PROSELECT PSTSN11AWH Non Programmable Thermostat Installation Guide
Installer setup (ISU) (continued)
ISU Setup Number and Description
Options (factory default in bold)
50 °F to 99 °F (50 °F)
10.0 °C to 37.0 °C (10.0 °C)
430 = Minimum Cool Setpoint
Note: The cool temperature cannot be set below this
level.
32 °F to 90 °F (90 °F)
0 °C to 32.0 °C (32 °C)
431 = Maximum Heat Setpoint
Note: The heat temperature cannot be set above this
level.
0 = On Demand
1 = Continuous
1400 = Backlighting
Note: Common wire needed for continuous.
1 - 5
1401 = Backlight Brightness
Note: Only displayed if continuous backlight
selected.
-3 °F to 3 °F (0 °F)
-1.5 °C to 1.5 °C (0 °C)
Note: 0 °F = No difference in displayed temperature
and the actual room temperature. The thermostat
can display up to 3 °F (1.5 °C) lower or higher than
the actual measured temperature.
1420 = Temperature Display Offset
NOTE: Once you have cycled through all of the System Setup numbers, press
Done to save and exit to the home screen.
Setup Complete
You have now finished installing and setting up your thermostat.
Specifications
Temperature Setpoint Ranges
Operating Relative Humidity
Heat: 32 °F to 90 °F (0 °C to 32.0 °C)
Cool: 50 °F to 99 °F (10.0 °C to 37.0 °C)
5% to 90% (non-condensing)
Physical Dimensions in inches (mm)
(H x W x D)
3.86” H x 5.19” W x 1.08” D
98.24 mm H x 132 mm W x 27.5 mm D
Operating Ambient Temperature
32 °F to 102 °F (0 °C to 38.9 °C)
Shipping Temperature
-20 °F to 120 °F (-28.9 °C to 48.9 °C)
Electrical Ratings
Terminal
Voltage (50/60Hz)
20-30Vac
Running Current
0.02-1.0 A
W Heating
W2 (Aux) Heating (PSTSN21AWH only)
E Emergency Heat (PSTSN21AWH only)
Y Compressor Stage 1
G Fan
20-30Vac
0.02-1.0 A
20-30Vac
0.02-0.5 A
20-30Vac
0.02-1.0 A
20-30Vac
0.02-0.5 A
O/B Changeover
20-30Vac
0.02-0.5 A
9