Danfoss KP 61 Temperature Switches Thermostat Installation Guide
Setting
For KP 61, KP 62, KP 63, KP 68, KP 69, KP 71,
KP 73, KP 75, KP 77, KP 79 and KP 81 w/auto reset
KP 61 and KP 71 w/man. reset
1. Adjust range spindle to desired
HIGH SET POINT (use hand knob)
1. Adjust range spindle to desired
LOW SET POINT
2. Adjust differential spindle to
desired DIFFERENTIAL
2. DIFFERENTIAL is fixed.
Value printed on scale plate
Note:
To find correct differential, see “Determination of differential”
HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT
Example:
HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT
Example:
HSP
7 °C
(45 °F)
–
–
DIFF.
5 °C
(10 °F)
=
=
LSP
2 °C
(35 °F)
HSP
3 °C
(37.4 °F)
–
–
DIFF.
3 °C
(5.4 °F)
=
=
LSP
0 °C
(32 °F)
KP w/ hand switch
CAUTION:
•
•
•
Hand switch breaks circuit by micro contact gab.
Use hand switch for service on refrigeration parts only
Cut out main switch before service on electrical parts
Switch position
Aut.
Contacts position
Automatic control operation
µ Stop
1 and 2 are closed
4
DKRCC.PI.CA0.C1.22 / 520H8304
© Danfoss A/S (AC-MCI / jmn), 2013-11
| General | Details |
|---|---|
| Name | Danfoss KP 61 Temperature Switches Thermostat Installation Guide |
| Make | Danfoss |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.74 MB |

Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide

Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide

Danfoss UT 72-UT 73 Universal Thermostat Installation Guide

Danfoss ECtemp 530 Electronic Thermostat Installation Guide

Danfoss 014G0251 Eco Radiator Thermostat User Guide

Danfoss RET230P Electronic Thermostat Instruction Manual

Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide

Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide

Danfoss RET1000 Series Electronic Thermostat User Guide