Home > LUX > LUX PSP511Ca Programmable Thermostat Instruction Manual

LUX PSP511Ca Programmable Thermostat Instruction Manual

TEMPERATURE HOLD  
SETUP OPTIONS  
A Temperature Hold is similar to an override, but is used for maintaining a  
constant set temperature for a longer time duration. Once a Hold is initiated, the  
thermostat will maintain the Hold set temperature indefinitely. A temperature  
hold may be used for days, weeks, or even months at a time. To enter a Hold,  
push the HOLD button once, and the word Hold will appear in the temperature  
portion of the screen, along with the set temperature flashing. While the set  
temperature is flashing, push either the UP or DOWN button to the new desired  
set temperature value. To cancel a Hold, press and release the HOLD button once  
again, rotate the dial, or change the Temperature mode switch.  
INSTALLATION AND  
OPERATING INSTRUCTIONS  
SYSTEM TYPE SETTING:  
This setting tells the thermostat about the type of heating and cooling equipment that  
it is controlling, so that the system is operated properly. There are two operating  
modes based on your system type, “Furnace (Fn)” or “Heat Pump (HP)”. If you have a  
Furnace, ensure this is set to "Fn". If you have a Heat Pump, ensure this is set to  
"HP".  
PSP511Ca / PSP511LCa  
Programmable Thermostat  
Install two new Energizer®  
or DURACELL® "AA" size alkaline batteries before  
WARNING: Use Energizer® or DURACELL® Alkaline Batteries Only.  
Energizer® is a registered trademark of Eveready Battery Company, Inc.  
DURACELL® is a registered trademark of The Gillette Company, Inc.  
continuing further. Ensure that the batteries are installed in the proper direction as per  
the markings shown in the battery tray. With the thermostat powered by batteries,  
press and hold the HOLD button, and then press the Hardware Reset button once on  
the back of the unit’s circuit board. Continue to hold the HOLD button until “SYS” is  
shown on the LCD screen. Use the UP or DOWN buttons to toggle between “Fn” and  
“HP” modes. When you are finished, press NEXT. This setting is now complete, and  
will not change unless you adjust it again. This is true even in the event of a power  
failure, or if a reset button is pressed.  
AIR FILTER MONITOR  
The Air Filter Monitor counts the number of days, and the amount of usage since  
your furnace filter has been replaced. In Run mode, the CHANGE FILTER indicator  
will appear when the remaining filter days have reached zero and the filter  
should be changed. To set and use the Air Filter Monitor, turn the rotary dial to  
AIR FILTER. Press NEXT and the Filter Days Left value will start flashing. Use  
the UP or DOWN buttons to select the number of days of filter life that your filter  
is rated for. Setting this value to OFF will disable the filter monitor. Return the  
dial to the RUN position once you are finished setting the filter life. To monitor  
the Filter Days Left or Filter Percent Left, turn the dial to the AIR FILTER position.  
The amount of filter life remaining will be shown in the clock portion of the  
display screen. Return the dial to the RUN position once you are finished viewing  
the filter life remaining.  
Mt. Laurel, New Jersey 08054, USA  
52074  
Thank you for your confidence in our product. To obtain the best results from your  
investment, please read these instructions and acquaint yourself with your purchase.  
NOTE:  
All of the settings, options, and components listed in this section are located on the  
rear of the thermostat, on the circuit board.  
COMPATIBILITY  
This thermostat can be used with most single stage 24 volt: gas, oil or electric heating  
and/or cooling systems, single stage heat pumps, or gas Millivolt heating systems. It  
cannot be used with 3-wire zone valves, 120 volt heating systems, or multi-stage heat  
pumps. Ask your dealer for other LUXPRO thermostats to control those systems.  
HARDWARE RESET  
The hardware reset is a push button that is located on the right edge of the circuit  
board, just above the battery location. This reset button is used by the thermostat to  
reset the unit’s clock, and read the position of all of the option switches. When any of  
the following items are changed, the hardware reset button must be pushed for the  
change to be recognized. User temperature programs are not erased when a hardware  
reset is performed.  
