Home > Warmup > warmup RFT-P Programmable Radiant Floor Thermostat User Manual

warmup RFT-P Programmable Radiant Floor Thermostat User Manual

Cancel the key lock mode:  
Ground Fault Circuit Interrupter (GFCI)  
Under real-time temperature interface, press and hold until the lock mark on the screen  
This thermostat has a built-in GFCI function that protects people from electric shock. It is very  
important to check whether the GFCI function is normal or not every month using these check  
steps:  
disappears.  
USER MANUAL  
Weekly program parameter setting  
In the automatic mode, the thermostat runs automatically according to the setting parameters  
of the weekly program. The weekly program parameters contain two parameters: Schedule  
and Event.  
1. Confirm that the thermostat is turned on.  
2. Press the [Test Monthly] button. If a red light appears in the upper left corner of the  
thermostat and GROUND FAULT appears on the screen, the GFCI function is normal. If there  
is no response, it means the function is invalid; please contact the dealer or electrical installer.  
Note: Do not press and hold the [Test Monthly] button.  
4.Sensor selection - In addition to the floor sensor, this thermostat has built-in sensors to  
detect room temperature. Therefore, three sensor applications are available:  
Room: Controls room temperature based solely on built-in air sensor.  
Floor: Controls the floor temperature based solely on the floor sensor.  
Room Limit: Controls the room temperature based on the built-in sensor while monitoring  
the floor temperature not to exceed the upper limit. This application, like Floor, can be used  
in places such as wood floors where floor temperature is critical.  
Model: RFT-P  
1. Schedule  
Programmable Radiant Floor Thermostat  
Assign seven days a week to the following two schedules:  
5+1+1: The Event parameter is the same from Monday to Friday, with separate Event  
parameters on Saturday and Sunday.  
3. Press the [Reset] button. The red light is off and the screen shows the power off state.  
4. Press the [Reset] button again. The thermostat is turned on.  
warmup.com  
7: With separate Event parameters every day.  
Schedule parameter setting method:  
RFT-P V1.1  
Sensor Selection setting method:  
If in daily use, the red light is on and the screen appears GROUND FAULT, then you need to  
check if the ground fault is present by pressing the [Reset] button. If the red light is off and the  
screen shows the shutdown status, it is nuisance tripping. If not, it means that ground fault has  
occurred. Please contact your dealer or professional technician immediately.  
After entering Settings, tap ▲ or ▼ to select Sensor Selection .  
Under real-time temperature interface, tap OK to enter the first level menu, and Mode is  
flashing.  
Tap OK to enter the selection.  
Tap ▲ or ▼ to select the sensor application type.  
Installation  
Tap ▲ or ▼ to select Schedule.  
Tap OK to confirm.  
1.Loosen the bottom screw by a Phillips  
screwdriver, then open the thermostat from the upper  
right side as shown.  
Tap OK to enter the parameter settings.  
Tap OK to return to the real-time temperature interface.  
Note: If Room.Limit is selected, you need to set the maximum temperature that the floor  
can accept.  
Tap ▲ or ▼ to select a parameter.  
Instruction  
Tap OK to confirm.  
The RFT-P thermostat controls your floor heating system based on built-in weekly program,  
running in 4 or 2 stages per day, 7 days a week. The default weekly program parameters  
satisfies most usage scenarios, however you can also modify the weekly program parameters  
in the thermostat. When there is no one in the house, it is recommended to set the  
temperature down to save energy. The thermostat also has built-in adaptive function. When  
this function acts, the thermostat heats or stops heating in advance of next stage to bring  
the room temperature to the set temperature of the next stage. Please note that after turning  
adaptive on, the thermostat takes a few days to learn the time required.  
Tap OK to return to the real-time temperature interface.  
2. Event  
In the Home scenario, the day is divided into four events:  
5. Calibration - This thermostat has built-in probe and floor sensor calibration function. In the  
case of demand for higher precision  
Note: You do not need to unscrew the screw com-  
pletely.  
Calibration setting method:  
After entering Settings , tap ▲ or ▼ to select Calibration .  
Wake--  
Leave-- Return--  
Sleep--  
2. Wire as shown:  
Tap OK to go to select Room or Floor .  
Tap ▲ or ▼ to select Compensate Built-in Probe or Floor Sensor.  
(In the Office scene, the day is divided into two phases: on work-- off work-- ).  
The set temperature for each stage can be set separately.  
Event parameter setting method:  
L/N lead: Connect the power cord using the terminal block.  
L1/N1 lead: Use a terminal block to connect the load line.  
IN/SNR terminal: Connect the floor sensor.  
