When radiant floor heating is installed, it is always the first stage of heating, followed by  
the heat pump, and lastly any backup heating. This allows the floor to remain warm in the  
heating season.  
Equipment Setting  
1HP  
1HP/  
1Aux  
1HP/  
2Aux  
2HP  
2HP/  
1Aux  
2HP/  
2Aux  
First stage heating  
Second stage heating  
Third stage heating  
Fourth stage heating  
First stage cooling  
Second stage cooling  
Fan  
Y1  
-
W1  
Y1  
-
W1  
Y1  
W2  
-
Y1  
Y2  
-
W1  
Y1  
Y2  
-
W1  
Y1  
Y2  
W2  
Y1  
Y2  
-
-
-
-
Y1  
-
Y1  
-
Y1  
-
Y1  
Y2  
Y1  
Y2  
G
Accessory 1  
Choice of: Humidifier, Dehumidifier, HRV/ERV ventilator  
Accessory 2  
Reversing valve O or B.  
O relay remains closed during heating operation.  
B relay remains closed during cooling operation.  
Emergency Heat  
For systems with heat pumps, the thermostat includes an Emergency Heat mode. This mode  
shuts off the heat pump Y1 and Y2 relays and operates the auxiliary heat, which is usually  
more expensive. Select Emergency Heat if the heat pump will not operate due to refrigerant  
pressure lockout condition.  
Heating Differentials  
The first stage heat turns on when the air temperature falls 1.5°F (1°C) below the Heat To  
setting and shuts off when the air temperature reaches the Heat To setting.  
The second, third and fourth stage heat each have an adjustable differential and time delay  
setting to determine when the stage turns on, and shut off when they reach 1.5, 1.0, and  
0.5°F (0.75, 0.5, and 0.25°C) of the Heat To setting respectively.  
Radiant Floor Heating  
Radiant floor heating is operated differently than other heating types due to the large time  
delays to heat and cool the slab. When Radiant Floor Heating is selected in the setup  
menu, the W1 relay operates using Pulse Width Modulation. This improves comfort for  
radiant systems with high mass floors.  
• 100% on time at Heat To setting -1.5  
°F  
• 50% on time at Heat To setting  
• 0% on time at Heat To setting + 1.5  
°F  
Room Sensor and Averaging  
The thermostat can measure room temperature between -46 to 212°F (-43 to 100°C). The room  
temperature can be measured using a combination of the built-in and auxiliary sensors.  
• Built-in room sensor only  
• Built-in room sensor with auxiliary room sensor(s) (temperature is averaged)  
• Auxiliary room sensor only  
11  
GeneralDetails
NameWATTS IOM-T-563 Tekmar WiFi Thermostat Installation Guide
MakeWATTS
LanguageEnglish
FiletypePDF (Download)
File size0.63 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
WATTS IOM-T-564 tekmar Invita WiFi Thermostat Instruction Manual
WATTS IOM-T-564 tekmar Invita WiFi Thermostat Instruction Manual
WATTS BT-A03 RF Electronic Room Thermostat Installation Guide
WATTS BT-A03 RF Electronic Room Thermostat Installation Guide
WATTS TEK564 Invita WiFi Thermostat Instruction Manual
WATTS TEK564 Invita WiFi Thermostat Instruction Manual
WATTS WTC-ES Contact Thermostat User Manual
WATTS WTC-ES Contact Thermostat User Manual
WATTS 563 WiFi Thermostat User Manual
WATTS 563 WiFi Thermostat User Manual
WATTS W561 WiFi Thermostat Instruction Manual
WATTS W561 WiFi Thermostat Instruction Manual
WATTS Tekmar Wi-Fi Thermostat Instruction Manual
WATTS Tekmar Wi-Fi Thermostat Instruction Manual

WATTS IOM-T-563 Tekmar WiFi Thermostat Installation Guide