RESET FILTER COUNTER  
Once you have replaced your filter, the filter life counter is reset back to its full  
amount remaining value by turning the dial to AIR FILTER and pressing the UP  
and DOWN buttons together at the same time. NOTE: The counter is also reset  
by changing the filter setting value, as described above, to a different number of  
days.  
FEATURES  
LCD - Liquid Crystal Display  
Set Temperature Buttons  
Fan Mode  
Switch  
HEAT FAN CONTROL  
This setting defines the fan operation while in Heat mode, and when the fan is in Auto.  
This setting has no effect while the thermostat is in Cool mode, or if there is no blower  
fan connected to the “G” wire terminal.  
ADVANCED FEATURES  
TU  
SWING SETTING  
DAY  
HEAT  
FAN  
PM  
A thermostat works by turning your heating or cooling system on and off  
whenever the room temperature varies from the set-point temperature. The  
amount of this variation is called the “swing.” Your system should cycle on about  
3 to 6 times per hour. A smaller swing number increases the number of cycles  
per hour, so the room temperature is more precise and constant. A larger swing  
number decreases the number of cycles per hour, but saves energy in most  
cases. To change the Swing setting, turn the dial to RUN mode. Hold down the  
NEXT button and push the HOLD button once, then let go of both. The words  
SWING and SET will appear on the screen with a number. Use the UP/DOWN  
buttons to change the number value between 1 and 9. Number 1 is the default  
setting. Press the NEXT button to accept the setting and return to normal Run  
mode.  
:
Software  
Reset Button  
5 36 72  
GAS: Use this setting if you have a Gas or Oil heating  
system. In the GAS setting, the heating system itself  
controls the operation of the blower fan (if equipped).  
ELECTRIC: Use this setting if you have a Heat Pump or  
Electric heating system. In the ELEC setting, the heating  
system requires the thermostat to control the operation of  
Temperature  
Mode Switch  
JP1  
FAN  
WEEKEND  
PROGRAM  
FAN  
TEMERATURE  
HEAT  
WEEKDAY  
PROGRAM  
RESET  
AUTO  
ON  
OFF  
COOL  
NEXT  
R U N  
SET  
DAY/TIME  
LUX  
Quick Reference  
Door Instructions  
HOLD  
AIR FILTER  
Speed  
Dial®  
LUX  
PSP511Ca  
ELECTRIC  
GAS  
the blower fan.  
The following option settings are all located within a group of small switches labeled 1  
through 4 as shown below, and are located in the center of the circuit board.  
Small elegant design  
F/C Temperature Display  
12/24 Hr Clock Display  
Exclusive LUX Speed Dial®  
“ELIlluminated Display  
Air Filter Monitor  
TEMPERATURE CALIBRATION  
Adjustable Temperature Differential /  
Cycle Rate  
The internal temperature sensor in this thermostat is accurately calibrated at the  
factory. The Temperature Calibration feature allows you to manually offset the  
measured temperature by as much as plus or minus 5°F (3°C) degrees from its  
original value. This feature can be useful to match this thermostat to another  
one or more, if multiple thermostats are used in the same home. To change the  
Temperature Calibration, turn the dial to RUN mode, and place the Temperature  
mode switch in the OFF position. Hold down the UP button and push the DOWN  
button once, then let go of both. The words CAL and SET will appear on the  
screen with a number. Use the UP/DOWN buttons to change the number value  
between -5°F (-3°C) and +5°F (+3°C) degrees. 0 degrees of correction is the  
default setting. Press the NEXT button to accept the setting and return to Run  
mode.  
5-2 Day Programming  
Energy Star Compliant  
4 Periods Per Day  
User Temperature Offset /  
Calibration  
System or Battery Powered  
5 Minute Minimum Run/Off Time For  
Short Cycle and Compressor  
Protection  
TIME FORMAT  
This determines how the thermostat displays the clock and all other times on the  
screen. Switch position OFF is 12 HR, and ON is 24 HR.  
Battery Free Memory Storage  
Temporary Temperature Override  
Temperature Hold  
Keyboard Lockout  
TEMPERATURE SCALE  
This determines how the thermostat displays all temperatures on the screen. Switch  
position OFF is F°, and ON is C°.  