Tap OK to enter the compensation setting.  
Tap ▲ or ▼ to adjust the real-time temperature to match the displayed temperature value  
of the calibration instrument.  
Under real-time temperature interface, tap OK to enter the first level menu, and Mode is  
flashing.  
OUT terminal: Connect to IN/SNR of Power Module.  
Note: Disconnect the main power supply before wiring.  
Tap OK to return to the setting item selection.  
Tap ▲ or ▼ to select Event.  
6. Location - This thermostat is suitable for use in both homes and offices. For the office, a  
set of weekly program parameters is built in. See the Weekly Program Parameters section for  
details.  
Functions and operation  
Tap OK to enter the week selection.  
If an electric floor heating cable or mat system requires more than 15 Amps, install a  
power module. [Wiring diameter: 12 to 22 AWG]  
Tap ▲ or ▼ to select the day you want to modify the parameters.  
Tap OK to enter the stage selection for the day.  
Location setting method:  
After entering Settings, tap ▲ or ▼ to select Location.  
1 On/Off/GFCI Reset Button  
2 GFCI Test Button  
3 Mode  
4 Temperature  
5 Sensor Selection  
6 Setpoint  
7 Event  
8 Date and Time  
9 Touch Buttons  
Tap ▲ or ▼ to select the stage that you want to modify the parameters.  
Tap OK to enter the temperature setting of the current phase.  
Tap ▲ or ▼ to select the temperature value you want to set.  
Tap OK to enter the hour setting for the start time of the current phase.  
Tap ▲ or ▼ to select the hour of the start time.  
Tap OK to go to select Office or Home.  
Tap ▲ or ▼ to select one.  
Tap OK to confirm.  
Tap OK to return to the real-time temperature interface.  
7.Adaptive  
Tap OK to enter the minute setting for the start time of the current phase.  
Note: Return to the interface of the real-time temperature and tap multiple times.  
This thermostat has an adaptive function. When this function is enabled, the thermostat  
heats up or stops heating in advance so that the next stage comes and the temperature just  
reaches the set temperature.  
Adaptive setting method:  
After entering Settings, tap ▲ or ▼ to select Adaptive.  
Event default parameter list  
Tap OK to enter the selection.  
Press ▲ or ▼ to get Yes or No.  
Tap OK to confirm.  
On/Off  
3. Install the back cover into the  
terminal box and secure it with the  
set screw.  
Tap OK to return to the real-time temperature interface.  
The GFCI Reset button is also the switch button. Press the [Reset] button to switch the  
8.Readout  
thermostat on and off.  
This thermostat has the function of calculating the percentage of heating time over  
a period of time. The relevant parameters can be queried through the Readout  
item.  
Readout query method:  
After entering Settings, tap ▲ or ▼ to select Readout.  
Temporary Override Temperature  
4. Fit the left side of the front and  
rear covers as shown. Rotate to the  
right again and press the upper half  
of the right border until you hear a  
click. Secure the bottom screw.  
Turn on the power and test the  
GFCI function.  
This function is enabled in the automatic intelligent mode; when the temperature demand  
changes, the setting temperature is enabled, but the parameters in the Event schedule are not  
changed.  
Operation method:  
Settings  
Tap OK to enter the selection.  
Tap ▲ or ▼ to select 1Day, 30Days or 365Days to query.  
Under the interface showing the real-time temperature, tap ▲ or ▼ to modify the set  
temperature.  
In addition to the above common functions, the thermostat also provides a number of  
advanced settings. It should be noted that such settings should be set by professional  
technicians to avoid damage caused by abnormal settings.  
Settings access method:  
Tap OK to return to the setting item selection.  
Tap OK to confirm and return to the interface showing the real-time temperature.  
9.Factory reset  
Mode selection  
This thermostat provides three operating modes:  
This thermostat has the function of restoring factory parameters.  
Factory Reset setting method:  
Under real-time temperature interface, tap OK to enter the first level menu, and Mode is  
flashing.  
WARNINGS  
To avoid risk of electric shock, disconnect all power coming to heater at main service panel  
before installing the thermostat. Keep thermostat air vents clean and free from obstructions.  
All wiring must conform to local and national electrical codes and ordinances. Installation  
must be carried out by qualified personnel.  
Automatic mode: According to the weekly program, the thermostat automatically adjusts the  
set temperature operation.  
Tap ▲ or ▼ to select Settings.  
After entering Settings, tap ▲ or ▼ to select Factory Reset.  
Tap OK to enter the selection.  
Tap ▲ or ▼ to select Yes or No.  
Tap OK to confirm.  
Tap OK to return to the real-time temperature interface.  
Tap OK to enter Settings.  
Settings contains the following items:  
Manual mode: The thermostat runs continuously according to the set temperature.  
