Honeywell N100 Series FocusPRO Thermostat Installation Guide
#ISU
3090
ISU Name
Backup Heat Droop
ISU Options (factory defaults are in bold)
0 = Comfort
2 °F to 15 °F (in 1 °F increments)
1.0 °C to 7.5 °C (in 0.5 °C increment).
0 (comfort) setting only available if Backup Heat (ISU 2180) is
set to Electric. TH1320U4002 only.
3110
Upstage Timer for Backup Heat
0 = Off
8 = 4 hours
1 = 30 minutes
2 = 45 minutes
3 = 60 minutes
4 = 75 minutes
5 = 90 minutes
6 = 2 hours
9 = 5 hours
10 = 6 hours
11 = 8 hours
12 = 10 hours
13 = 12 hours
14 = 14 hours
15 = 16 hours
7 = 3 hours
(TH1320U4002 only)
If 3090 = 0 and 2180 = 31, 3110 only has settings 0-3.
0 = Off
25 = 25°F (-4°C)
30 = 30°F (-1°C)
35 = 35°F (1.5°C)
40 = 40°F (4.5°C)
45 = 45°F (7°C)
50 = 50°F (10°C)
55 = 55°F (13°C)
60 = 60°F (15.5°C)
1 = -15°F (-26°C)
2 = -10°F (-23.5°C)
3 = -5°F (-20.5°C)
4 = 0°F (-18°C)
5 = 5°F (-15°C)
10 = 10°F (-12°C)
15 = 15°F (-9.5°C)
20 = 20°F (-6.5°C)
0 = Off
5 = 5°F (-15°C)
10 = 10°F (-12°C)
15 = 15°F (-9.5°C)
20 = 20°F (-6.5°C)
25 = 25°F (-4°C)
30 = 30°F (-1°C)
[0] = Off
Compressor Lockout / Balance Point
(TH1320U4002 only)
3120
3121
Outdoor Lockout Backup Heat
(TH1320U4002 only)
35 = 35°F (1.5°C)
40 = 40°F (4.5°C)
45 = 45°F (7°C)
50 = 50°F (10°C)
55 = 55°F (13°C)
60 = 60°F (15.5°C)
65 = 65°F (18.5°C)
13 = 65 min
3125
Lockout Fan after a Cool call
1 = 5 min
14 = 70 min
2 = 10 min
15 = 75 min
3 = 15 min
16 = 80 min
4 = 20 min
17 = 85 min
5 = 25 min
18 = 90 min
6= 30 min
19 = 95
7= 35 min
20 = 100 min
8= 40 min
21 = 105 min
9= 45 min
22 = 110 min
10 = 50 min
23 = 115 min
11 = 55 min
24 = 120 min
12 = 60 min
3140
3141
3150
3151
3160
3165
3240
Compressor Cycle Rate (Stage 1)
Compressor Cycle Rate (Stage 2)
Heating Cycle Rate (Stage 1)
Heating Cycle Rate (Stage 2)
Heating Cycle Rate Auxiliary Heat
Heating Cycle Rate Emergency Heat
Compressor Protection
1 – 6
1 – 6(TH1320U4002 only)
1 – 12
1 – 12 (TH1320U4002 only)
1 – 12 (TH1320U4002 only)
1 – 12 (TH1320U4002 only)
0 = Off
1 - 5 minutes
4100
4101
4102
4103
7110
Maximum Cool Setpoint
Minimum Cool Setpoint
Maximum Heat Setpoint
Minimum Heat Setpoint
50°F to 99°F
10°C to 37°C
50°F to 99 °F
10.0°C to 37.0 °C
40°F to 90°F
4.5°C to 32.0°C
32 °F to 50 °F (Default is 40 °F)
0 °C to 10.0 °C (Default is 4.5 °C)
0 = Off
1 = 10 Run Time Days
2 = 20 Run Time Days
3 = 30 Run Time Days
4 = 45 Run Time Days
5 = 60 Run Time Days
6 = 90 Run Time Days
7 = 120 Run Time Days
8 = 150 Run Time Days
9 = 30 Calendar Days
Air Filter
Replacement Reminder
10 =45 Calendar Days
11 =60 Calendar Days
12 =75 Calendar Days
13 =3 Calendar Months
14 =4 Calendar Months
15 =5 Calendar Months
16 =6 Calendar Months
17 =9 Calendar Months
18 =12 Calendar Months
19 =15 Calendar Months
11
| General | Details |
|---|---|
| Name | Honeywell N100 Series FocusPRO Thermostat Installation Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 1.36 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell D1-528 Direct Thermostat Installation Guide

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell Lyric T5 Wi-Fi Thermostat Installation Guide