Example  
Example  
Parameters  
Note  
Min. expected ambient  
temperature  
15°C  
/ –15°C  
Range: –40°C to 0°C  
Sensor PASC (AMBIENT)  
Default: –15°C  
The temperature is the minimal outdoor  
temperature to be expected and will be  
used for the ambient temperature (PASC)  
algorithm only. It will set the correct duty  
cycle for an optimized and energy saving  
operation. If the ambient temperature is  
below this set point, the relay is 100% ON.  
Select the temperature by using  
the + / – keys.  
Cable type  
15XL2-ZH  
Heating cable range:  
10XL2-ZH  
Select the type of nVent RAYCHEM heating  
cable used in your installation, connected to  
heating zone 1.  
XL-TRACE -1  
15XL2-ZH  
26XL2-ZH  
Other system can be used if the heating  
cable type is not known or listed.  
31XL2-ZH  
FS-C10-2X  
Other systems  
Default: ---  
Cable type  
15XL2-ZH  
Heating cable range:  
10XL2-ZH  
Select the type of nVent RAYCHEM heating  
cable used in your installation, connected to  
heating zone 2.  
XL-TRACE -2  
15XL2-ZH  
Other system can be used if heating cable  
type is not known or listed.  
26XL2-ZH  
31XL2-ZH  
FS-C10-2X  
Other systems  
Default: ---  
Pipe diameter  
DN 25  
/ DN 25  
Range: DN 10 - DN 125  
Assign the correct pipe diameter per  
heating zone 1 and/or 2.  
Default: DN 25  
You can change the value from DN 10 up  
to DN 125.This has impact in the ambient  
temperature sensing mode to define the  
correct duty cycle.  
Note: In case of multiple pipe sizes per  
heating zone, select the bigger size of the  
pipe network.  
Low temperature alarm 0°C  
/ 0°C  
Standard NTC Sensor:  
Range : –40°C to +78°C  
Default: 0°C  
To determine the low temperature limit.  
When the value is reached, a warning will  
appear on the screen. The buzzer tone will  
be active.  
The relay will be continuously ON and will  
not interrupt the unit’s functioning. The info  
status main screen will show the actual  
pipe temperature.  
PT-100 Sensor with  
SM-PT-100-2:  
Range: –40°C to +245°C  
Default: 0°C  
High temperature alarm +65°C  
+65°C  
Standard NTC Sensor:  
Range : +2°C to +90°C  
Default: +65°C  
To determine the high temperature limit; A  
warning will appear on the screen when the  
value is reached.  
The relay will be continuously OFF and will  
not interrupt the unit’s functioning.  
PT-100 Sensor with  
SM-PT-100-2:  
Value range:  
+2°C to +90°C /Standard NTC sensor  
Range: +2°C to +250°C  
Default: +65°C  
+2°C to +250°C /Sensor module  
SM-PT-100-2 for PT-100  
RAYCHEM-OM-EU1838-ELEXANT450c-ML-2108  
nVent.com/RAYCHEM  
|
6
GeneralDetails
NameRaychem Elexant 450c Thermostat Instruction Manual
MakeRaychem
LanguageEnglish
FiletypePDF (Download)
File size0.42 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

Raychem Elexant 450c Thermostat Instruction Manual