telkonet Aida Wireless Thermostat User Guide
Aida IOM
Mounting Con-
Best Practices
If the occupants will likely
siderations
position within 0-9 feet of
their expected location.
be stationary (e.g., sleeping
in bed)…
If the occupants will move
occasionally (e.g., working position within 18 feet of
at a desk)…
their expected location.
If the occupants will move
regularly (e.g., walking
down a hall) …
position within 25 feet of
their expected location.
Distance to Occupant
The thermostat has a 140° wide horizontal viewing
angle.
If no door contacts or remote occupancy sensors are
used in a residence, then the thermostat should either
be located with 9 feet of the bed with an unobstructed
view or have delays adjusted with "night locking" to pre-
vent setback during the evening hours.
PLACEMENT GUIDELINES
Placement Guidelines
Point toward main sleeping area if possible (max 9' from bed)...
...otherwise, point to center of room
Mount ON wall, not IN wall
Vents in backplate require proper air flow
Standard height is 60" from finished floor; ADA height is above 15" and below 48"
Mount on an interior wall if possible
Chapter 2: Installation