Raychem Elexant 450c Thermostat Instruction Manual
FACTORY SETTINGS (DEFAULT)
Language
English
Country
None; To be selected
Date
01/01/2018 or last saved date
Time
00:00 or last saved time
Operation mode
To be selected
To be selected
DN 25
30 mm
+3°C
Heating cable type
Pipe diameter
Insulation thickness
SET temperature
Minimum ambient temperature
Heating in sensor failure mode
Low temperature limit
High temperature limit
Low temperature alarm
High temperature alarm
Alarm sound
–15°C
ON
–40°C
+85°C
0°C
+65°C
OFF
Key lock
ON
ERROR / ALARMS AND TROUBLESHOOTING
Error Code
E:2.1
E:2.2
E:2.3
E:2.4
E:3.1
E:3.2
E:4.1
E:4.2
E:5
Elexant 450C
Remedy
SENSOR_1_OPEN
SENSOR_1_SHORT
SENSOR_2_OPEN
SENSOR_2_SHORT
SENSOR_1_TEMP_HIGH
SENSOR_2_TEMP_HIGH
SENSOR_1_TEMP_LOW
SENSOR_2_TEMP_LOW
n/a
Check sensor connection
Check sensor and replace it
Check sensor connection
Check sensor and replace it
Sensor 1 High temperature alarm
Sensor 2 High temperature alarm
Sensor 1 Low temperature alarm
Sensor 2 Low temperature alarm
E:6.0
E:6.1
E:6.2
E:6.3
E:6.4
E:6.5
E:6.6
n/a
INTERNAL_ERROR
INTERNAL_ERROR_RTC
INTERNAL_ERROR_PM
INTERNAL_ERROR_ADC
INTERNAL_ERROR_IP
n/a
Replace unit
Replace unit
Replace unit
Replace unit
Replace unit
RAYCHEM-OM-EU1838-ELEXANT450c-ML-2108
nVent.com/RAYCHEM
|
8
| General | Details |
|---|---|
| Name | Raychem Elexant 450c Thermostat Instruction Manual |
| Make | Raychem |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.42 MB |