Please read ALL of these instructions carefully before beginning  
installation. Save them for future reference.  
FILTER DISPLAY  
This determines how the remaining filter life will be displayed when the rotary dial is  
turned to the AIR FILTER position. In the Percent (%) mode, the display will count down  
the percentage of air filter life remaining before a filter change is recommended. In  
the Days mode, the display will count down the number of calendar days remaining  
before a filter change is recommended. Switch position OFF is Percent mode, and ON  
is Days mode.  
INSTALLATION  
TOOLS REQUIRED  
#1 Phillips screwdriver  
Drill with 3/16 in. (4.8mm) bit  
Wire Stripper / Cutter  
BATTERY MONITOR  
CAUTION: This thermostat is protected against normal minor static electric  
discharges, however to minimize the risk of damaging the unit in extremely dry  
weather, touch a grounded metal object before touching your thermostat.  
This determines whether the internal battery voltage monitor watches the condition of  
the batteries that are installed in the thermostat. This setting should always remain  
enabled unless the thermostat is being powered by System Power alone, without any  
batteries present. Switch position OFF is Battery Monitor On (Enabled), and Switch  
position ON is Battery Monitor Off (Disabled).  
LOCATION  
On replacement installations, mount the new thermostat in place of the old one unless  
the conditions listed below suggest otherwise. On new installations, follow the  
guidelines listed below.  
1. Locate the thermostat on an inside wall, about 5 ft. (1.5m) above the floor, and in a  
room that is used often.  
PROGRAMMING  
FRONT PANEL ITEMS  
For all of the programming areas that are described below, this thermostat  
provides four independent periods per day for Heat mode and Cool mode, they  
are: MORN, DAY, EVE, and NITE. Each period ends at the start time of the  
following period. The programs for each Temperature mode are programmed  
separately. When you perform a Software Reset, a default temperature program  
routine is inserted into all of the program periods. You can use these default  
programs or alter any portion of them to suit your own preferences. When setting  
the program items, the value that is flashing is the item that you can change at  
that time.  
SOFTWARE RESET  
The software reset is a small recessed push button that is located right above the  
NEXT button. This button can be pushed with a pencil or the end of a paper clip. This  
reset clears all of the heating and cooling programs, filter settings, and  
other user changeable preferences to their default values. You should write down your  
heating and cooling program times and temperatures prior to using the software reset.  
2. Do not locate where air circulation is poor, such as in a corner or an alcove, or  
behind an open door.  
3. Do not install it where there are unusual heating conditions, such as: in direct  
sunlight; near a lamp, television, radiator, register, or fireplace; near hot water  
pipes in a wall; near a stove on the other side of a wall.  
4. Do not locate in unusual cooling conditions, such as: on a wall separating an  
unheated room; or in a draft from a stairwell, door, or window.  
5. Do not locate in a damp area. This can lead to corrosion that may shorten  
thermostat life.  
MODE SWITCHES  
There are two mode switches on the front, a Temperature mode switch and a Fan  
mode switch. The Temperature mode switch has three positions: HEAT, OFF, and COOL.  
In the winter, set the system switch to HEAT to control your heating system. In the  
summer, set the switch to COOL to control your air conditioner. In the spring and fall or  
when the windows are open, you can set the switch OFF. The Fan mode switch has  
two positions, AUTO and ON. Setting the Fan mode switch to AUTO, automatically runs  
your system's blower fan as required only during heating and cooling activation.  
Setting the Fan mode switch to ON, runs your system’s fan continuously, even if  
heating or cooling is not needed,  
SET WEEKDAY PROGRAM  
Select either HEAT or COOL with the Temperature mode switch. Rotate the dial to  
WEEKDAY PROGRAM. You will be programming all five weekdays at the same  
time. The first period is MORN. Using the UP and DOWN buttons, set the start  
time for this period, and then push the NEXT button to proceed. Now set the  
desired set temperature for the MORN period using the UP and DOWN buttons,  
and push NEXT to proceed. Now set the start time and set temperature for the  
DAY period, pushing NEXT after each to advance. Continue with these same steps  
to set the start time and set temperature for the EVE, and NITE program periods.  
