Home > Trane > TRANE XR102 Non-Programmable Thermostat User Guide

TRANE XR102 Non-Programmable Thermostat User Guide

Installation and User Guide  
Trane XR102 Non-Programmable Thermostat  
6. TROUBLESHOOTING  
Reset Operation  
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation you can reset the thermostat by  
pressing and at the same tie while moving the SYSTEM switch from OFF to HEAT. This also resets the factory defaults.  
If the thermostat has power, has been reset and still does not function correctly contact your heating/cooling service person or place of  
purchase.  
Batteries  
For best results, replace batteries once a year with new premium brand alkaline battery.  
SYMPTOM  
POSSIBLE CAUSE  
CORRECTIVE ACTION  
No Heat/  
No Cool/  
No Fan  
(common problem)  
1.) Blown fuse or tripped circuit breaker  
2.) Furnace power switch to OFF  
3.) Furnace blower compartment door panel  
loose or not properly installed  
1.) Replace fuse or reset breaker  
2.) Turn switch to ON  
3.) Replace door panel in proper position to engage safety interlock or door switch  
1.) Set System Switch to Cool and lower setpoint below room temperature.  
2.) Verify thermostat and system wires are securely attached.  
3.) Same procedures as diagnostic for “No Heat” condition except set the thermostat to Cool  
and lower the setpoint below the room temperature. There may be up to a five minute delay  
before the thermostat clicks in Cooling.  
1.) System Switch not set to Cool  
2.) Loose connection to thermostat or system  
3.) Cooling System requires service or  
thermostat requires replacement  
No Cool  
1.) Re-light pilot.  
2.) Set System Switch to Heat and raise the setpoint above room temperature.  
3:) Verify thermostat and system wires are securely attached.  
4.) Many surfaces have safety devices that shutdown when a lock-out condition occurs. If  
the heat works intermittently contact the furnace manufacturer or local service person for  
assistance.  
5:) Diagnostic: Set SYSTEM Switch to HEAT and raise the setpoint above room temperature.  
Within a few seconds the thermostat should make a soft click sound. This sound usually  
indicates the thermostat is operating properly. If the thermostat does not click, try the reset  
operation listed below. If the thermostat does not click after being reset contact your heating and  
cooling service person or place of purchase for a replacement. If the thermostat clicks, contact  
the furnace manufacturer or a service person to verify the heating is operating correctly.  
1.) Pilot light not lit  
2.) System Switch not set to Heat  
3.) Loose connection to thermostat or system  
4.) Furnace Lock-Out Condition. Heat may  
also be intermittent.  
5.) Heating System requires service or  
thermostat requires replacement  
No Heat  
Check each wire connection to verify they are not shorted or touching together. No bare wire  
should stick out from under terminal screws. Try resetting the thermostat as described above.  
If the condition persists the manufacturer of your system or service person can instruct you on  
how to test the Heat/Cool system for correct operation. If the system operates correctly, replace  
the thermostat.  
1.) Possible short in wiring.  
2.) Possible short in thermostat.  
3.) Possible short in heat/cool/fan system.  
4.) FAN Switch set to Fan ON.  
Heat, Cool or Fan Runs  
Constantly  
Digital thermostats normally provide precise temperature control and may cycle faster than  
some older mechanical models. A faster cycle rate means the unit turns on and off more  
frequently but runs for a shorter time so there is no increase in energy use. If you would like to  
increase the cycle time, clip Jumper W-905 as for Hydronic Heating Systems. It is not possible  
to shorten the cycle time. If an acceptable cycle rate is not achieved as received or by clipping  
W-905 contact a local service person for additional suggestions.  
Furnace Cycles Too  
Fast or Too Slow  
(narrow or wide  
1.) The location of the thermostat and/or the  
size of the Heating System may be influencing  
the cycle rate.  
temperature swing)  
Thermostat Display &  
Thermometer Disagree  
Cooling Cycles Too  
Fast or Too Slow  
(narrow or wide  
temperature swing)  
1. The location of the thermostat and the size  
of the Cooling System can influence the  
cycle rate.  
The cycle rate for cooling is fixed and can not be adjusted. Contact a local service person for  
suggestions.  
Thermostat Setting and  
Thermostat  
Thermometer Disagree  
1. Thermostat thermometer setting requires  
adjustment.  
The thermometer can be adjusted +/- 3 degrees. See Temperature Display Adjustment in the  
Operation section.  
Blank Display and/  
or Keypad Not  
Responding  
1. Voltage spike or static discharge.  
2. Battery change required.  
Replace batteries and check heat/cool system for proper operation. If a voltage spike occurs use  
the Reset Operation listed above.  
Pub. No. 18HD54D1-1B-EN 09/2020 Part No. 37-7770002  
11  
GeneralDetails
NameTRANE XR102 Non-Programmable Thermostat User Guide
MakeTrane
LanguageEnglish
FiletypePDF (Download)
File size0.3 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
TRANE BAYECON089A Programmable Touch Screen Thermostat Instruction Manual
TRANE BAYECON089A Programmable Touch Screen Thermostat Instruction Manual
TRANE XR103 Non-Programmable Heat Pump Thermostat User Guide
TRANE XR103 Non-Programmable Heat Pump Thermostat User Guide
TRANE XR202 Programmable Thermostat User Guide
TRANE XR202 Programmable Thermostat User Guide
TRANE SC360 Link System Controller and Smart Thermostat Instructions
TRANE SC360 Link System Controller and Smart Thermostat Instructions

TRANE XR102 Non-Programmable Thermostat User Guide