Home > WATTS > WATTS IOM-T-563 Tekmar WiFi Thermostat Installation Guide

WATTS IOM-T-563 Tekmar WiFi Thermostat Installation Guide

Sequence of Operation  
Heating Operation  
• The heating setpoint can be set from 40 to 95°F (4.5 to 35°C).  
• The Heat On symbol is shown on the display when the thermostat is heating.  
• Heating for freeze protection is provided whenever the air or floor temperature falls below 40  
(4.5°C), regardless of operating mode.  
°F  
• The cooling setpoint can be set from 45 to 100°F (7.0 to 38.0°C).  
• The Cool On symbol is shown on the display when the thermostat is cooling.  
The thermostat supports two heating system types: 1) conventional, or 2) heat pump.  
Conventional Systems  
A conventional heating system includes: furnaces, air conditioners, hydronic heating  
systems with baseboards, radiant floors, or fan coils and electric heating.  
The thermostat supports up to two heating stages, two cooling stages, a fan and two  
accessory relays.  
Equipment Setting  
First stage heating  
Second stage heating  
First stage cooling  
Second stage cooling  
Fan  
1H/1C  
1H/2C  
W1  
-
2H/1C  
W1  
W2  
Y1  
2H/2C  
W1  
W2  
Y1  
W1  
-
Y1  
-
Y1  
Y2  
-
Y2  
G
Accessory 1  
Choice of: Humidifier, Dehumidifier, HRV/ERV  
Choice of: Humidifier, Dehumidifier  
Accessory 2  
Heat Pump Systems  
A heat pump system may include additional heat sources as backup. The thermostat  
supports up to four heating stages, two cooling stages, a reversing valve, a fan and one  
accessory relay.  
Equipment Setting  
1HP  
1HP/  
1Aux  
1HP/  
2Aux  
2HP  
2HP/  
1Aux  
2HP/  
2Aux  
First stage heating  
Second stage heating  
Third stage heating  
Fourth stage heating  
First stage cooling  
Second stage cooling  
Fan  
Y1  
-
Y1  
W1  
-
Y1  
W1  
W2  
-
Y1  
Y2  
-
Y1  
Y2  
W1  
-
Y1  
Y2  
W1  
W2  
Y1  
-
-
-
-
Y1  
-
Y1  
-
Y1  
-
Y1  
Y2  
Y1  
Y2  
Y2  
G
Accessory 1  
Choice of: Humidifier, Dehumidifier, HRV/ERV ventilator  
Accessory 2  
Reversing valve O relay remains closed during cooling.  
Reversing valve B relay remains closed during heating.  
10  
GeneralDetails
NameWATTS IOM-T-563 Tekmar WiFi Thermostat Installation Guide
MakeWATTS
LanguageEnglish
FiletypePDF (Download)
File size0.63 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
WATTS IOM-T-564 tekmar Invita WiFi Thermostat Instruction Manual
WATTS IOM-T-564 tekmar Invita WiFi Thermostat Instruction Manual
WATTS BT-A03 RF Electronic Room Thermostat Installation Guide
WATTS BT-A03 RF Electronic Room Thermostat Installation Guide
WATTS TEK564 Invita WiFi Thermostat Instruction Manual
WATTS TEK564 Invita WiFi Thermostat Instruction Manual
WATTS WTC-ES Contact Thermostat User Manual
WATTS WTC-ES Contact Thermostat User Manual
WATTS 563 WiFi Thermostat User Manual
WATTS 563 WiFi Thermostat User Manual
WATTS W561 WiFi Thermostat Instruction Manual
WATTS W561 WiFi Thermostat Instruction Manual
WATTS Tekmar Wi-Fi Thermostat Instruction Manual
WATTS Tekmar Wi-Fi Thermostat Instruction Manual

WATTS IOM-T-563 Tekmar WiFi Thermostat Installation Guide