject to change  
B3182en  
2014-10-20  
GeneralDetails
NameSIEMENS RDG400 Room Thermostat Instruction Manual
MakeSIEMENS
LanguageEnglish
FiletypePDF (Download)
File size0.18 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual
SIEMENS RDF660MB Flush Mount Room Thermostat Instruction Manual
SIEMENS RDF660MB Flush Mount Room Thermostat Instruction Manual

SIEMENS RDG400 Room Thermostat Instruction Manual