Home > telkonet > telkonet Aida Wireless Thermostat User Guide

telkonet Aida Wireless Thermostat User Guide

Aida IOM  
INSTALLATION - HIGH VOLTAGE (NON-CLASS 2)  
CAUTION!  
l
High voltage installation should only be performed by a qualified heating & air  
conditioning contractor or licensed electrician.  
l
Failure to understand and follow all instructions carefully before installing or  
operating this device could cause personal injury and/or property damage.  
l
All wiring must conform to local and national electrical ordinances and codes.  
l
Prevent electrical shock, personal injury, and equipment damage: prior to install-  
ation or service, disconnect system’s electric power at main fuse or circuit  
breaker box.  
1. Ensure the JBox (not provided by Telkonet) has been installed with a vertical  
single gang mud ring.  
2. Turn off power at the Aida or mounting location using a disconnect switch or  
breaker lockout/tag out on appropriate breaker panel.  
3. Test that power is off by using a voltmeter.  
4. Strip the LINE wire back 0.25 inches.  
5. Cap the LINE wire with a wire nut or electrical tape.  
6. Cut the COMMON wire so the copper is flush with the insulation.  
7. Strip all wires except for COMMON back 0.25 inches.  
8. Remove the safety screw from the top of the thermostat using the Phillips head  
screwdriver  
9. Separate the backplate from the thermostat: use a flathead screwdriver to  
GENTLY press the tab next to the screw hole to allow the thermostat to pop  
open. WARNING: Using too much force can break the tab.  
10. Place thermostat backplate against the JBox adapter plate. The adapter plate  
and backplate holes should align if both are correctly oriented.  
11. Connect wires and harnesses as per the pinout tables in the Tables section.  
12. Mount the Aida backplate on top of the JBox adapter plate, using four #5 ½”  
coarse thread screws (or other appropriate mounting screws).  
13. Feed wire harnesses through the applicable holes in the backplate.  
14. Connect the harnesses to the Aida.  
REMINDER: Wiring to the screw terminal block must exit the enclosure at Opening A  
of the backplate. Wiring to all other connectors must exit the enclosure at Opening B  
of the backplate.  
Class 2 and Non-Class 2 wiring must not be mixed within a junction box or conduit  
run.  
Chapter 2: Installation  