Home > Raychem > Raychem Elexant 450c Thermostat Instruction Manual

Raychem Elexant 450c Thermostat Instruction Manual

FACTORY SETTINGS (DEFAULT)  
Language  
English  
Country  
None; To be selected  
Date  
01/01/2018 or last saved date  
Time  
00:00 or last saved time  
Operation mode  
To be selected  
To be selected  
DN 25  
30 mm  
+3°C  
Heating cable type  
Pipe diameter  
Insulation thickness  
SET temperature  
Minimum ambient temperature  
Heating in sensor failure mode  
Low temperature limit  
High temperature limit  
Low temperature alarm  
High temperature alarm  
Alarm sound  
15°C  
ON  
40°C  
+85°C  
0°C  
+65°C  
OFF  
Key lock  
ON  
ERROR / ALARMS AND TROUBLESHOOTING  
Error Code  
E:2.1  
E:2.2  
E:2.3  
E:2.4  
E:3.1  
E:3.2  
E:4.1  
E:4.2  
E:5  
Elexant 450C  
Remedy  
SENSOR_1_OPEN  
SENSOR_1_SHORT  
SENSOR_2_OPEN  
SENSOR_2_SHORT  
SENSOR_1_TEMP_HIGH  
SENSOR_2_TEMP_HIGH  
SENSOR_1_TEMP_LOW  
SENSOR_2_TEMP_LOW  
n/a  
Check sensor connection  
Check sensor and replace it  
Check sensor connection  
Check sensor and replace it  
Sensor 1 High temperature alarm  
Sensor 2 High temperature alarm  
Sensor 1 Low temperature alarm  
Sensor 2 Low temperature alarm  
E:6.0  
E:6.1  
E:6.2  
E:6.3  
E:6.4  
E:6.5  
E:6.6  
n/a  
INTERNAL_ERROR  
INTERNAL_ERROR_RTC  
INTERNAL_ERROR_PM  
INTERNAL_ERROR_ADC  
INTERNAL_ERROR_IP  
n/a  
Replace unit  
Replace unit  
Replace unit  
Replace unit  
Replace unit  
RAYCHEM-OM-EU1838-ELEXANT450c-ML-2108  
nVent.com/RAYCHEM  
|
8
GeneralDetails
NameRaychem Elexant 450c Thermostat Instruction Manual
MakeRaychem
LanguageEnglish
FiletypePDF (Download)
File size0.42 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

Raychem Elexant 450c Thermostat Instruction Manual