When you are finished setting all four periods, you may continue pushing the  
NEXT button through all four periods to review your entries, or turn the dial to  
RUN if you are finished. These same programming steps for all four periods must  
be performed in both Heat and Cool Temperature modes independently.  
6. If painting or construction work has yet to be completed, cover the unit completely  
or do not install it.  
WARNING:  
Read instructions carefully before removing any wires from your existing  
thermostat.  
This thermostat should be limited to 1.5 amps per terminal, and a maximum  
of 2 amps total; higher current than this may cause damage to the thermostat.  
All wiring must conform to the local codes and ordinances that are in your  
particular location.  
including when the Temperature mode switch is in the OFF position to provide air  
circulation only.  
NOTE:  
The Fan mode switch only works if your system provides a wire for the thermostat’s  
“G” wire terminal.  
REMOVAL OF OLD UNIT  
SET WEEKEND PROGRAM  
1. Turn OFF the electricity to all heating and cooling components.  
Do not turn the electricity back on until all work is completed.  
2. Remove the cover and front portion of your old thermostat to  
expose the wiring connections.  
Turn the dial to WEEKEND PROGRAM. You will be programming both Saturday and  
Sunday at the same time. You will begin with the start time of the MORN period,  
and use the same procedures that were performed while setting the Weekday  
Program periods, using the NEXT button to advance through the values. Return  
the dial to the RUN position when you are finished.  
PUSH BUTTONS  
There are four primary push buttons on the front of the thermostat: The UP and DOWN  
arrow keys, the NEXT button, and the HOLD button.  
3. Write down the letters printed near each wire terminal that is  
used, and the color of the wire that is connected to it. Using the  
enclosed labels, attach a label to each of your wires so that the  
letter matches the marking on your existing thermostat.  
F
OF  
ROTARY DIAL  
The LUX Speed Dial®  
programming areas. This rotary dial has five individual positions.  
provides an easy way to quickly navigate between the different  
BATTERIES AND MAINTENANCE  
4. When they are all labeled, carefully remove the wires one at a time, making sure  
that they do not fall back inside the wall. Do not allow any of the bare wire ends to  
touch each other, or any parts on the thermostat.  
This thermostat can be powered either by “AA” alkaline batteries, by 24VAC  
system common power, or a combination of both. If you are using batteries  
alone, the batteries should be replaced AT LEAST once per year, or sooner if the  
LOW BAT battery symbol appears in the lower  
left portion of the display screen as shown  
below.  
OPERATING INSTRUCTIONS  
5. Loosen all of the screws on the old thermostat and remove it from the wall.  
SET DAY/TIME  
Rotate the dial to the SET DAY/TIME position. You should see the word SET appear on  
the display, along with the clock and a day of the week that is flashing. With the day  
flashing, press the UP button to advance the day to the desired day. Press the NEXT  
button, this should cause the time to start flashing and the day to remain on steady.  
Using either the UP or DOWN buttons, adjust the clock to the desired time. The clock  
digits will increment rapidly if either the UP or DOWN buttons are held in the pressed  
position.  
MOUNTING  
T
U
1. Strip insulation leaving 3/8 in. (9.5mm) bare wire ends and clean off any corrosion.  
2. Fill wall opening with non-combustible insulation to prevent drafts from affecting  
the thermostat.  
3. Remove the body from the thermostat’s base by pressing the thumb latch at the  
bottom center of the unit and swinging the body away.  
DAY  
LOW BAT  
PM  
:
To replace the batteries in the thermostat,  
remove the thermostat’s body from the base  
plate attached to the wall by pressing the  
LOW BAT  
5 36  
thumb latch at the bottom center of the unit and swinging the body towards you,  
up and away from the base. Remove the used batteries from the battery tray and  
discard appropriately.  
NOTE:  
HEATING AND COOLING  
If you are mounting the base to soft material like plasterboard or if you are using the  
old mounting holes, the screws may not hold. Drill a 3/16 in. (4.8mm) hole at each  
screw, and insert the plastic anchors provided.  
