Home > EPH CONTROLS > EPH Controls RF1A Programmable RF Thermostat Instruction Manual
EPH Controls RF1A Programmable RF Thermostat Instruction Manual
Page 1 of 1
Operating Instructions
RF1A - Wireless Receiver with TRFPi2
Contents
1. Specifications & wiring
2. Mounting
3. Installation
4. Button / LED description
5. Resetting the RF1A receiver
6. To connect the TRFPi2 thermostat to an
RF1A receiver
CAUTION!
Before commencing any work on the electrical
connections, you must first disconnect the device from
the mains. None of the 230V connections must be live
until the installation has been completed and the housing
is closed. Only qualified electricians or authorised service
staff are permitted to open the terminal box.
7. To disconnect the TRFPi2 thermostat from an
RF1A receiver
There are parts that carry mains voltage behind the cover.
The terminal box must not be left unsupervised when
open. (Prevent non specialists and especially children
from gaining access to it.)
Important: Keep this document
Ensure that this wireless enabled receiver is installed 1
metre from any metalic object, television, radio or wireless
internet transmitter.
Prior to operation, it is neccessary to complete all
required settings described in this section.
1. Specifications & wiring
4. Button / LED description (Continued)
Manual override: This button will manually override the system.
Power Supply: 230 Vac 50Hz
Contact Rating: 250 Vac 10(3)A
Ambient Temp: 0~50°C
Class II appliance
Pollution degree 2: Resistance to
voltage surge 2500V; as per EN 60730
Wireless connect indicator: This LED will flash on receiving wireless signals.
If it is constantly ON, the RF1A receiver has been disconnected from the
wireless thermostat.
Internal wiring diagram for RF1A
5. Resetting the RF1A receiver
RESET
Press the
button located on the side of the receiver. Within 2
3
2
1
L
L
N
N
seconds, press the ‘Connect’button. The RF1A receiver is now reset.
COM
ON
OFF
6. To connect the TRFPi2 thermostat to an RF1A
receiver
* If mains voltage output is required,
MAINS
SUPPLY
Please note, If you are installing a CombiPack2 the TRFPi2 thermostat and
the RF1A receiver will have a pre-established RF connection so it is not
necessary to carry out the RF connection process below.
terminals L & 2 must be electrically linked.
2. Mounting
On the RF1A receiver:
The RF1A receiver should be wall mounted in an area within 20 metres
distance of the wireless thermostat.
Press the
button. The red and green light will begin to flash.
Connect
It is important that the receiver is mounted more than 1 metre away from
metal objects as this will affect communication with the thermostat.
On the TRFPi2 thermostat:
Connect
Press the
button.
The receiver should also be installed at least 1metre from any electronic
devices such as radio, TV, microwave or wireless network adaptor.
The thermostat will begin to search through the RF channels.
Once an RF connection has been established the thermostat will show ‘r01’
The unit can be fitted to:
1. Recessed conduit boxes
2. Surface mounting boxes
on the LCD screen.
Press the ‘OK’button to finish the process.
The thermostat is now connected to the RF1A receiver.
‘RF Connect’appears on the screen.
3. Installation
Slacken the fastening screw on the bottom of the receiver with a philips
screwdriver.
7. To disconnect the TRFPi2 thermostat from an
The receiver is hinged and can be opened 180 degrees. Mount the unit as
described in section 2. Wire the unit as described in section 1. Close the
receiver and tighten the fastening screw.
RF1A receiver
On the TRFPi2 thermostat:
Connect
Press the
button.
4. Button / LED description
The thermostat will begin to search through the RF channels.
Press and hold the standby button for 10 seconds.
‘AdL’ & ‘AdH’will flash intermittently on the screen of the thermostat.
Press the ‘OK’button twice to complete the unpairing process.
The thermostat TRFPi2 is now disconnected from the receiver RF1A.
Note: RF Connect may remain on the screen for 1-2 minutes.
System ON
(Green LED)
Connect button
Manual override
Reset button
Wireless connect
indicator (Red LED)
On the RF1A receiver:
RESET
Press the
button and immediately press the
button.
Connect
The red and green lights will flash quickly followed by a solid red light.
The RF1A receiver is now disconnected from the TRFPi2 thermostat.
Wireless connect: Once voltage has been applied this button may be
pressed to initialise the pairing process with the wireless thermostat. Once
pressed the red and green LED will begin to flash.
EPH Controls Ireland
EPH Controls UK
20230123_RF1A-TRFPi2_OpIns_PK
General | Details |
---|---|
Name | EPH Controls RF1A Programmable RF Thermostat Instruction Manual |
Make | EPH CONTROLS |
Language | English |
Filetype | PDF (Download) |
File size | 0.11 MB |

EPH CONTROLS eTRV-HW Smart Cylinder Thermostat User Guide

EPH CONTROLS eTRV-HW Smart Hot Water Thermostat Instruction Manual

EPH CONTROLS eTRV Smart Radiator Thermostat Instruction Manual

EPH CONTROLS 20221026 RFRA – RF Room Thermostat Instruction Manual

EPH CONTROLS CDTP2 Hardwired Room Thermostat Instruction Manual

EPH Controls CDT2-24 24V Room Thermostat Installation Guide

EPH CONTROLS RFCA RF Cylinder Thermostat Instruction Manual

EPH CONTROLS PR092K7 RF Cylinder Thermostat Instruction Manual

EPH CONTROLS COMBIPACK2 Smart Thermostat with Automation and Optimum Start Instructions

EPH CONTROLS RFRA RF Room Thermostat Installation Guide

EPH Controls RF1A Programmable RF Thermostat Instruction Manual Overview
Summary of Contents
- Page 1: Operating instructions for RF1A - Wireless Receiver with TRFPi2. Specifications & wiring include power supply, contact rating, and ambient temperature. Mounting instructions specify the RF1A receiver should be wall mounted within 20 meters of the wireless thermostat. Installation steps involve loosening a fastening screw and wiring the unit as described. Button/LED descriptions detail functions such as manual override and wireless connect indicators. Resetting the RF1A receiver requires pressing specific buttons in sequence. Connecting the TRFPi2 thermostat to the RF1A receiver involves pressing the connect button and ensuring proper distance from metal objects. Disconnecting the TRFPi2 thermostat from the RF1A receiver includes pressing and holding the standby button. Important safety cautions include disconnecting the device from mains before electrical work and ensuring the terminal box is not left unsupervised when open. The document emphasizes keeping it accessible for reference during installation and operation.