Frost protection mode: The temperature controller runs at a lower set temperature. The  
temperature range is set from 41°F to 59°F in this mode. This mode is used when you want  
to keep your room at a lower temperature when you are on vacation.  
How to set the mode selection:  
1.Time - Set the current real time and day of the week.  
Time setting method:  
After entering Settings, tap ▲ or ▼ to select Time.  
Classification  
Settings default parameter list  
Tap OK to enter the hour setting for the time.  
Tap ▲ or ▼ to select the hour value for the current time.  
The thermostat is a Class II device (reinforced insulation) and used for controlling electrical  
floor heating. The product must be connected to the following leads:  
L/N lead: Connect the power cord using the terminal block.  
In the interface displaying the real-time temperature, tap OK to enter the first level menu, and  
Mode is flashing.  
Tap OK to enter the minute setting for the time.  
Tap ▲ or ▼ to select the minute value for the current time.  
Tap OK to enter the mode selection.  
Tap OK to enter the day of the week setting.  
Tap ▲ or ▼ to select the day of the week.  
L1/N1 lead: Use a terminal block to connect the load line(Max 15A).  
Note: Electric floor heating cable/mat must be in accordance with the supply voltage. The  
terminals are designed to handle a cross-section of wire measuring 12-22AWG.  
Tap ▲ or ▼ to change the mode.  
Tap OK to confirm your selection.  
Tap OK to enter the hour setting for the time.  
If you select manual mode or freeze protection mode, you also need to tap ▲ or ▼ to set the  
temperature.  
Tap multiple times to return to the real-time temperature interface.  
2. Temp unit - °F or °C can be selected as the temperature unit.  
Temp Unit setting method:  
Tap OK to return to the interface showing the real-time temperature.  
Technical specification  
After entering Settings, tap ▲ or ▼ to select °F/°C.  
Key lock  
Supply voltage: 120/240 VAC 50/60 Hz Load: max.15 A (resistive load)  
GFCI: Class A (5 mA trip level) Setpoint range: +5 to +40°C / +41 to +104°F  
Temperature range: +5 to +45°C / +41 to +113°F  
Tap OK to enter the selection.  
Tap ▲ or ▼ to select the desired temperature unit.  
The thermostat provides a key lock function to prevent the thermostat setting parameters from  
being incorrectly modified.  
Tap OK to confirm.  
Note: the [Reset] button and the [Test Monthly] button still operate normally so as to respond  
Tap OK to return to the real-time temperature interface.  
to an emergency.  
Dimensions (inches)  
3.Sensor type - This thermostat connects to the supplied floor sensor but also to two other  
commonly used floor sensors; useful when replacing an existing floor thermostat.  
Sensor Type setting method:  
Set the key lock mode:  
1. Under real-time temperature interface, press and hold until the lock symbol appears.  
2. Under real-time temperature interface, tap OK to enter the first level menu, and Mode is  
flashing.  
After entering Settings, tap ▲ or ▼ to select Sensor Type.  
Troubleshooting  
Tap OK to enter the selection.  
Tap ▲ or ▼ to select the type of floor sensor you are currently using.  
Tap ▲ or ▼ to select Key Lock.  
E1: Built-in probe failure, please contact your dealer or professional technician.  
E2: External probe failure, please contact your dealer or professional technician  
Tap OK to enter the key lock setting.  
Tap OK to confirm.  
Tap OK to confirm.  
Tap OK to return to the real-time temperature interface.  
Warranty: 1-Year replacement Warranty  
Tap OK to return to the interface showing the real-time temperature.  
GeneralDetails
Namewarmup RFT-P Programmable Radiant Floor Thermostat User Manual
MakeWarmup
LanguageEnglish
FiletypePDF (Download)
File size0.21 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Warmup 6iE mini WiFi Thermostat User Guide
Warmup 6iE mini WiFi Thermostat User Guide
Warmup 3iE Energy Monitoring Thermostat Instruction Manual
Warmup 3iE Energy Monitoring Thermostat Instruction Manual

warmup RFT-P Programmable Radiant Floor Thermostat User Manual
Get the free PDF manual for the warmup RFT-P Programmable Radiant Floor Thermostat User Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

warmup RFT-P Programmable Radiant Floor Thermostat User Manual Overview

Summary of Contents

  • Page 1: Cancel the key lock mode. Ground Fault Circuit Interrupter (GFCI) protects people from electric shock. Check the GFCI function every month using specific steps. The thermostat runs automatically according to the weekly program parameters. The weekly program parameters contain two parameters: Schedule and Event. This thermostat has built-in sensors to detect room temperature. The thermostat controls your floor heating system based on a built-in weekly program. The thermostat has an adaptive function that adjusts heating in advance. The GFCI Reset button is also the switch button. This thermostat has the function of restoring factory parameters.