Home > telkonet > telkonet Aida Wireless Thermostat User Guide

telkonet Aida Wireless Thermostat User Guide

Aida IOM  
Mounting Con-  
Best Practices  
If the occupants will likely  
siderations  
position within 0-9 feet of  
their expected location.  
be stationary (e.g., sleeping  
in bed)…  
If the occupants will move  
occasionally (e.g., working position within 18 feet of  
at a desk)…  
their expected location.  
If the occupants will move  
regularly (e.g., walking  
down a hall) …  
position within 25 feet of  
their expected location.  
Distance to Occupant  
The thermostat has a 140° wide horizontal viewing  
angle.  
If no door contacts or remote occupancy sensors are  
used in a residence, then the thermostat should either  
be located with 9 feet of the bed with an unobstructed  
view or have delays adjusted with "night locking" to pre-  
vent setback during the evening hours.  
PLACEMENT GUIDELINES  
Placement Guidelines  
Point toward main sleeping area if possible (max 9' from bed)...  
...otherwise, point to center of room  
Mount ON wall, not IN wall  
Vents in backplate require proper air flow  
Standard height is 60" from finished floor; ADA height is above 15" and below 48"  
Mount on an interior wall if possible  