Home > ICM CONTROLS > ICM CONTROLS SC2010 N-L Non Programmable Electronic Thermostat Instruction Manual
ICM CONTROLS SC2010 N-L Non Programmable Electronic Thermostat Instruction Manual
1 Heat/1 Cool
Manual Changeover
Battery or Hardwire
To Install Thermostat
ELECTRICAL SHOCK HAZARD – Turn off power at the main service panel by removing
the fuse or switching the appropriate circuit breaker to the OFF position before
removing the existing thermostat.
SC2010 N/L
Non-Programmable Electronic Thermostat
IMPORTANT: Thermostat installation must conform to local and national building and
electrical codes and ordinances.
Note: Mount the thermostat about five feet above the floor. Do not mount the thermostat on an
• Configurable
outside wall, in direct sunlight, behind a door, or in an area affected by a vent or duct.
• Single Stage Heat/Cool Systems
• Single Stage Heat Pump Systems
• Large Display With Backlight (SC2010L)
• Selectable Fahrenheit or Celsius
• Compatible with Gas, Oil, or Electric
• SimpleSet™ Field Programming
1. Turn off power to the heating and cooling system by removing the fuse or switching the
appropriate circuit breaker off.
2. To remove cover, pull gently at the seam at the top.
3. Put thermostat base against the wall where you plan to mount it (Be sure wires will feed through
the wire opening in the base of the thermostat).
• Relay Outputs
(minimum voltage drop in thermostat)
4. Mark the placement of the mounting holes.
5. Set thermostat base and cover away from working area.
6. Using a 3/16” drill bit, drill holes in the places you have marked for mounting.
7. Use a hammer to tap supplied anchors in mounting holes.
• Ideally Suited for:
– Residential (New Construction/Replacement)
– Light Commercial
8. Align thermostat base with mounting holes and feed the control wires through slit in thermal
intrusion barrier and into wire opening.
9. Use supplied screws to mount thermostat base to wall.
10. Insert stripped, labeled wires in matching wire terminals.
CAUTION!: Be sure exposed portion of wires does not touch other wires.
Installation, Operation & Application Guide
For more information on our complete range of American-made products
– plus wiring diagrams, troubleshooting tips and more, visit us at www.
icmcontrols.com
11. Gently tug wire to be sure of proper connection. Double check that each wire is connected to the
proper terminal.
12. Place gas/elec jumper in correct position.
gas = gas/oil systems
elec = electric heat or heat pump systems
Parts Diagram
13. Remove RC/RH jumper for 2-transformer systems.
Up button
14. Non-heat pump jumper must be in Non-HP unless the system is a heat pump.
15. Insert 2 “AAA” batteries into battery holder. Orient them in the proper direction.
16. Turn on power to the system at the main service panel.
17. Configure thermostat (see Configuration Mode Settings) to match the type of system you have.
18. Replace cover on thermostat by snapping it in place.
19. Test thermostat operation as described in “Testing the Thermostat”.
Down button
HP/Non-Heat
Jumper
SC2010 N/L
Freeze
Protection
High
Temperature
Protection
Wiring Diagrams
Hardwired
4-Wire, Single Transformer
Hardwired
3-Wire, Single Transformer
Mode switch
Reset switch
Optional
Optional
Battery
compartment
Gas/Elec
RC/RH Jumper
Fan switch
Right switch
Left switch
Field programming pins
Specifications
Electrical rating:
• 24 VAC (18-30 VAC)
• 3.0 VDC (2 “AAA” batteries)
• 1 amp maximum per terminal
• 3 amp maximum total load
Common wire connection optional with batteries installed.
Temperature control range: 45°F to 90°F (7°C to 32°C) Accuracy: ± 1°F (± 0.5°C)
System configurations: 1-stage heat, 1-stage cool, heat pump, gas, oil, electric
Timing: Anti-short Cycle: 4 minutes
Hardwired
4 or 5-Wire, Single Transformer
Hardwired
Backlight Operation (Note: with SC2010L only)
5-Wire, Two Transformer
(Both transformers must be in phase)
Terminations: G, B, O, Y, RH, RC, W, C
Optional
Important Safety Information
Always turn off power at the main power supply before installing, cleaning,
Heating
Transformer
WARNING!
:
or removing thermostat.
• This thermostat is for 24 VAC applications only; do not use on voltages over 30 VAC
• Do not short across terminals of gas valve or system control to test operation; this will damage your
thermostat and void your warranty
Cooling
Transformer
• All wiring must conform to local and national electrical and building codes
• Do not use air conditioning when the outdoor temperature is below 50 degrees; this can damage
your A/C system and cause personal injuries
• Use this thermostat only as described in this manual
IMPORTANT: Before wiring, remove pre-installed
Common wire connection optional with
batteries installed.
RC/RH jumper.
Package Contents/Tools Required
Package includes: SC2010 N/L thermostat on base, thermostat cover, wiring labels, screws and wall
anchors, 2 “AAA” batteries, Installation, Operation and Application Guide
Tools required for installation: Drill with 3/16” bit, hammer, screwdriver
Hardwired
Cool or Heat Active Reversing Valve
Hardwired
4-Wire, Single Transformer
Optional
Optional
To Remove Existing Thermostat
ELECTRICAL SHOCK HAZARD – Turn off power at the main service panel by removing
the fuse or switching the appropriate circuit breaker to the OFF position before
removing the existing thermostat.
1. Turn off power to the heating and cooling system by removing the fuse or switching the appropriate
circuit breaker off.
2. Remove cover of old thermostat. This should expose the wires.
3. Label the existing wires with the enclosed wire labels before removing wires.
4. After labeling wires, remove wires from wire terminals.
5. Remove existing thermostat base from wall.
6. Refer to the following section for instructions on how to install this thermostat.
Common wire connection optional with
batteries installed.
Common wire connection optional with batteries
installed.
Note: Non-HP jumper must be installed on the
HP pin for heat pump systems
| General | Details |
|---|---|
| Name | ICM CONTROLS SC2010 N-L Non Programmable Electronic Thermostat Instruction Manual |
| Make | ICM CONTROLS |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.46 MB |

ICM CONTROLS SC2010 N-L Non Programmable Electronic Thermostat Instruction Manual Overview
Summary of Contents
- Page 1: Heat/1 Cool Manual changeover Battery or hardwire To install thermostat Electrical shock hazard - Turn off power at the main service panel before removing the existing thermostat. Thermostat installation must conform to local and national building and electrical codes and ordinances. Mount the thermostat about five feet above the floor. Installation, operation & application guide Test thermostat operation as described in “Testing the Thermostat”. Important safety information - Always turn off power at the main power supply before installing, cleaning, or removing thermostat. Package includes: SC2010 N/L thermostat on base, thermostat cover, wiring labels, screws and wall anchors, 2 “AAA” batteries. Tools required for installation: Drill with 3/16” bit, hammer, screwdriver.
- Page 2: Installing and changing batteries is essential for proper thermostat operation. In OFF mode, the thermostat will not activate heating or cooling devices. Cool mode allows the thermostat to control the cooling system. Heat mode enables the thermostat to control the heating system. Batteries are not required when a common wire is connected to the C terminal. The SC2010 N/L features a button lockout to limit temperature adjustments. Configuration mode is used to set the thermostat to match your system. SimpleSet field programming allows transferring configuration settings from a master thermostat to target thermostats. Troubleshooting includes checking for 24 VAC at the thermostat if there is no display. The one-year limited warranty covers defects in material or workmanship.