Basic operation of your heating or cooling system can be obtained by ensuring that the  
rotary dial is in the RUN position, and simply moving the Temperature mode switch to  
either the HEAT or COOL position. Prior to being set initially with your custom  
temperature program, and also after a Software Reset, the thermostat will follow the  
default temperature program routines that are preset within the thermostat’s memory,  
as shown below.  
Install two new Energizer® or DURACELL®, “AA” size alkaline batteries into the  
battery tray. Observe the polarity markings shown in the battery compartment to  
ensure proper installation. When finished, hang the top of the unit by the tabs at  
the top corners of the base, then snap the bottom of the unit into place. Do not  
use unnecessary force. If the body does not snap into place easily, remove the  
body, re-hang it from the tabs and try again.  
4. Hold the base against the wall. Route the wires through the hole below the terminal  
block. Position the base for best appearance (to hide any marks from an old  
thermostat). Attach the base to the wall with the two screws provided.  
CONNECTING THE WIRES  
5. Wires must be trapped between the black clamps and the brass  
terminals as shown here.  
PERIOD  
HEAT MODE  
COOL MODE  
TECHNICAL ASSISTANCE  
MORN 6:00 AM 70 °F (21 °C) 6:00 AM 78 °F (26 °C)  
DAY  
EVE  
If you have any problems installing or using this thermostat, please carefully and  
thoroughly review the instruction manual. If you require assistance, please  
contact our Technical Assistance department at 856-234-8803 during regular  
business hours between 8:00AM and 4:30PM Eastern Standard Time, Monday  
through Friday. You can also receive technical assistance online anytime day or  
most common technical questions, and also permits you to email your questions  
to our technical support staff at your convenience.  
8:00 AM 62 °F (17 °C) 8:00 AM 85 °F (29 °C)  
6:00 PM 70 °F (21 °C) 6:00 PM 78 °F (26 °C)  
6. Being careful not to overighten them, securely tighten all of the  
electrical terminal screws, including any unused ones.  
NITE 10:00 PM 62 °F (17 °C) 10:00 PM 82 °F (28 °C)  
NOTE:  
When you are finished performing your installation and setup options, please remove  
the thin plastic film that is protecting the LCD display screen on the front of the  
thermostat. This plastic may or may not be present, and is evident by the appearance  
of fake digits appearing on the display screen.  
MINIMUM RUN TIME DELAY  
This is determined by the thermostat, and controls the minimum length of time that  
the thermostat must remain with Heat or Cool either On or Off, before it will automat-  
ically switch to the alternate On or Off state. This feature prevents rapid or short  
cycling, and provides compressor protection for cooling equipment. The time amount  
for this delay is fixed at 5 minutes between on or off load changes.  
WARRANTY  
Limited Warranty: If this unit fails because of defects in materials or  
workmanship within three years of the date of original purchase, LUX will, at its  
option, repair or replace it. This warranty does not cover damage by accident,  
misuse, or failure to follow installation instructions. Implied warranties are  
limited in duration to three years from the date of original purchase. Some  
states do not allow limitations on how long an implied warranty lasts, so the  
above limitation may not apply to you. Please return malfunctioning or defective  
units to the location from which the purchase was made, along with proof of  
purchase. Please refer to “TECHNICAL ASSISTANCE” before returning thermostat.  
Purchaser assumes all risks and liability for incidental and consequential damage  
resulting from installation and use of this unit. Some states do not allow the  
exclusion of incidental or consequential damages, so the above exclusion may  
not apply to you. This warranty gives you specific legal rights and you may also  
have other rights which vary from state to state. Applicable in the U.S.A. and  
Canada only.  
WIRING INFORMATION  
TEMPERATURE OVERRIDE  
A Temperature Override occurs in Run mode, in either Heat or Cool, anytime the user  
adjusts the set temperature to a value that differs from the stored program  
temperature for that day and time. When the thermostat is in an Override, the word  
Override will appear in the temperature area of the display. The thermostat will  
maintain thermal control using this new set temperature, until the start of the next  
program period time is reached. At the start of the next program period, the set  
temperature will return to its programmed value. To enter an Override in either Heat or  
Cool mode, push either the UP or DOWN button once and the set temperature will  
begin to flash. Push either the UP or DOWN button to the new desired set temperature  
value. An Override may be cancelled by rotating the dial, changing the Temperature  
mode switch, or by initiating a Temperature Hold.  
