Home > ICM CONTROLS > ICM CONTROLS SC2010 N-L Non Programmable Electronic Thermostat Instruction Manual

ICM CONTROLS SC2010 N-L Non Programmable Electronic Thermostat Instruction Manual

Installing and Changing Batteries  
Operating Modes  
For Battery Thermostat Operation  
OFF Mode  
• In this mode, the thermostat will not turn on the heating or cooling devices (manual fan can operate)  
OFF mode is also used to access the configuration screens  
If your LCD is blank, or displaying LO BAT, the batteries are not installed or  
need to be changed. We suggest you change the batteries at least once a year,  
or whenever the LO BAT warning displays.  
Cool Mode  
Remove the cover, and install the two “AAA” alkaline batteries into the battery  
compartment. Proper battery installation is important! Make sure the positive  
ends of the batteries match the positive terminals in the battery compartment.  
• In this mode, the thermostat controls the cooling system  
Heat Mode  
• In this mode, the thermostat controls the heating system  
For Hardwired Thermostat Operation  
Batteries are not required when a common wire is connected to the C terminal of the SC2010 N/L  
thermostat.  
Lockout Feature  
The SC2010 N/L has a button lockout feature so the temperature adjustment is  
prohibited or limited. Select the appropriate lockout from Configuration Mode Settings  
(Step 4) of this guide.  
Configuration Mode  
The configuration mode is used to set the SC2010 N/L to match your system.  
To activate the LOC feature:  
To configure the SC2010 N/L, perform the following steps:  
1. Simultaneously press the LEFT, RIGHT and UP buttons for 10 seconds.  
2. LOC will display and the lockout function will be enabled.  
To deactivate the LOC feature, repeat steps 1 and 2 above.  
1. Verify the SC2010 N/L is in the OFF mode.  
Slide the system switch to the center position until off mode displays.  
2. Remove the cover of the thermostat by gently pulling near one of the  
corners at the top of the thermostat.  
TM  
SimpleSet Field Programming  
This feature is used for transferring the configuration settings from the master to the target  
thermostat. All thermostats for a job can be mounted and powered up. Configure one thermostat. This  
will be the master. The master will be used to copy the configuration to the rest of the thermostats.  
3. Press both the LEFT and RIGHT switches for 1 second while the SC2010 N/L is in OFF mode.  
Press the up or down button to change settings within each screen.  
Preparing the master to Send:  
1. The master must be powered by 24 VAC or batteries.  
Press the RIGHT switch to advance to the next screen.  
Note: Pressing the LEFT switch will return you to the previous screen.  
2. Verify the master thermostat is in OFF mode. Slide system switch to center  
position.  
To exit configuration mode, press both the LEFT and RIGHT switches for 1 second or slide the mode  
3. Remove cover of the master thermostat by gently pulling near one of the corners  
at the top of the thermostat.  
switch to heat or cool.  
4. Press the up and down buttons and RIGHT switch simultaneously for 5  
seconds.  
Configuration Mode Settings  
The setup screens for Configuration Mode are as follows:  
5. The OUT screen displays indicating the master thermostat is ready to  
transfer data.  
SC2010 N/L  
Note: Press the up and down buttons and RIGHT switch simultaneously for  
5 seconds to exit from data transfer mode and to return the master to  
the OFF mode.  
1. Temperature Scale (F or C) – Choose Fahrenheit or Celsius.  
Press the up or down button to select.  
F
P
P
i
n
s
6. Connect the master to the target using the 3 wire connector. Attach one end to  
the Master’s FP pins and the other end to the Target’s FP pins.  
Press the RIGHT switch to advance to the next screen.  
Note: Target thermostat must be powered by 24 VAC or batteries for field programming to  
occur.  
When the connection has been made correctly, the master thermostat will power up and the target will  
count from 6 down to 1. It will then display LOC confirming the data has been saved in memory.  
2. Temperature Differential (1°F to 5°F) (1°C to 3°C) – Set the number  
of degrees between your “setpoint” temperature and your “turn on”  
temperature.  
When all target thermostats have been completed, reinstall the master thermostat.  
Press the up and down buttons and the RIGHT switch simultaneously for 5 seconds to exit from the  
data transfer mode and to return the master thermostat to the OFF mode.  
Press the up or down button to set differential value.  
Press the RIGHT switch to advance to the next screen.  
Troubleshooting  
3. Heat Pump and Non-Heat Pump – Set to heat pump, or non-heat pump  
system. For heat pumps, there will be a compressor time delay for heating  
