GREYSTONE TLDF Series Flexible Cable Duct Average Low Limit Thermostat Instruction Manual

WIRING  
Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent electrical shock or equipment damage.  
Use 14-22 AWG shielded wiring for all connections and do not locate the device wires in the same conduit with wiring used to supply inductive loads such as  
motors. Make all connections in accordance with national and local codes.  
The temperature thermostat comes with the temperature sensor pre-wired to the PCB. If removal is required for installation then it may be re-wired as shown  
in Figure 7.  
Pull at least six inches of control wire into the enclosure, then complete the wiring connection according to the wire diagram for the applicable power supply  
as shown in Figure 8.  
Connect the DC positive or the AC voltage hot side to the PWR terminal. The supply common is connected to the COM terminal. See Figure 8.  
The relay has both Normally Open (NO) and Normally Closed (NC) contacts available. The relay output is available on the NO/COM/NC terminal. Make  
connections before applying power as shown in Figure 9.  
The setpoint differential has 3 jumper selectable settings (Low/Mid/High). Set jumper to desired differential as shown in Figure 11.  
To set the switching setpoint, turn the setpoint potentiometer to the desired temperature setting as shown in Figure 10.  
Once all connections settings are made and checked, power can be applied.  
Figure 11  
Setpoint Differential Setting  
Figure 7  
DIFFERENTIAL  
HIGH  
MID  
LOW  
Temperature sensor wiring to PCB  
(Factory Wiring)  
DIFFERENTIAL  
HIGH = 5.6°C/10°F  
MID = 2.8°C/5°F  
LOW = 1.1°C/2°F  
No Polarity  
HIGH  
MID  
LOW  
NO COM NC  
TEMP COM PWR  
Figure 9  
Relay Output Wiring  
Figure 8  
Power Supply Wiring  
+24 Vdc  
DI  
Digital  
INPUT  
NO  
COM  
NC  
COM  
PWR  
COMMON  
+24 Vdc  
Temperature  
Sensor  
Controller  
24 Vdc Power Supply  
+24 Vdc  
NO  
COM  
NC  
Figure 10  
COMMON  
Setpoint Adjustment  
24 Vdc Power Supply  
3C/38F  
1C/33F  
-2C/29F  
-4C/25F  
5C/42F  
8C/46F  
10C/50F  
COMMON  
24 Vac  
COM  
PWR  
COMMON  
DI  
24 Vac Transformer  
Controller  
SETPOINT  
SPECIFICATIONS:  
Power Supply:.........................................12 to 28 Vac/dc  
Consumption:.........................................50 mA max  
DIMENSIONS  
Relay Contacts:.......................................SPDT, Form C contacts (N.O. and N.C.)  
5 Amps @ 30 Vac/250 Vac resistive  
1.5 Amps @ 30 Vdc/250 Vac inductive  
Relay Action:............................................Activates on temperature fall  
Setpoint Operation:.............................Single-turn knob-pot on PCB  
Adjustable Setpoint:............................-4 to 10°C (25 to 50°F)  
Setpoint Temperature:........................Low/Mid/High jumper selectable  
Differential 1.1, 2.8, 5.6°C (2, 5, 10°F)  
112.5 mm  
4.43"  
99.7 mm  
3.93"  
53.7 mm  
2.11"  
Temperature Sensor:...........................10K ohm curve matched precision thermistor  
Sensor Accuracy:................................... 0.2°C, 0 to 70°C ( 0.36°F, 32 to 158°F)  
Probe Sensing Range:.........................-20 to 60°C (-4 to 140°F)  
Probe Material:.......................................304 Series Stainless Steel  
Probe Diameter:.....................................6 mm (0.236")  
Various Probe Lengths  
See Specifications  
116.5 mm  
4.58"  
Probe Length: .........................................1800mm, 3600mm, 6100mm, 7300mm  
(6', 12', 20', 24')  
Wire Material:..........................................FT-6 Plenum-rated cable  
304 Series S/S Probe  
FT-6 Plenum Rated Cable  
Foam Gasket  
Operating Conditions:........................-10 to 50°C (14 to 122°F), 5 to 95% RH, non-condensing  
Storage Conditions:.............................-30 to 70°C (-22 to 158°F), 5 to 95% RH, non-condensing  
Wiring Connections:............................Screw terminal block (14 to 22 AWG)  
Enclosure:..................................................Grey Polycarbonate UL94-V0, IP65 (NEMA 4X)  
Optional thread adapter (1/2" NPT to M16)  
0.5" NPT  
and cable gland fitting  
Country of Origin:.................................Canada  
Page 2  
IN-GE-TLDFXXX-003  
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com  
GeneralDetails
NameGREYSTONE TLDF Series Flexible Cable Duct Average Low Limit Thermostat Instruction Manual
MakeGreystone
LanguageEnglish
FiletypePDF (Download)
File size0.19 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
GREYSTONE TLGLF24X01 Glass Low Limit Thermostat Instruction Manual
GREYSTONE TLGLF24X01 Glass Low Limit Thermostat Instruction Manual
GREYSTONE TLOSF24X01 TLOS Series Outside Low Limit Thermostat Instruction Manual
GREYSTONE TLOSF24X01 TLOS Series Outside Low Limit Thermostat Instruction Manual
GREYSTONE TLDCB24J01 Flexible Copper Duct Average Low Limit Thermostat Instruction Manual
GREYSTONE TLDCB24J01 Flexible Copper Duct Average Low Limit Thermostat Instruction Manual
GREYSTONE TLFLF24X01 Flying Lead Low Limit Thermostat Instruction Manual
GREYSTONE TLFLF24X01 Flying Lead Low Limit Thermostat Instruction Manual

GREYSTONE TLDF Series Flexible Cable Duct Average Low Limit Thermostat Instruction Manual