** Complete heating and/or cooling system wiring can be found in the WIRE  
IDENTIFICATION AND WIRING SCHEMATICS section of this instruction sheet. The  
schematics shown provide component information for brand new installations or  
for unreferenced wires.  
©
2 0 0 9 L U X P R O D U C T S C O R P O R AT I O N . A L L R I G H T S R E S E R V E D  
GeneralDetails
NameLUX PSP511Ca Programmable Thermostat Instruction Manual
MakeLUX
LanguageEnglish
FiletypePDF (Download)
File size0.21 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
LUX TX700U Universal Thermostat Instruction Manual
LUX TX700U Universal Thermostat Instruction Manual
LUX TX500Ub Non Programmable Thermostat Instruction Manual
LUX TX500Ub Non Programmable Thermostat Instruction Manual
LUX TX1500E Programmable Thermostat Instruction Manual
LUX TX1500E Programmable Thermostat Instruction Manual
LUX CAG1500 SERIES Smart Temp Electronic Thermostat Instruction Manual
LUX CAG1500 SERIES Smart Temp Electronic Thermostat Instruction Manual
LUX PSP511A Smart Temp Electronic Thermostat Instruction Manual
LUX PSP511A Smart Temp Electronic Thermostat Instruction Manual
LUX PSP511A Series Programmable 5-2 Thermostat Instruction Manual
LUX PSP511A Series Programmable 5-2 Thermostat Instruction Manual
LUX PSPH521 Series Programmable Heat Pump Thermostat Instruction Manual
LUX PSPH521 Series Programmable Heat Pump Thermostat Instruction Manual
LUX DHP2120 Battery Powered Non Programmable Digital Heat Pump Thermostat Installation Guide
LUX DHP2120 Battery Powered Non Programmable Digital Heat Pump Thermostat Installation Guide
CH200SA Versatile Deluxe Low Voltage Thermostat Installation Guide
CH200SA Versatile Deluxe Low Voltage Thermostat Installation Guide
LUX TH10 Heating Only Mercury FREE Manual Thermostat Instruction Manual
LUX TH10 Heating Only Mercury FREE Manual Thermostat Instruction Manual

LUX PSP511Ca Programmable Thermostat Instruction Manual
Get the free PDF manual for the LUX PSP511Ca Programmable Thermostat Instruction Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

LUX PSP511Ca Programmable Thermostat Instruction Manual Overview

Summary of Contents

  • Page 1: Temperature hold is used for maintaining a constant set temperature for a longer duration. To enter a hold, push the HOLD button once and adjust the set temperature. To cancel a hold, press the HOLD button again or change the temperature mode switch. System type setting tells the thermostat about the type of heating and cooling equipment it controls. There are two operating modes: Furnace (Fn) or Heat Pump (HP). The air filter monitor counts the number of days since the furnace filter was replaced. The CHANGE FILTER indicator will appear when the filter should be changed. The hardware reset button is used to reset the unit’s clock and read the position of all option switches. User temperature programs are not erased when a hardware reset is performed. The temperature calibration feature allows you to manually offset the measured temperature by as much as plus or minus 5°F (3°C) degrees. The thermostat provides four independent periods per day for heat mode and cool mode, which can be programmed separately. The software reset clears all heating and cooling programs and user changeable preferences to their default values. The fan mode switch has two positions: AUTO and ON, controlling the operation of the blower fan. The keylock feature prevents tampering with settings and can be activated by a specific button sequence. The limited warranty covers defects in materials or workmanship within three years of the original purchase date.
  • Page 2: heating only systems jumper provided typical 2, 3, or 4-wire, 24-volt heating only systems and millivolt heating systems typical 5 and 6-wire, 24-volt heating and cooling systems with two transformers typical single stage heat pump wiring wiring diagram notes: all of the dashed wires are optional, and usage depends upon your specific system type if replacing a Honeywell TM-11, tape off the “R” wire if a “B” wire in your system is a common wire, connecting it to the “B” terminal of this thermostat may damage your system use B or O, not both