Home > Danfoss > Danfoss FH-RT Wireless Room Thermostat Installation Guide

Danfoss FH-RT Wireless Room Thermostat Installation Guide

If no signal is received from one or more thermostats, the corresponding  
LEDs on the indicator panel remain lit.  
If after a further 8 hours the base unit has still not received a signal from the  
thermostat, an acoustic alarm begins buzzing.The buzzer can be de-activated  
by selecting the alarm “OFF” setting on the base unit (see Fig. 9). The alarm  
is reset when a button on the control panel is pressed or when the base unit  
receives a signal from the thermostat.  
When the required number of thermostats have been checked, press and  
hold “MODEfor 3 seconds to return the system to normal mode.  
Note: The system returns automatically to normal mode if no buttons are  
pressed during a 15-minute period.  
5.6 Thermal actuator & pump exercise  
This function prevents the manifold valve and circulating pump from  
sticking.  
5.3 Thermostat test mode  
This mode is used to test thermostat transmission.  
Using the point of a pencil or similar, press and hold the transmission button  
on the front of the thermostat for 3 seconds.  
This forces the thermostat to transmit a signal every 7 seconds for 5-6  
minutes.  
It is activated once yearly. First, all assigned outputs are activated for 5  
minutes, and the pump output is then activated for 5 minutes (only if pump  
output is installed).  
The function can be turned off by switching the EXERCISE switch to the OFF  
position. (See Fig. 10).  
Then check whether a signal from the thermostat is received by the base  
unit at 7 second intervals (the LED indicator for the assigned channel flashes  
on receiving a signal).  
5.7 NO/NC thermal actuator settings  
This function allows“Normally Closed’(N/C) or“Normally Open”(N/O) thermal  
actuators to be used.  
The test can be terminated by again pressing the thermostat transmission  
Type is selected on the ACTUATOR switch (see Fig. 10).  
button.  
Note: The system returns automatically to normal mode if no buttons are  
5.8 “Cooling” mode  
pressed during a 5-minute period.  
This mode allows thermostat signals to be invertedso that outputs are opened  
when the temperature is above the desired temperature and closed when  
below and is intended for use in cooling systems.  
5.4 Thermal actuator output testing  
Thermal actuator output testing is used to check the functioning of the base  
unit output relays.  
6.0 Boiler and pump interlock setting  
Press and hold the “MODEbutton for 3 seconds (all LED indicators flash).  
As standard, outputs 7 and 8 are set to control thermal actuators.  
However, output 7 can also be used to control a boiler via an ON/OFF signal,  
and output 8 can be used to control a pump.  
The first indicator then begins flashing.  
Press “OK” to test the first channel. The LED indicator now flashes rapidly  
(on/off at half-second intervals) and a small click can be heard after about 5  
seconds indicating that the output has been activated. Press “OK” again to  
de-activate the output.  
To enable a boiler or pump to be controlled, the system must be configured  
as shown in Figs 8 and 9 respectively.  
Note: If outputs 7 and 8 are not used for thermal actuators, the following  
applies:  
PressMODEto select the next output to be tested, and repeat the process  
described above.  
- LED indicators 7 and 8 light up when any other channel requires heat.  
The test can be terminated by pressing and holding the “MODE” button for  
3 seconds.  
Note: The system returns automatically to normal mode if no buttons are  
pressed during a 10-minute period.  
5.5 Alarm function  
This function is initiated automatically in case of communication failure.  
If the base unit does not receive a signal from a registered thermostat for 2  
hours, the corresponding LED indicator starts flashing. Simultaneously, the  
thermal actuator output begins a continuous cycle of 7 minutes’ activation  
and 14 minutesde-activation.  
Fig. 7. Switches  
Fig. 9. Step 2. Bend left-hand jumper as illustrated.  
5
GeneralDetails
NameDanfoss FH-RT Wireless Room Thermostat Installation Guide
MakeDanfoss
LanguageEnglish
FiletypePDF (Download)
File size0.32 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide
Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide
Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide
Danfoss UT 72-UT 73 Universal Thermostat Installation Guide
Danfoss UT 72-UT 73 Universal Thermostat Installation Guide
Danfoss ECtemp 530 Electronic Thermostat Installation Guide
Danfoss ECtemp 530 Electronic Thermostat Installation Guide
Danfoss 014G0251 Eco Radiator Thermostat User Guide
Danfoss 014G0251 Eco Radiator Thermostat User Guide
Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide
Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide
Danfoss RET230P Electronic Thermostat Instruction Manual
Danfoss RET230P Electronic Thermostat Instruction Manual
Danfoss CET B-RF Wireless Electronic Hot Water Cylinder Thermostat Installation Guide
Danfoss CET B-RF Wireless Electronic Hot Water Cylinder Thermostat Installation Guide
Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide
Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide

Danfoss FH-RT Wireless Room Thermostat Installation Guide