and cooling.  
Symptom  
Remedy  
No display  
Check for 24 VAC at thermostat; display is blank when 24 VAC  
is not present or if batteries are completely discharged  
• 1 = Heat pump system  
• 0 = Non-heat pump system  
System fan does not come on  
properly  
Verify wiring is correct, check Gas/Electric jumper position (see  
Parts Diagram)  
Press the up or down button to select.  
Press the RIGHT switch to advance to the next screen.  
All thermostat buttons are  
inoperative  
Verify 24 VAC is present; unit locks out when 24 VAC is not  
present with no batteries installed  
4. Lockout (0°F-8°F) (0°C-8°C) Select the number of degrees set  
temperature can be changed during keypad lockout  
No response with first button  
press  
First button press activates backlight only when back light is  
configured “ON” (see Configuration Mode Setting 9)  
Press the up or down button to select.  
Heat or Cool not working  
RC/RH jumper must be installed on single transformer systems  
For heat pumps, Non-HP jumper must be on HP pins  
Press the RIGHT switch to advance to the next screen.  
Thermostat turns on and off too  
frequently  
Adjust temperature differential  
(see Configuration Mode Setting 2)  
5. Maximum Heat Setpoint (45°F to 90°F) (7°C to 32°C)  
Adjust to control the maximum heat set temperature allowed.  
Press the up or down button to select.  
Fan runs continuously  
Slide FAN switch to auto to turn fan off  
Room temperature is not correct Calibrate thermostat (see Configuration Mode Setting 7)  
LOC displays when any button  
is pressed  
Thermostat has the button lockout function activated (see  
Lockout Feature and Configuration Mode Setting 4)  
Press the RIGHT switch to advance to the next screen.  
Heat or Cool not coming on  
Verify wiring is correct, verify RC/RH jumper is in place (for  
single transformer system)  
on display  
Replace batteries with two fresh “AAA” alkaline batteries  
Press Reset button once*  
6. Minimum Cool Setpoint (45°F to 90°F) (7°C to 32°C)  
Adjust to control the minimum cool set temperature allowed.  
Press the up or down button to select.  
Problem not listed above  
* Reset Button Function: Configuration settings are unchanged.  
Press the RIGHT switch to advance to the next screen.  
ONE-YEAR LIMITED WARRANTY  
7. Room Temperature Offset (+9°F to -9°F) (+5°C to -5°C)  
The Seller warrants its products against defects in material or workmanship for a period of one (1) year  
from the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a  
non-case credit for the purchase prices of the goods which are provided to be defective. The warranty and  
remedies set forth herein do not apply to any goods or parts thereof which have been subjected to misuse  
including any use or application in violation of the Seller’s instructions, neglect, tampering, improper storage,  
incorrect installation or servicing not performed by the Seller. In order to permit the Seller to properly  
administer the warranty, the Buyer shall: 1) Notify the Seller promptly of any claim, submitting date code  
information or any other pertinent data as requested by the Seller. 2) Permit the Seller to inspect and test  
the product claimed to be defective. Items claimed to be defective and are determined by Seller to be non-  
defective are subject to a $30.00 per hour inspection fee. This warranty constitutes the Seller’s sole liability  
hereunder and is in lieu of any other warranty expressed, implied or statutory. Unless otherwise stated  
in writing, Seller makes no warranty that the goods depicted or described herein are fit for any particular  
purpose.  
Adjust to calibrate displayed room temperature to match actual room  
temperature.  
Press the up or down button to select.  
Press the RIGHT switch to advance to the next screen.  
8. Maximum Cycles Allowed Per Hour (- -, 2-6)  
- - = as many as needed, 2-6 = maximum cycles/hour  
Press the up or down button to select.  
Press the RIGHT switch to advance to the next screen.  
9. Back Light (0 or 1) (Note: For SC2010L only)  
0 = Back light never on (best for long battery life)  
1 = Back light on when button pressed  
Press the up or down button to select.  
Patent No. 424,953  
7313 William Barry Blvd., North Syracuse, NY 13212  
(Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276  
To exit configuration mode, press both the LEFT and RIGHT switches for 2 seconds or slide the  
mode switch to heat or cool.  
LIAF019-1  
GeneralDetails
NameICM CONTROLS SC2010 N-L Non Programmable Electronic Thermostat Instruction Manual
MakeICM CONTROLS
LanguageEnglish
FiletypePDF (Download)
File size0.46 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

ICM CONTROLS SC2010 N-L Non Programmable Electronic Thermostat Instruction Manual