SIEMENS RDF660MB Flush Mount Room Thermostat Instruction Manual

Operating Instructions  
RDF660MB..  
Protection mode  
Comfort mode  
Economy mode **  
Condensation in the room *  
Cooling demand/mode  
Heating demand/mode  
Key lock  
The key symbol  
indicates buttons are locked.  
Electrical heater active  
Key lock can be configured via parameter P14.  
Measured room temperature,  
setpoints and parameters  
Reminder to clean filters and for external faults  
Automatic fan  
Low fan speed  
Medium fan speed  
High fan speed  
Current time of day or  
additional user  
information  
FIL *This message reminds user to clean HVAC equipment filters.  
Recalibrating the sensor  
Actual room  
temperature  
Outdoor temperature  
After installation for at least one hour, the displayed room temperature  
can be recalibrated via parameter P05.  
Commissioning  
Buttons are locked  
Fault indicator *  
User can adjust several different control parameters to adapt the  
thermostat to your system and optimize control performance. User  
can do this during operation either via the buttons on the thermostat  
or using a commissioning tool via Modbus.  
*
Needs to be configured by your HVAC installer  
** Needs to be enabled via parameter P02  
Change room temperature setpoint  
Press + or buttons to increase or decrease the current room temperature setpoint for Comfort  
mode. The thermostat changes to Comfort  
The setting range is 5...35 °C, unless limited by parameters P09 and P10.  
.
Baud rate and parity  
The Baud rate can be adjusted to 9600 bps, 19200 bps (factory  
setting), 38400 bps or 57600 bps. The Parity can be set to none, odd or  
even (factory setting). Your HVAC installer can set them through  
additional parameters.  
Adjust fan speed/fan mode  
Press the button to adjust the fan mode and fan speed.  
In Auto mode  
, the thermostat automatically selects the fan speed based on setpoint and actual  
room temperature.  
In manual mode, the fan always runs at the speed that user selects:  
Low fan speed  
Important: Once making any changes on the baud rate or parity,  
user must reset the power before the changes take effect.  
Medium fan speed  
High fan speed  
Control parameters  
Proceed as follows to change the most important control parameters  
Change thermostat operating mode  
1. Press the and + buttons simultaneously for more than 6  
seconds.  
Press operating mode button  
to change the operating mode display.  
Release, and within 2 seconds, press + again for more than 3  
seconds. "P01" is displayed.  
2. Repeatedly press the + or button to select the required  
parameter.  
In Comfort mode , the thermostat maintains the room temperature at the setpoint which can be  
readjusted using the + and buttons.  
In Economy mode , the room temperature is maintained at a lower or higher fixed setpoint (factory-  
set: 15 °C, 30 °C) to save energy. Adjust parameters P11 and P12 to change the preselected  
setpoints. The availability of Economy mode depends on parameter P02 or via an external signal  
(switch or Modbus command) such as keycard or presence detector.  
In Protection mode , the thermostat stops operating. However, it will operate if the room  
temperature is below 8 °C (heating application) against frost (P65) and the value is adjustable.  
In Protection mode, press any button to activate the screen, then press the mode button to change to  
another operating mode.  
3. Press + and – simultaneously once to enter EDIT mode. Then press  
+ or button to change the value of the selected parameter and  
press + and simultaneously to save the change.  
4. Repeat steps 2 to 3 to display and change additional parameters.  
5. Press + or – until “End” is displayed, and then press + and –  
simultaneously to exit parameter entry mode.  
Important: User can set Protection setpoints to OFF; the thermostat then is inactive, i.e. no  
protective heating or cooling function. Risk of frost!  
Change from heating to cooling mode  
Changeover between cooling and heating is either automatic using a heating/cooling changeover sensor or a remote changeover switch or via instruction from the  
central management station via Modbus, or manual by pressing operating mode button  
.
No changeover is possible if the thermostat is configured for cooling only or heating only (see parameter P01).  
Meaning of cooling and heating symbols when displaying on LCD:  
For automatic changeover or heating only/cooling only:  
-
-
Heating valve is open  
Cooling valve is open  
For manual changeover only:  
-
-
Thermostat is in heating mode  
Thermostat is in cooling mode  
Parameter Description  
Factory setting  
Setting range  
2-pipe = 1 [selection: 0…3] 0 = Heating only; 1 = Cooling only; 2 = H/C changeover manual  
P01  
Control sequence  
4-pipe = 4 [selection: 2, 4]  
3 = H/C Changeover auto; 4 = Heating and cooling  
3 = Comfort – Protection; 4 = Comfort - Economy - Protection  
0 = °C (Celsius); 1 = °F (Fahrenheit)  
P02  
P04  
Mode selection by user via operating mode button  
Unit  
3
0
Measured value correction (for built-in/external  
sensor)  
-5 K...5 K  
P05  
P06  
P07  
0
0
0
Standard display  
0 = Room temperature; 1 = Setpoint; 2 = Temperature value via bus  
0 = No display; 1 = Room temperature °C or °F; 2 = Outside temperature (via bus)  
3 = Time of day (12 h) via bus; 4 = Time of day (24 h) via bus  
Additional display information  
21 °C  
5 °C  
35 °C  
15 °C  
30 °C  
1
5...40 °C  
P08  
P09  
P10  
P11  
P12  
Comfort basic setpoint  
5...40 °C  
Minimum Comfort setpoint  
5...40 °C  
Maximum Comfort setpoint  
Economy heating setpoint (WheatEco)  
Economy cooling setpoint (WcoolEco)  
OFF, 5 °C…WcoolEco  
OFF, WheatEco…40 °C  
0 = Disabled; 1 = Enabled  
P13 *** Electrical heater in cooling mode  
0 = Unlock; 1 = Lock (all lock); 2 = Setpoint adjustable; 3 = Setpoint lock; 4 = Fan lock;  
5 = Operating mode lock  
P14 Key lock  
0
All temperature settings are in increments of 0.5 °C.  
***Parameter P13 is only displayed for application "2-pipe with electric heater".  
Issued by  
© Siemens Switzerland Ltd, 2020  
Technical specifications and availability subject to change without notice.  
Siemens Switzerland Ltd  
Smart Infrastructure  
Global Headquarters  
Theilerstrasse 1a  
CH-6300 Zug  
Tel. +41 58 724 2424  
2/2  
A6V12060783_en--_c  
A5W00123793A_AC  
2022-11-24  
Siemens Smart Infrastructure  
GeneralDetails
NameSIEMENS RDF660MB Flush Mount Room Thermostat Instruction Manual
MakeSIEMENS
LanguageEnglish
FiletypePDF (Download)
File size1.04 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDZ100ZB Zigbee Room Thermostat Owner’s Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS RDG400 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS M3182 Room Thermostat Instruction Manual
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS RDS120-B Smart Thermostat Instructions
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS Powers Controls TH 192-3 Series Day Night Vent Room Thermostat Instruction Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDY2000BN BACnet Commercial Thermostat User Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Room Thermostat Instruction Manual
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RDH100RF/SET Wireless Room Thermostat with LCD User Guide
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RS485 Flush Mounted Room Thermostat User Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual
SIEMENS RDG260KN Room Thermostat Instruction Manual

SIEMENS RDF660MB Flush Mount Room Thermostat Instruction Manual